background image

Note
Use the drain valve connection (9) as a

 

connection of the circulation pipe on the water

 

heater.

Note
Make sure that the circulation pump has the

 

correct capacity for the length and resistance of

 

the circulation system.

Install a circulation pump:
1. Install a circulation pump (6).
2. Install a non-return valve (5) after the

circulation pump to make sure that the
direction of circulation is guaranteed.

3. Install a stop valve (4) before the circulation

pump.

4. Install a stop valve (4) after the non-return

valve.

5. Connect the circulation pipe to the drain

valve (9).

8.4.4 Drain valve

Install the drain valve:
1. Fasten the drain valve (9) in the connection

in the front of the water heater.

2. Place the cap over the connection to make it

watertight.

8.5 Gas connection

Caution
Make sure that the gas supply pipe has the

 

correct diameter and length to supply sufficient

 

capacity to the water heater.

Caution
Make sure that the gas supply pipe is clean.

 

Contamination in the pipe can cause damage to

 

the gas control valve, during operation.

Caution
Install the manual gas valve on a spot

 

accessible for the user.

Install the gas connection:
1. Install the manual gas valve (10) in the gas

supply pipe.

2. Make sure that the gas pipe is clean before

use. If necessary, remove the contamination
from the pipe.

3. Close the manual gas valve.

n

c

4. Install the gas supply pipe to the gas control

valve.

5. Make sure that there are no gas leaks.

8.6 Flue gas discharge

Caution
It is not allowed to make changes to the flue
gas discharge or to apply casings on it.

Install the flue gas discharge:
1. Install the draught diverter on top of the

water heater. (see 8.6.1)

2. Install the T.R.S.
3. Install the discharge pipe. (see 8.6.3)

8.6.1 Draught diverter

Install the delivered draught diverter on top of
the water heater.

For correct installation of the draught diverter,
please refer to the installation instructions
delivered with the draught diverter.

Fig. Install the draught diverter

8.6.2 T.R.S. (Thermal Reflux
Safeguard)

The T.R.S. (Thermal Reflux Safeguard) is
installed on the draught diverter.

Note
Make sure that the temperature probe is
positioned at the front side of the water heater.
If necessary, reinstall the draught diverter.

To install the T.R.S.:
1. Remove the screws from the bracket.

c

n

0313126_BTL_UKUK_V1.1, 30-11-2018

15

Содержание BTL 100

Страница 1: ...Innovation has a name BTL 85 BTL 100 0313126 4918 Reserved Changes United Kingdom Ireland HOT WATER STORAGE HEATERS Installation User and Service Manual...

Страница 2: ......

Страница 3: ...Supplier The BTL water heater is designed in accordance with the applicable regulations The water heater is delivered with the CE marking and all necessary documentation to obey these regulations A O...

Страница 4: ...ons in this manual n Caution Read this manual carefully before you start the water heater It can cause personal injury and damage to the water heater when you do not read the manual and or do not obey...

Страница 5: ...perature setting 9 4 2 Turn off the water heater 9 4 2 1 Turn off for a short period 9 4 2 2 Turn off for a long period 9 Installation Maintenance and Service part 9 5 Introduction 9 5 1 About the wat...

Страница 6: ...er for sanitary purposes Cold water enters the tank 3 through the water inlet 2 The heated water leaves the tank at the top through the hot water outlet 1 When hot water is used the tank of the water...

Страница 7: ...g or has explained how the water heater should be used these persons can use the water heater Caution This water heater is not intended to be used by children Always supervise children and make sure t...

Страница 8: ...in the system freezes the frost protection is activated when the water heater is in OFF mode The frost protection starts when the temperature of the water drops below 5 C The water heater will heat th...

Страница 9: ...water heater needs to be turned off for more than 2 months contact your service and maintenance engineer to decommission the water heater 5 Introduction 5 1 About the water heater The BTL water heate...

Страница 10: ...ssure and the burner pressure are correct If the gas supply pressure is not correct contact your mains gas supply company Do not use the water heater Danger Never deactivate the T R S Backdraft of flu...

Страница 11: ...the cold water main supply Pressure reducing valve The pressure reducing valve reduces the water mains pressure if necessary T P valve Temperature and pressure relief valve 1 The T P valve is a temper...

Страница 12: ...control valve The gas control valve controls the gas supply to the burners Fig Components water heater 8 6 7 6 1 9 10 11 12 13 14 16 15 2 4 3 5 1 Draught diverter 2 T R S sensor 3 T R S thermostat 4 T...

Страница 13: ...e If necessary adjust the installation site to keep it frost free Air humidity and ambient temperature Air humidity Max 93 RH at 25 C Ambient temperature Functionality 0 T 40 C 8 2 2 Maximum floor loa...

Страница 14: ...connection 1 Install an approved stop valve 4 as required by the applicable regulations see 6 2 Install an approved pressure reducing valve 1 to prevent that the pressure in the cold water supply pipe...

Страница 15: ...manual gas valve on a spot accessible for the user Install the gas connection 1 Install the manual gas valve 10 in the gas supply pipe 2 Make sure that the gas pipe is clean before use If necessary re...

Страница 16: ...of the pressure relief valve of the inlet security group 2 or the T P valve 3 If water comes out Examine if the water supply pressure is greater than the specified value in the Technical details If ne...

Страница 17: ...eed from the supplier of your water heater The conversion kit contains all the parts needed to do the conversion and an instruction how to do the conversion The following conversions are possible Conv...

Страница 18: ...the anode The life cycle of the anode is determined by the quality and the quantity of the water that flows through the water heater Inspect the anode at least once a year to make sure that the tank i...

Страница 19: ...nk 11 Put the isolating material in place 12 Put the cover plate in place and tighten the two screws 13 Fill the water heater Fig Cleaning opening 10 3 Gas side maintenance Do gas side maintenance whe...

Страница 20: ...pply pressure is not correct contact your mains gas supply company Do not use the water heater 3 Make sure that the burner pressure is correct refer to burner pressure see 8 7 2 4 Turn on the water he...

Страница 21: ...n 11 1 3 Condensation Condensation of flue gases can occur on the cold surfaces of the combustion chamber and the flue gas discharge pipe when the water heater is filled with cold water or when the w...

Страница 22: ...water heater see 4 1 Control knob is in position Turn on the water heater see 4 1 Thermocouple is not working Replace thermocouple Thermocouple does not make contact Restore contact Turn on the water...

Страница 23: ...the operation control knob to close the gas supply valve and contact your installer Water leakage There is a leakage from a threaded water connection Tighten the threaded connection There is a condens...

Страница 24: ...let mm 130 130 Dimensions connections 1 Cold water supply connection female 1 1 1 4 2 Hot water outlet connection female 1 1 1 4 3 Gas control valve connection male Rp 1 2 Rp 1 2 4 Drain valve connect...

Страница 25: ...ergy label B C Energy efficiency 58 58 Daily electricity usage kWh 0 0 Daily fuel consumption kWh GCV 37 940 42 545 Mixed water 40 C V40 l 1246 648 Additional load profile Load profile XXL 3XL Energy...

Страница 26: ...Description Unit BTL 85 BTL 100 Daily fuel consumption kWh GCV 44 315 72 544 Mixed water 40 C V40 l 538 649 26 Installation Maintenance and Service part...

Страница 27: ...rate flue gases nominal load kg h 74 72 Flue gas temperature nominal load C 142 125 Gas category 3 G30 Diameter main orifice mm 1 45 1 45 Diameter orifice pilot burner mm 2 x 0 16 2 x 0 16 Nominal lo...

Страница 28: ...Gross kW 17 9 17 8 Nominal output kW 13 9 14 4 Supply pressure mbar 37 0 37 0 Burner pressure mbar Gas consumption kg h 1 3 1 3 NOx emission mg kWh GCV 9 9 Mass flow rate flue gases nominal load kg h...

Страница 29: ...12 5 Declaration of conformity 0313126_BTL_UKUK_V1 1 30 11 2018 29...

Страница 30: ...l times can freely circulate a separately installed heat exchanger is mandatory for heating saline water or corrosive water The tank is safeguarded against harmful scaling and lime build up by means o...

Страница 31: ...sed dealer for A O Smith Water Products Company products Inspection of the water heater as referred to in Articles 1 and 2 shall take place in one of the laboratories of A O Smith Water Products Compa...

Страница 32: ...h 1800 Bourges 01 3975 5140 ou 008008 AOSMITH 2676484 info aosmith nl www aosmith fr United Kingdom A O Smith Water Heaters Unit B8 Armstrong Mall Southwood Business Park Farnborough Hampshire GU14 0N...

Отзывы: