A TYPICAL HEATER INSTALLATION - FIGURE 10

Refer to pages 2, 3, and 4 in this manual for more information about
burner series numbers and characteristics for adaptability to the following
systems.

SYSTEM TYPES

Single Stage, Supply Line Only:  The bottom of the oil storage tank must
be above the level of the fuel unit, fig. 11.  The fuel oil will flow by gravity
to the burner.  A single pipe is run between the tank and fuel unit.  Burner
Series No. 940 is from this type of service as shipped (the bypass plug is
not installed).

         

A GRAVITY FEED, SUPPLY LINE ONLY, INSTALLATION

FIGURE 11

If the bottom of the oil tank is at least 2 inches (50.8 mm) higher than the
plug opening at which the supply line connects to the fuel pump, a single-
line gravity-feed system with 3/8" O.D. tubing may be used with a maximum
run length of 100 feet.

A two stage pump may be used on one line, gravity feed
installations.  The pump will function as a single stage unit when
the by-pass plug is not installed.

Single Stage, Supply and Return Lines.  This type of system,
fig. 12, is self-priming.  Burner Series No. 940 with by-pass plug
field installed, is for this type of service.

If the  tank bottom is no lower than 10 feet below the plug, a single stage
pump may be used but, it must be a two line system with maximum
tubing runs (which includes lift) as shown in Table 6.

A SINGLE STAGE (LOW LIFT), SUPPLY AND RETURN

 LINE INSTALLATION - FIGURE 12

TABLE  6

  Distance                  Max.

Distance                  Max.

Tank                 Run length

Tank                Run Length

Bottom                  Ft. (M)

Bottom                    Ft. (M)

Below

Below

Pump

3/8"

1/2"

Pump

3/8"

1/2"

Plug

O.D.

O.D.

Plug

O.D.

O.D.

Ft. (M)

Tubing

Tubing

 Ft. (M)

Tubing

Tubing

1 (0.3)

66 (20.1) 100 (30.4)

6 (1.8)

36 (10.9)

100 (30.4)

2 (0.6)

55 (16.7) 100 (30.4)

7 (2.1)

31 (9.4)

100 (30.4)

3 (0.9)

50 (15.2) 100 (30.4)

8 (2.4)

26 (7.9)

100 (30.4)

4 (1.2)

45 (13.7) 100 (30.4)

9 (2.7)

21 (6.4)

83 (25.2)

5 (1.5)

40 (12.1) 100 (30.4)

10 (3.0)

16 (4.8)

64 (19.5)

Two Stage, Supply and Return Lines:   This system, fig. 13, is required
when long lines and high lifts (requiring up to 20" of vacuum and 10'
vertical lift) are encountered. Burner Series No. 941 is used in this service.
Bypass plug must be installed.

A TWO STAGE (HIGH LIFT), SUPPLY AND RETURN

LINE INSTALLATION - FIGURE 13

If the tank(s) bottom is lower than the plug by more than 10 feet, a two
stage pump with a two line system must be used with  maximum tubing
runs (which includes lift) as shown in Table 7.

TABLE 7

  Distance                  Max.

Distance                  Max.

Tank                Run length

Tank               Run Length

Bottom                   Ft. (M)

Bottom                  Ft. (M)

Below

Below

Pump

3/8"

1/2"

Pump

3/8"

1/2"

Plug

O.D.

O.D.

Plug

O.D.

O.D.

Ft. (M)

Tubing

Tubing

Ft. (M)

Tubing

Tubing

1 (0.3)

74 (22.5) 100 (30.4)

9 (2.7)

51 (15.5)

100 (30.4)

2 (0.6)

71 (21.6) 100 (30.4)

10 (3.0)

48 (14.6)

100 (30.4)

3 (0.9)

69 (21.0) 100 (30.4)

11 (3.3)

45 (13.7)

100 (30.4)

4 (1.2)

66 (20.1) 100 (30.4)

12 (3.6)

42 (12.8)

100 (30.4)

5 (1.5)

63 (19.2) 100 (30.4)

13 (3.9)

39 (11.8)

100 (30.4)

6 (1.8)

60 (18.2) 100 (30.4)

14 (4.2)

37 (11.2)

100 (30.4)

7 (2.1)

57 (17.3) 100 (30.4)

15 (4.5)

34 (10.3)

100 (30.4)

8 (2.4)

54 (16.4) 100 (30.4)

MULTIPLE HEATER FUEL LINES

Where two  or more heaters form a water heating system, each burner
shall have an entirely separate oil supply line from the tank to the burner.

BURNER INSTALLATION

GENERAL

An oil Burner Certificate  is packed with the oil burner. Following the burner
manual installation the necessary tests shall be performed and the results
recorded on the certificate, see BURNER CERTIFICATE. The certificate
and this instruction manual must be left with the user for future reference.

Check to be certain the heater and burner model numbers are alike and
the oil pump characteristics are proper for the job. See IDENTIFICATION,
page 3.

Содержание COF 245

Страница 1: ...MMERCIAL OIL FIRED WATER HEATER FOR HOT WATER SUPPLY Installation Service Maintenance MODELS COF 199 THRU 700A CAUTION TEXTPRINTEDOROUTLINEDINREDCONTAINSINFORMATIONRELATIVE TO YOUR SAFETY PLEASE READ...

Страница 2: ...0 2750 2357 2063 1833 1650 1500 1375 1269 1179 COF 700 000 69 80 GPH 1677 1341 1118 958 838 745 671 610 559 516 479 700 700A 205 261 LPH 6347 5077 4231 3627 3173 2821 2539 2308 2116 1953 1813 All tank...

Страница 3: ...listed by Underwriters Laboratories Inc Accordingly the burner bears one of the UL labels indicating periodic inspection of the production of this equipment All ASME tanks are built to the standards...

Страница 4: ...HEATER NEVER TOUCH ELECTRICAL COMPONENTSWITHWETHANDSOFWHENSTANDINGINWATER WHEN REPLACING FUSESALWAYS USE THE CORRECT SIZE FOR CIRCUIT If it is necessary to reset the safety control depress red button...

Страница 5: ...These materials are corrosive at very low concentration levels with little or no odor to reveal their presence Products of this sort should not be stored near the heater Also air which is brought in c...

Страница 6: ...10 254 These models are factory supplied with a flue reducer which should be installed on the top cover In venting systems where a continuous or intermittent back positive draft is found to exist the...

Страница 7: ...shutoff system actuated by high water temperature CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in th...

Страница 8: ...100 30 4 7 2 1 31 9 4 100 30 4 3 0 9 50 15 2 100 30 4 8 2 4 26 7 9 100 30 4 4 1 2 45 13 7 100 30 4 9 2 7 21 6 4 83 25 2 5 1 5 40 12 1 100 30 4 10 3 0 16 4 8 64 19 5 Two Stage Supply and Return Lines...

Страница 9: ...ainst electrical shock from the heater or water system 3 All burners have intermittent ignition as defined by UL ignition is on during the time the burner is on and off when the burner is off 4 Do not...

Страница 10: ...includes a circulating pump it may need to be lubricated before operated The tube of lubricant supplied with the pump includes directions for use Field installed circulating pumps should be all bronze...

Страница 11: ...hermostat temperature dial fig 17 is accessible by taking off the access cover and removing the control cover The dial is adjustable and may be set for 120 48 9 C to 180 F 82 2 C water temperature but...

Страница 12: ...g condition To check a relief valve lift the lever at the end of the valve several times The valve should seat properly and operate freely If water does not flow remove the valve and inspect for obstr...

Страница 13: ...is the standard 5 gallon container for UN LIME or it is available as a deliming kit with UN LIME hose and fittings Contact your dealer distributor or the A O Smith Water Products Company Figure 18 il...

Страница 14: ...n the motor oil cups SOOT REMOVAL Soot must be removed semi annually from the heater and flow passages to insure efficient operation of the heater A TYPICAL HEATER FLUEWAYAND FLUE BAFFLE FIGURE19 1 Re...

Страница 15: ...ATION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES...

Страница 16: ...SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUP...

Страница 17: ...ED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER S...

Страница 18: ...URES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTU...

Страница 19: ...CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP CONTROL SHOULD BE SET AT 185 F 85 C NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE...

Страница 20: ...units with the higher water flow may have a shortened life Unions and T P valves shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by comp...

Страница 21: ...water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve leakage It is often caused by a closed system If a check valve is in th...

Страница 22: ...n must be reset before trying again for ignition When this occurs allow about 5 minutes for safety heater to cool before depressing the red safety button Depress red button one time only If burner doe...

Страница 23: ...ting screws slightly and shift Noisy fuel pump in different positions until noise is eliminated Operation Retighten mounting screws Air in inlet line Check all connections Use only good flare fittings...

Страница 24: ...l at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater...

Страница 25: ...L COF 199 245 315 385 455 700 AND COF 315A 385A 455A 700A SERIES 940 941 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 WWW HOTWATER C...

Страница 26: ...519 Wiring Diagram 195056 000 195056 000 195056 000 195056 000 195056 000 195056 000 17 Gasket Skirt Ring 76443 76443 76443 76443 76443 76443 18 Insulation Foil Faced 41175 41175 41175 41175 41175 411...

Страница 27: ...27 NOTES...

Страница 28: ...28...

Страница 29: ...pr sent manuel pour r duire au minimum le risque d incendie ou d explosion et pr venir les blessures la mort ou les dommages mat riels Ne pas entreposer ni utiliser d essence ou d autres vapeurs et l...

Страница 30: ...838 745 671 610 559 516 479 700 700A 205 261 LPH 6347 5077 4 231 3627 3 173 2821 2 539 2 308 2116 1953 1813 Tous les r servoirs sont test s une pression de service de 320 lb po2 Bas sur l utilisation...

Страница 31: ...ur porte l une des tiquettes UL qui atteste que cet appareil a subi des inspections p riodiques au cours de sa fabrication Tous les r servoirs ASME sont conformes aux normes de la section IV du code d...

Страница 32: ...ECTRIQUE DU CHAUFFE EAU OU PROXIMIT DE CELUI CI NE JAMAIS TOUCHER DES COMPOSANTS LECTRIQUES AVEC LES MAINS MOUILL ES OU AVEC LES PIEDS DANS L EAU LORS DU REMPLACEMENT DE FUSIBLES UTILISER TOUJOURS LE...

Страница 33: ...les produits chimiques pour piscines le chlorure de calcium le chlorure de sodium les cires et les produits chimiques industriels peuvent provoquer une telle corrosion Ces substances sont corrosives...

Страница 34: ...315A 8 203 2 COF 385 385A 8 203 2 COF 455 455A 8 203 2 COF 700 700A 10 254 Ces mod les sont livr s avec un raccord de r duction d vent installer sur le couvercle sup rieur S il se produit un refoulem...

Страница 35: ...st me en circuit ferm se forme si un dispositif antiretour clapet de retenue un d tendeur de pression ou un dispositif similaire est install dans la conduite d eau froide entre le chauffe eau et la ca...

Страница 36: ...ompe 3 8 po de 1 2 po de pi m diam ext diam ext pi m diam ext diam ext 1 0 3 66 20 1 100 30 4 6 1 8 36 10 9 100 30 4 2 0 6 55 16 7 100 30 4 7 2 1 31 9 4 100 30 4 3 0 9 50 15 2 100 30 4 8 2 4 26 7 9 10...

Страница 37: ...r sultant d un contact avec le chauffe eau ou la tuyauterie 3 Tous les br leurs disposent d un allumage intermittent tel que d fini par UL l allumage est actif pendant que le br leur est en marche et...

Страница 38: ...utilis e il peut tre n cessaire de la lubrifier avant de la mettre en marche Le tube de lubrifiant fourni avec la pompe contient le mode d emploi Seules les pompes de circulation tout bronze sont rec...

Страница 39: ...17 L un des capteurs se trouve pr s du sommet du r servoir et l autre pr s du centre Le thermostat est r gl en usine sa position la plus basse Le cadran de r glage du thermostat est accessible en ret...

Страница 40: ...ermique Pour ce faire actionner plusieurs fois le levier l extr mit de la soupape Celle ci devrait tre bien appuy e et fonctionner sans entrave Si l eau ne circule pas enlever la soupape et v rifier s...

Страница 41: ...uple et des raccords Pour plus de d tails communiquer avec le fournisseur le distributeur ou directement avec A O Smith Water Products Company La figure 18 pr sente la plupart des tapes de d tartrage...

Страница 42: ...paliers et 10 12 gouttes dans le godet huileur du moteur ENL VEMENT DE LA SUIE Enlever la suie tous les six mois du chauffe eau et du conduit des gaz de combustion afin d assurer un fonctionnement eff...

Страница 43: ...ER LA TEMP RATURE DE CONSIGNE NE DOIT PAS D PASSER LES VALEURS CONSID R ES COMME S CURITAIRES POUR LES APPAREILS UTILISATEURS VOIR LASECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RATU...

Страница 44: ...APPAREILS UTILISATEURS VOIR LASECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RA TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUILLA...

Страница 45: ...APPAREILS UTILISATEURS VOIR LA SECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RA TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUIL...

Страница 46: ...TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUILLANTAGE DANS LES CONDUITES D EAU QUIALIMENTENT DES APPAREILS RACCORDER LA CONDUITE DE CIRCULATION...

Страница 47: ...EN T NON ISOL PLAC AU DEL DU T DE PR L VEMENT DU LAVE VAISSELLE DANS LABOUCLE DE D SINFECTION R GLER LA TEMP RATURE DE CONSIGNE 185 F 85 C NOTA3 AJUSTER LE ROBINET TOURNANT DE MANI RE CE QUE LE D BIT...

Страница 48: ...teur Les dimensions indiqu es s appliquent l espace minimal occup par les chauffe eau Pr voir de l espace pour l entretien l avant des appareils DANGER LA TEMP RATURE DE CONSIGNE NE DOIT PAS D PASSER...

Страница 49: ...ses causes Pression de l eau trop lev e Temp rature de l eau trop lev e Soupape de d charge d fectueuse Une fuite la sortie de la soupape de d charge est habituellement caus e par une pression trop le...

Страница 50: ...iron cinq minutes pour laisser le dispositif de s curit se refroidir avant d enfoncer le bouton rouge Enfoncer le bouton rouge une seule fois V rifier la chambre de combustion si le br leur ne fonctio...

Страница 51: ...us de montage de la pompe mazout et placer la pompe dans diff rentes positions jusqu l limination du bruit Resserrer les crous de montage Fonctionne Air dans la conduite d alimentation V rifier tous l...

Страница 52: ...e remplacement du chauffe eau ou des pi ces d fectueuses Tous les autres frais sont la charge du propri taire Ces frais peuvent inclure sans s y limiter a Les frais de main d uvre pour l entretien la...

Страница 53: ...5 315 385 455 et 700 ET MOD LES COF 315A 385A 455A et 700A S RIE 940 941 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 T L PHONE 1 800 433 2545 T L COPIEUR 1 800 433 2515 WW...

Страница 54: ...56 000 195056 000 17 Joint anneau de la jupe d isolation 76443 76443 76443 76443 76443 76443 18 Isolation rev tement m tallique 41175 41175 41175 41175 41175 41175 19 Chemise 193062 193062 193062 1930...

Страница 55: ...27 NOTES...

Страница 56: ...28...

Отзывы: