1.2  Technical safety equipment

1.2.1 Control box

The temperature control for the water heater is 

situated in the control box (see figure 1), which is 

fitted to the heater cover.

The water heater has been fitted with three 

thermostats:

- a control thermostat,

- a high-limit thermostat

- an overheating cut-out.

The control thermostat is the thermostat by means 

of which the desired water temperature is set. The 

high-limit thermostat acts as a safeguard against 

excessive water temperatures at the top of the 

heater, if as a result from a certain draining pattern 

(frequently draining of small quantities), stratification 

of the water temperatures in the heater occur. If both 

the control thermostat and the high-limit thermostat 

fail the overheating cut-out will automatically shut 

down the water heater.

4

1. GENERAL

1.1

Description of the heater

Construction of the heater is in accordance with the

European standards for gas-fired water heaters for

sanitary use (EN 89). The heaters therefore comply with

the European Guidelines for Gas Heaters and are

permitted to carry the CE mark.

They are atmospheric heaters suitable for both gas-fired

and oil-fired ventilator burners

(heater category B23).

The heaters are suitable for use with a working pressure

of up to 8 bar. The cylindrical tank is made from sheet

steel containing a number of vertically placed flue tubes.

For protection against corrosion, the inside of the tank is

glass lined. The tank is also fitted with a number of

magnesium anodes for extra protection against

corrosion. A thick PU insulating layer between the tank

and the steel jacket helps to reduce heat loss.

When the heater is completely filled with water, it is

under continuous mains water pressure. When hot water

is drained from the heater, cold water immediately

enters the heater. For effective heat transfer, flue baffles

have been included in the flue tubes. Heat from the flue

gases is transferred to the water by means of radiation

and convection.

1.2

Technical safety equipment

1.2.1 Control box

The temperature control for the water heater is situated in

the control box (see figure 1), which is fitted to the heater

cover.

The water heater has been fitted with three thermostats:

- a control thermostat,

- a high-limit thermostat

- an overheating cut-out.

The control thermostat is the thermostat by means of

which the desired water temperature is set.

The high-limit thermostat acts as a safeguard against

excessive water temperatures at the top of the heater,

if as a result from a certain draining pattern (frequently

draining of small quantities), stratification of the water

temperatures in the heater occur. If both the control

thermostat and the high-limit thermostat fail

the overheating cut-out will automatically shut down

the water heater.

The overheating cut-out interrupts the current supply

to the burner, as a result of which the gas valves of the

gas block will close.

Figure 1: Control box COF

Figure 1: Control box COF

The overheating cut-out interrupts the current supply 

to the burner, as a result of which the gas valves of 

the gas block will close.

The control thermostat can be set between 40°C 

and 80°C by means of the temperature control knob. 

The high-limit thermostat switches at 84°C, the 

overheating cut-out at 95°C. 

The control thermostat’s sensor is located in the 

lower immersion well in the control box; the sensors 

of the high-limit thermostat and overheating cut-out 

are located in the immersion well at the top of the 

heater.

If the overheating cut-out is activated, it must be 

manually reset. This is only possible when the 

temperature at the top of the heater has dropped 

below 89°C.

The control box is fitted with an ‘ON/OFF’ switch 

(‘I/0’). In position ‘I’ the ventilator burner is controlled 

on the basis of the heat demand from the control 

thermostat. In position ‘0’ the heater is switched off.

Содержание COF 199

Страница 1: ...Manuel d installation Mode d emploi Manual d entretien Manual de Instalaci n Usuario y Servicio Manual de Instala o Utiliza o e Manuten o Manuale Installazione d uso e manutenzione Instrukcja Serwisu...

Страница 2: ...on and or a fire and can cause material and or physical injuries An accredited installer must install the heater and commission it according to the locally valid requirements The heater may only be in...

Страница 3: ...2 1 Filling the heater 19 2 2 2 Turning on the burner 19 2 3 Shutting down 19 2 4 Usage temperature control 19 2 5 Setting the nominal load 20 2 6 Conversion to another gas type 20 2 7 Maintenance 20...

Страница 4: ...he heater is completely filled with water it is under continuous mains water pressure When hot water is drained from the heater cold water immediately enters the heater For effective heat transfer flu...

Страница 5: ...of against etween the tank at loss h water it is e When hot water mmediately nsfer flue baffles eat from the flue ans of radiation eater is situated in itted to the heater hree thermostats t by means...

Страница 6: ...00 1700 1720 1650 1650 1770 P mm 620 620 620 620 620 755 R mm 540 540 585 605 605 670 S mm 1700 1700 1700 1630 1630 1750 1 Cold water inlet Rp 1 Rp 1 Rp 1 Rp 1 Rp 1 Rp 1 2 Hot water outlet Rp 1 Rp 1 R...

Страница 7: ...7 Figure 2 Dimensions IMD 0011...

Страница 8: ...unted burner must be less than the diameter of the heater s combustion chamber This diameter is 510 mm for all heaters For the COF 455 and COF 700 a starting load of 120 kW at maximum according to EN...

Страница 9: ...2 mg kWh GCV 76 79 81 86 90 97 PROPANE DATA G30 50 mbar Burner model BS 2 BS 2 BS 3 BS 3 BS 3 BS 3 Burner type 912 T1 912 T1 913 T1 913 T1 913 T1 913 T1 Nominal load lower value kW 60 75 90 115 135 17...

Страница 10: ...7 Rp 1 ISO 7 Rp 1 ISO 7 Rp 1 ISO 7 Rp 1 Drain valve 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT Anode 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT T P connection 1 11 5 NPT 1 11 5 NPT 1 11 5 NPT 1 11 5 NP...

Страница 11: ...Riello front mounted burners is The values above are recommended settings and have been determined under laboratory conditions The air proving switch s switching point must be set during the commissio...

Страница 12: ...mended settings and have been determined under laboratory conditions The gas pressure switch s switching point must be set during the commissioning of the water heater Please make sure that the burner...

Страница 13: ...to the burner s instruction manual The setting of the burner head for Riello front mounted burners is as follows Gas fired burner GAS G20 GAS G25 GAS G30 GAS G31 COF 199 2 2 2 2 2 COF 245 3 3 3 3 3 C...

Страница 14: ...lve Gas fired burner Oil fired burner GAS G20 GAS G25 GAS G30 GAS G31 COF 199 1 6 1 7 1 9 1 6 2 4 COF 245 2 1 2 5 2 3 2 1 3 5 COF 315 1 9 1 8 1 5 1 5 1 7 COF 385 2 9 2 9 2 5 2 5 2 7 COF 455 3 1 3 1 3...

Страница 15: ...nt 2 1 1 Installation These water heaters must be installed by a qualified competent installer in accordance with the following standards and regulations Gas safety installation and use regulations 19...

Страница 16: ...capacity of greater volume than the hourly recovery rate of the water heater s which it supplies The minimum actual capacity is 50 gallons or 227 litres see figure 3 3 T P valve 4 Stop valve 5 Non ret...

Страница 17: ...nt building regulations and BS 7206 should be used Installation should be carried out generally as shown on figure 4 1 Pressure limiting valve 3 T P valve 4 Stop valve 5 Non return valve 6 Circulation...

Страница 18: ...etres For pipes with an inside diameter exceeding 25 mm maximum dead leg 3 0 metres Depending on the length and insulation of the water piping and the water demand frequency it may be necessary to ins...

Страница 19: ...f the high limit thermostat is activated the heater is not locked and the control thermostat will take over the temperature 2 1 3 Gas connection The gas supply to this appliance must be installed in a...

Страница 20: ...and safety valves the glow igniter and anodes must also be checked 2 8 Anode The life of the anode is determined by the quality and quantity of the water flowing through the heater Therefore we recomm...

Страница 21: ...he access covers Descaling must be carried out with a suitable substance Consult the supplier or installer 2 10 Condensation When the heater is filled with cold water or the hot water consumption is v...

Страница 22: ...nite the burner and keep it burning until the control ceases to supply voltage signals High water temperatures cause more calcium precipitation in the water heater Moreover the stand by losses of the...

Страница 23: ...ctions connections screw thread Leakage from another water appliance Trace the cause or pipes in neighbourhood Please consult the front mounted burner s installation manual in the event of faults in t...

Страница 24: ...ty with A O Smith Water Products Companies installation instructions f When anodes have been inspected and renewed if they are worn or erroded by 50 or more at any point of their length 5 4 Exclusions...

Страница 25: ...be fitted bet ween B4 and earth to prevent EMI The same applies to the installation of a fault alarm SB in this case a 100 nF capacitor must be fitted between S3 and earth if the cable length exceeds...

Страница 26: ...26 0311962 R0...

Страница 27: ......

Страница 28: ...osmith nl France A O Smith L Eau Chaude SARL 14 All e Charles Path 1800 Bourges 01 3975 5140 ou 008008 AOSMITH 2676484 info aosmith nl www aosmith fr United Kingdom A O Smith Water Heaters Unit B8 Arm...

Отзывы: