instructions for installation of the valves. Before changing the factory 

setting on the thermostat, read the entire “Temperature Regulation” 

section in this manual.
It is recommended that lower water temperatures be used to avoid 

the risk of scalding. It is further recommended, in all cases, that the 

water temperature thermostat be set for the lowest temperature 

which satisfies your hot water needs. This will also minimize water 

scale formations on the heating elements and provide the most 

energy efficient operation of the water heater. Thermostat(s) are 

factory set at 120°F (49°C) unless specified differently by state 

requirements.

KEEPING THE THERMOSTAT SETTING AT 120°F WILL REDUCE 

THE RISK OF SCALDS.
Figure  1  shows  the  approximate  time-to-burn  relationship  for 

normal adult skin.

teMperature adjustMent

Always close and lock the cabinet door after making a temperature 

adjustment. Turn on electricity.

therMostat teMperature control

When the water heater 

cIrculatInG puMp

 (optional) is provided, 

horizontal and vertical model heater thermostats may be set to 185°F 

if dishwasher rinse water is supplied by the heater.

General

Water heater maintenance includes inspection and testing of the 

Temperature Pressure Relief Valve, periodic tank flushing and 

cleaning, and removal of lime scale from the heating elements. 

Where used, water heating system circulating pumps should 

be oiled.

Tank  flushing  and  circulating  pump  lubrication  should  be 

performed in accordance with the maintenance schedule, see 

Table 6 on page 16. Tank sediment removal and element lime 

scale removal must be performed when needed as determined 

by periodic inspections.

anode InspectIon and replaceMent

This  water  heater  is  equipped  with  a  sacrificial  anode. Anodes 

protect  the  glass-lined  tank  from  corrosion  by  sacrificing 

themselves  through  electrolysis.  When  the  anode  material  is 

consumed, there is no more protection and corrosion of the tank 

accelerates.

Inspection of the anode every 6 to 12 months allows you to identify 

a spent anode and replace it. Replace the anode when its diameter 

is 3/8” (1 cm) of an inch, or annually which ever is first. Aggressive, 

very  hot  and  softened  water  causes  rapid  consumption  of  the 

anode requiring frequent inspections. Anodes are available from 

your distributor or A.O. Smith.

MaIntenance

wIthout

 the circulating pump, horizontal model heaters should be 

set not higher than 165°F. Vertical models may be set as desired, 

not to exceed 185°F.

Where 

MultIple therMostats

 are used on a vertical model 

heater, they may all be set at the same temperature or 2° to 4°F apart 

to achieve “step control”. The bottom thermostat is set the hottest 

and the top thermostat the coolest.

 

 Temperature  

Time to Produce 2nd & 3rd 

 

Settings 

Degree Burns on Adult Skin 

 

180°F (82°C)

 

Nearly Instantaneous

 

160°F (71°C) 

About 1/2 second

 

150°F (66

°C) 

About 1-1/2 seconds

 

140°F (60°C) 

Less than 5 seconds

 

130°F (54°C) 

About 30 seconds 

 

120°F (49°C) 

More than 5 minutes

 

80°F (27°C) 

- - - - - - - - - - - - - - - - 

fIGure 1.

teMperature control (MechanIcal therMostat)

fIGure 2a.

solId state step control (wIth or wIthout ModulatIon)

Additional  instructional  literature  is  provided  with  the  heater 

sequencer control.

hIGh teMperature deVIces

A manual reset temperature high limit is in the control circuit 

in addition to the automatic device previously described. The 

contacts open at 210°F and must be manually reset after the 

temperature  hi-limit  switch  has  been  activated  and  the  water 

temperature is below 210°F.

The  reset  button  is  located  on  the  temperature  hi-limit  in  the 

control  cabinet  of  the  heater.  Disconnect  the  power  before 

opening the door to push the reset button.

Содержание DVE-150, DHE-200

Страница 1: ...ce COMMERCIAL ELECTRIC WATER HEATERS ASME Thank you for buying this energy efficient water heater fromA O Smith Water Products Company We appreciate your confidence in our products MODELS DVE 150 THRU...

Страница 2: ...hat of a Qualified Agency as defined by ANSI below in the field involved Installation skills such as plumbing air supply venting gas supply electrical supply are required in addition to electrical tes...

Страница 3: ...3 GENERAL SAFETY When servicing this unit verify the power to the unit is turned off prior to opening the control cabinet door...

Страница 4: ...chnician 4 Carefully plan your intended placement of the water heater Examine the location to ensure the water heater complies with the Locating the New Water Heater section in this manual INSTALLATIO...

Страница 5: ...5 dimensions and capacities data...

Страница 6: ...6 FEATURES AND COMPONENTS NOTE Your actual configuration may vary DVE Vertical Water Heater typical...

Страница 7: ...7 FEATURES AND COMPONENTS NOTE Your actual configuration may vary DHE Horizontal Water Heater typical...

Страница 8: ...BILITY EQUIVALENT TO THAT OF A QUALIFIED AGENCY PAGE 2 IN THE FIELD INVOLVED PLUMBING AND ELECTRICAL WORK IS REQUIRED general The installation must conform to these instructions and the local code aut...

Страница 9: ...g the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 and the ASME code If replaced the valve must meet the requirements of local codes but not less than a combination temperat...

Страница 10: ...ater heater Heater Circuits The water heater s electrical components are pictured and identified by the Features and Components illustrations on pages 6 and 7 The model and rating plate illustration i...

Страница 11: ...11 electrical and recoveries data TABLE 2...

Страница 12: ...12 WIRING DIAGRAMS TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS 300 600 VOLTS STANDARD THERMOSTAT CONTROL WIRING WYE...

Страница 13: ...13 WIRING DIAGRAMS TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS 208 240 VOLTS STANDARD THERMOSTAT CONTROL WIRING DELTA...

Страница 14: ...e manually de energized if full capacity is not needed Filling the Water Heater To fill the water heater with water 1 Turn off the electrical disconnect switch 2 Turn off pilot toggle switch 3 Close t...

Страница 15: ...pped with a sacrificial anode Anodes protect the glass lined tank from corrosion by sacrificing themselves through electrolysis When the anode material is consumed there is no more protection and corr...

Страница 16: ...re of the water is increased more scale is deposited on the elements 3 Mineral level characteristics of the water supply Regardless of water treatment the elements should be examined regularly STRANGE...

Страница 17: ...kes strange sounds 1 Sediment or lime scale accumulations on the elements causes sizzling and hissing noises when the heater is operating The sounds are normal however the tank bottom and elements sho...

Страница 18: ...he owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipp...

Страница 19: ...19 NOTES...

Страница 20: ...20 www aosmithwaterheaters com...

Отзывы: