taBle 1. Branch cIrcuIt wIre sIZe.

These  ampacities  relate  only  to  conductors 

described  in  Table  310-13  of  the  NEC. 

For  ambient  temperatures  over  30°C,  see 

Correction Factors, Note 13 in the NEC.

electrIcal

General

Check the water heater model and rating plate information against 

the  characteristics  of  the  branch  circuit  electrical  supply.  Do  not 

connect the heater to an improper source of electricity. 

Voltage applied to the heater should not vary more than +5% to -10% 

of the model and rating plate marking for satisfactory operation.

Do 

not 

energize the branch circuit for any reason before the water 

heater tank is filled with water. Doing so may cause the heating 

elements to fail.

The factory wiring is attached to a terminal block on the unit. The 

branch circuit is connected to the block through an opening provided 

on the heater. Factory terminal block has 500 MCM maximum copper 

wire size capacity in each opening. If apparent field wire size is over 

500 MCM multiple terminal blocks will be furnished. If other opening 

sizes are desired they should be specified when unit is ordered.

The  installation  must  conform  to  these  instructions  and  the  local 

 

code authority having jurisdiction. Grounding and electrical wiring 

connected to the water heater must also conform to the National Electrical 

Code, NFPA 70. This publication is available from The National Fire 

 

Protection Association, 1 Batterymarch Park, Quincy, MA 02269.

Branch cIrcuIt

The branch circuit wire size should be established through reference 

to the 

nec (national electrical code)

 or other locally approved 

sources in conjunction with the water heater amperage rating.. Wire 

rated at 75°C should be used. For convenience, portions of the wire 

size tables from the Code are reproduced in Table 1. It is suggested 

the electrician size the branch circuit at 125 percent of the heater 

rating and further increase wire size as necessary to compensate 

for voltage drop in long runs. Voltage drop should not exceed 3% 

at the water heater.

heater cIrcuIts

The water heater’s electrical components are pictured and identified 

by the Features and Components illustrations on pages 6 and 7. 

The model and rating plate illustration identifies the heater electrical 

characteristics. The heater has two electrical circuits:

Control Circuit: 120V circuit containing all safety and control devices.  

The control circuit operates the contactors in the power circuit.

Power Circuit: High voltage, single or three phase circuit that carries 

the heating element load.

The following section and pages describe the water heater circuits 

and includes wiring diagrams. 

control cIrcuIts

The heater is equipped with one of the following control circuits, 

resulting in:

A.  Thermostats (mechanical)... where all of the heating elements

 

  are  switched  on/off  by  one  or  more  thermostats.  Heaters

 

  with thermostat control are adjusted as described in TEMPERATURE

 

  REGULATION section of this manual, see Page 14.
B.  Step controlled element operation...where elements are staged

 

  on/off  individually  or  in  groups  rotationally  by  the  controller.

 

  An optional feature is modulation which operates in conjunction with

 

  the staged on/off element operation.
C.  Sequencer... operates in conjunction with a thermostat (mechanical).

 

  The sequence is activated by a thermostat then the sequence

 

  switches on the heater elements in 3 sequences (multiple elements

 

  and contactors are required). 

 Additional instructional literature is provided with heaters equipped 

with modulating solid state step control or a sequencer.   
All control circuits are operated on single-phase 120 volt current.
Control circuit wiring is 14 Awg, AWM (Appliance Wiring Material) 

type, rated 600 volts, 105°C.
Standard equipment includes control circuit fusing.

power cIrcuIt

Power circuit wiring is type THHN (or equivalent) rated 600 volts, 

105°C, sized as necessary.
The following wiring diagrams are included in this manual to show 

typical arrangements of electrical components in the control and power 

circuits by voltage and phase characteristics. They are to be used as a 

reference by the installer or servicer in performing their work. An actual 

diagram of the water heater wiring is furnished with the heater.

Содержание DVE-150, DHE-200

Страница 1: ...ce COMMERCIAL ELECTRIC WATER HEATERS ASME Thank you for buying this energy efficient water heater fromA O Smith Water Products Company We appreciate your confidence in our products MODELS DVE 150 THRU...

Страница 2: ...hat of a Qualified Agency as defined by ANSI below in the field involved Installation skills such as plumbing air supply venting gas supply electrical supply are required in addition to electrical tes...

Страница 3: ...3 GENERAL SAFETY When servicing this unit verify the power to the unit is turned off prior to opening the control cabinet door...

Страница 4: ...chnician 4 Carefully plan your intended placement of the water heater Examine the location to ensure the water heater complies with the Locating the New Water Heater section in this manual INSTALLATIO...

Страница 5: ...5 dimensions and capacities data...

Страница 6: ...6 FEATURES AND COMPONENTS NOTE Your actual configuration may vary DVE Vertical Water Heater typical...

Страница 7: ...7 FEATURES AND COMPONENTS NOTE Your actual configuration may vary DHE Horizontal Water Heater typical...

Страница 8: ...BILITY EQUIVALENT TO THAT OF A QUALIFIED AGENCY PAGE 2 IN THE FIELD INVOLVED PLUMBING AND ELECTRICAL WORK IS REQUIRED general The installation must conform to these instructions and the local code aut...

Страница 9: ...g the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 and the ASME code If replaced the valve must meet the requirements of local codes but not less than a combination temperat...

Страница 10: ...ater heater Heater Circuits The water heater s electrical components are pictured and identified by the Features and Components illustrations on pages 6 and 7 The model and rating plate illustration i...

Страница 11: ...11 electrical and recoveries data TABLE 2...

Страница 12: ...12 WIRING DIAGRAMS TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS 300 600 VOLTS STANDARD THERMOSTAT CONTROL WIRING WYE...

Страница 13: ...13 WIRING DIAGRAMS TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS 208 240 VOLTS STANDARD THERMOSTAT CONTROL WIRING DELTA...

Страница 14: ...e manually de energized if full capacity is not needed Filling the Water Heater To fill the water heater with water 1 Turn off the electrical disconnect switch 2 Turn off pilot toggle switch 3 Close t...

Страница 15: ...pped with a sacrificial anode Anodes protect the glass lined tank from corrosion by sacrificing themselves through electrolysis When the anode material is consumed there is no more protection and corr...

Страница 16: ...re of the water is increased more scale is deposited on the elements 3 Mineral level characteristics of the water supply Regardless of water treatment the elements should be examined regularly STRANGE...

Страница 17: ...kes strange sounds 1 Sediment or lime scale accumulations on the elements causes sizzling and hissing noises when the heater is operating The sounds are normal however the tank bottom and elements sho...

Страница 18: ...he owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipp...

Страница 19: ...19 NOTES...

Страница 20: ...20 www aosmithwaterheaters com...

Отзывы: