background image

23

23

Figure 8: Resetting the overheating cut-out

 Fault

Possible cause

Measure

Heater is off or

Chimney is blocked.

Trace (or let trace) cause and rectify it.

does not ignite

Overheating cut-out is activated.

Let water in heater cool down and set the water

temperature to a lower value. Reset the overheating cut-out.

Let heater ignite.

Gas or oil supply shut off.

Open gas or oil valve.

Insufficient hot

Temperature set too low.

Set water temperature to higher value.

water or none

at all

Overheating cut-out is activated.

Reset overheating cut-out after the water has cooled down

and set the water temperature to a lower value.

Supply of hot water exhausted.

Reduce hot water use. Give the heater time to heat up the

water.

Cause cannot be traced.

Remove voltage supply. Close gas / oil supply valve and

contact your installer.

Water leakage

Insufficient sealing of the water

Tighten the screw thread connections.

connections (screw thread).

Leakage from another water appliance

Trace the cause.

or pipes in neighbourhood.

Please consult the front-mounted burner’s installation

manual in the event of faults in the front-mounted burner.

4. WHAT TO DO IN CASE OF FAILURE

4.1

General

If faults occur, check the following points:

Overheat thermostat

The water heaters are equipped with an overheating

cut-out, which, in the case of a too high water

temperature, interrupts the current supply to

the burner, as a result of which the gas valves in the

gas block are closed and the gas supply is cut off.

The overheating cut-out remains activated until the

water temperature drops below the overheating

cut-out’s switching-off point. Then the water

heater can be turned on again by resetting

the overheating cut-out. Next set the control

thermostat to a lower water temperature,

(see figure 8).

Water temperature too high:

Check if the control thermostat has been set too high.

Wrong hot water temperature:

1. Check the control thermostat setting;

2. Check that there are no leaks or if any taps are

open.

4.2

Fault overview

Содержание COF 199

Страница 1: ...Manuel d installation Mode d emploi Manual d entretien Manual de Instalaci n Usuario y Servicio Manual de Instala o Utiliza o e Manuten o Manuale Installazione d uso e manutenzione Instrukcja Serwisu...

Страница 2: ...on and or a fire and can cause material and or physical injuries An accredited installer must install the heater and commission it according to the locally valid requirements The heater may only be in...

Страница 3: ...2 1 Filling the heater 19 2 2 2 Turning on the burner 19 2 3 Shutting down 19 2 4 Usage temperature control 19 2 5 Setting the nominal load 20 2 6 Conversion to another gas type 20 2 7 Maintenance 20...

Страница 4: ...he heater is completely filled with water it is under continuous mains water pressure When hot water is drained from the heater cold water immediately enters the heater For effective heat transfer flu...

Страница 5: ...of against etween the tank at loss h water it is e When hot water mmediately nsfer flue baffles eat from the flue ans of radiation eater is situated in itted to the heater hree thermostats t by means...

Страница 6: ...00 1700 1720 1650 1650 1770 P mm 620 620 620 620 620 755 R mm 540 540 585 605 605 670 S mm 1700 1700 1700 1630 1630 1750 1 Cold water inlet Rp 1 Rp 1 Rp 1 Rp 1 Rp 1 Rp 1 2 Hot water outlet Rp 1 Rp 1 R...

Страница 7: ...7 Figure 2 Dimensions IMD 0011...

Страница 8: ...unted burner must be less than the diameter of the heater s combustion chamber This diameter is 510 mm for all heaters For the COF 455 and COF 700 a starting load of 120 kW at maximum according to EN...

Страница 9: ...2 mg kWh GCV 76 79 81 86 90 97 PROPANE DATA G30 50 mbar Burner model BS 2 BS 2 BS 3 BS 3 BS 3 BS 3 Burner type 912 T1 912 T1 913 T1 913 T1 913 T1 913 T1 Nominal load lower value kW 60 75 90 115 135 17...

Страница 10: ...7 Rp 1 ISO 7 Rp 1 ISO 7 Rp 1 ISO 7 Rp 1 Drain valve 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT Anode 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT 14 NPT T P connection 1 11 5 NPT 1 11 5 NPT 1 11 5 NPT 1 11 5 NP...

Страница 11: ...Riello front mounted burners is The values above are recommended settings and have been determined under laboratory conditions The air proving switch s switching point must be set during the commissio...

Страница 12: ...mended settings and have been determined under laboratory conditions The gas pressure switch s switching point must be set during the commissioning of the water heater Please make sure that the burner...

Страница 13: ...to the burner s instruction manual The setting of the burner head for Riello front mounted burners is as follows Gas fired burner GAS G20 GAS G25 GAS G30 GAS G31 COF 199 2 2 2 2 2 COF 245 3 3 3 3 3 C...

Страница 14: ...lve Gas fired burner Oil fired burner GAS G20 GAS G25 GAS G30 GAS G31 COF 199 1 6 1 7 1 9 1 6 2 4 COF 245 2 1 2 5 2 3 2 1 3 5 COF 315 1 9 1 8 1 5 1 5 1 7 COF 385 2 9 2 9 2 5 2 5 2 7 COF 455 3 1 3 1 3...

Страница 15: ...nt 2 1 1 Installation These water heaters must be installed by a qualified competent installer in accordance with the following standards and regulations Gas safety installation and use regulations 19...

Страница 16: ...capacity of greater volume than the hourly recovery rate of the water heater s which it supplies The minimum actual capacity is 50 gallons or 227 litres see figure 3 3 T P valve 4 Stop valve 5 Non ret...

Страница 17: ...nt building regulations and BS 7206 should be used Installation should be carried out generally as shown on figure 4 1 Pressure limiting valve 3 T P valve 4 Stop valve 5 Non return valve 6 Circulation...

Страница 18: ...etres For pipes with an inside diameter exceeding 25 mm maximum dead leg 3 0 metres Depending on the length and insulation of the water piping and the water demand frequency it may be necessary to ins...

Страница 19: ...f the high limit thermostat is activated the heater is not locked and the control thermostat will take over the temperature 2 1 3 Gas connection The gas supply to this appliance must be installed in a...

Страница 20: ...and safety valves the glow igniter and anodes must also be checked 2 8 Anode The life of the anode is determined by the quality and quantity of the water flowing through the heater Therefore we recomm...

Страница 21: ...he access covers Descaling must be carried out with a suitable substance Consult the supplier or installer 2 10 Condensation When the heater is filled with cold water or the hot water consumption is v...

Страница 22: ...nite the burner and keep it burning until the control ceases to supply voltage signals High water temperatures cause more calcium precipitation in the water heater Moreover the stand by losses of the...

Страница 23: ...ctions connections screw thread Leakage from another water appliance Trace the cause or pipes in neighbourhood Please consult the front mounted burner s installation manual in the event of faults in t...

Страница 24: ...ty with A O Smith Water Products Companies installation instructions f When anodes have been inspected and renewed if they are worn or erroded by 50 or more at any point of their length 5 4 Exclusions...

Страница 25: ...be fitted bet ween B4 and earth to prevent EMI The same applies to the installation of a fault alarm SB in this case a 100 nF capacitor must be fitted between S3 and earth if the cable length exceeds...

Страница 26: ...26 0311962 R0...

Страница 27: ......

Страница 28: ...osmith nl France A O Smith L Eau Chaude SARL 14 All e Charles Path 1800 Bourges 01 3975 5140 ou 008008 AOSMITH 2676484 info aosmith nl www aosmith fr United Kingdom A O Smith Water Heaters Unit B8 Arm...

Отзывы: