Code and description
Cause
Measure
F02 (lock out error)
Fan fails to run at correct
speed.
Defective motor and/or rotor.
Check the motor and rotor
Replace the fan if the motor or rotor is
defective.
Reset controller
•
•
•
Damaged wiring
Check the wiring between the fan and the
controller.
If any wires are damaged, the wiring
harness must be replaced.
Reset controller
•
•
•
Contaminated or blocked fan
Check if the fan is dirty and repair it if
necessary.
Check that the rotor can rotate freely
Reset controller
•
•
•
Because of a drop in the supply voltage,
the fan will not run at the correct speed.
Check the supply voltage, this must be
230 VAC(-15%, +10%)
Reset controller
•
•
F03 (lock out error)
The pressure switch fails
to work correctly
Damaged wiring/Open circuit
Check the wiring between the pressure
switch and the controller
If necessary, replace the wiring
•
•
Pressure switch not closing
Check the speed of the fan (see section
12.1).
Check that the hoses on the pressure
switch and the air supply hose between
fan and burner are correctly fitted. Refit
them if necessary
Check for cracks in the hoses on the
pressure switch and in the air supply
hose between fan and burner. If
necessary, replace the hoses.
Check whether the chimney flue is
compliant.
Check for blockage in the chimney flue.
Remove any blockage that may be
present
Check for blockage in the condensation
water discharge.
Remove any blockage that may be
present.
Measure the pressure differential across
the pressure switch.
See the table (see section 12.1). If there
is insufficient pressure differential, clean
the heat exchanger. If the pressure
differential is acceptable, check that the
pressure switch is closing, using a
multimeter
•
•
•
•
•
•
•
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
93
Содержание BFC Cyclone 120
Страница 6: ...6 ...
Страница 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Страница 14: ...14 ...
Страница 16: ...16 User part ...
Страница 18: ...18 User part ...
Страница 24: ...24 User part ...
Страница 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Страница 42: ...42 User part ...
Страница 46: ...46 Installation Maintenance and Service part ...
Страница 52: ...52 Installation Maintenance and Service part ...
Страница 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Страница 76: ...76 Installation Maintenance and Service part ...
Страница 78: ...78 Installation Maintenance and Service part ...
Страница 84: ...84 Installation Maintenance and Service part ...
Страница 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Страница 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Страница 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Страница 113: ......
Страница 114: ......
Страница 118: ...116 Installation Maintenance and Service part ...