background image

VII) COMBO HEATING

This section serves as a guide for the installation and use of
“Combo” heating systems utilizing a domestic water heater
which has been specifically approved for such use (see
Figure 32). It is written for those knowledgeable in the
required trades and professionals involved in the design
and installation of Combo Heating Systems.
It is the responsibility of the installer/designer to follow all
applicable codes to ensure the effectiveness and safety of
the installation.

System Requirements

The following requirements must be met for the installation
of Combo Heating Systems:
1.

The piping and components connected to the water
heater for the space heating applications shall be suit-
able for use with potable water. The system should be
installed with new, non-ferrous piping. Do not use
pumps, valves, fittings, solder, gluing and pipe sealant
that are not completely compatible with potable water
piping.

2.

A water heater which will be used to supply potable
water must not be connected to any heating system or
components previously used with a non-potable water
heating appliance. Do not use piping that has been
treated with chromates, broiler seal or other chemicals
and do not add chemicals to the water heating piping.
Do not introduce toxic chemicals, such as those used
for boiler treatment, into the potable water used for
space heating.

3.

Do not use this heater as a replacement for an existing
boiler installation.

4.

If the space heating water system requires water with
temperatures in excess of 60°C (140°F), a mixing valve,
or other means to temper the water and reduce scald
hazard potential, must be installed in the potable hot
water supply.

5.

If the heater is installed with a back-flow preventer on
the incoming water line or in a closed system, a
diaphragm-type expansion tank must always be
installed in the system to prevent the T&P from relieving
due to thermal expansion.

6.

Proper sizing of the water heater for the given space
and potable heating application is essential to ensure
adequate heating capacity. The sizing and installation of
such combination system must be performed by quali-
fied personnel and be in accordance with public utility
requirements and/or codes having jurisdiction.

The sizing of the water heater should be based on the
design heat loss of the structure to be heated plus the
potable water requirements.

IT IS IMPORTANT THAT THE WATER HEATER USED BE
SIZED PROPERLY TO ALLOW ADEQUATE HEATING
AND POTABLE WATER HEATING CAPACITY.

WATER

HEATER

AIR

HANDLER

CIRC. PUMP

CHECK VALVE

COLD TO

WATER HEATER

RADIATOR OR RADIANT FLOOR PIPING ARE

VIABLE ALTERNATIVES TO AIR HANDLER.

HOT WATER

TO HOUSE

Figure 32

Example Of Combo Heating Piping Schematic

MASSACHUSETTS
CODE DOES NOT
ALLOW THIS TYPE
OF INSTALLATION.

– 26 –

Содержание ATMOSPHERIC VENTED WATER HEATER

Страница 1: ...TY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agenc...

Страница 2: ...lation 13 Electrical Supply 14 24 Volt Control precautions Installations Check 15 IV OPERATING INSTRUCTIONS 15 Water Temperature Regulation 15 Temperature Adjustment Lighting Instructions White Rodger...

Страница 3: ...e outside In addition to the installation instructions found in this man ual the heater shall be installed according to all local and provincial or state codes and with the latest edition of the follo...

Страница 4: ...Shut Off Devices for Hot Water Supply Systems ANSI Z21 22 is applicable If this water heater has been exposed to flooding freezing fire or any unusual condition do not put it into operation until it h...

Страница 5: ...firm clearances Heaters with a volume of 19 gallons through 50 gallons and 60 gallon standard input must have the following minimum clearances to combustibles Front 102mm 4 in Sides and Rear 25mm 1 in...

Страница 6: ...ng tank or piping connections Refer to Figure 1 Under no circumstances is the manufacturer to be held responsi ble for any water damage in connection with this water heater Gas Supply Install the gas...

Страница 7: ...occur To avoid risk of fire or explosion ensure the area is well ventilated and all sources of ignition are de activated Contact your local gas authority for local requirements Gas Leak Testing Impor...

Страница 8: ...Refer to Figure 5 a or b and Table 2 for proper sizing and location of combustion air ducts and openings CHECK LOCAL CODES a Two permanent openings shall be provided connecting the confined space e g...

Страница 9: ...quipment located in confined spaces all air from outdoors When supplying air directly from the outdoors using hor izontal ducting each opening shall have a free mini mum area of one square inch per 2...

Страница 10: ...Figure 8 CSA U L recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regula...

Страница 11: ...lves that may cause excessive restriction to water flow Use full flow ball or gate valves only DO NOT use any lead based solder in potable water lines Use appropriate tin antimony or other equivalent...

Страница 12: ...eater Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater Do not place any valve between the relief valve and the tank The Tempera...

Страница 13: ...h ing connection point see Figure 14 Hold this connec tion in place against the heater Slide it up enough to pinch the lower connection post into the matching con nection point in place with your fing...

Страница 14: ...er is installed in accordance with prevailing provisions of local codes and the latest edition of Canadian Electrical Code CAN CSA C22 1 Part I Canada or National Electrical Code NFPA 70 U S A Before...

Страница 15: ...nd combustible construction as per specifica tions 7 Is the water piping correctly connected Are you certain that there are no leaks 8 Is the water heater filled with water 9 Is the cold water supply...

Страница 16: ...the appliance and call for service Valves for reducing the point of use temperature by mixing cold and hot water are available see Figure 11 Also avail able are inexpensive devices that attach to fau...

Страница 17: ...through the view port Do not release the gas control knob Repeat immediately if pilot does not light on the first try If the pilot does not light by the fourth attempt with the igniter repeat steps 5...

Страница 18: ...un appareil en marche N actionnez aucun interrupteur lectrique n utilisez aucun t l phone de votre b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin et suivez les instructions d...

Страница 19: ...ons Condensation Moisture from the products of combustion condenses on the tank surface and forms drops of water which may fall onto the burner or other hot surfaces This will produce a siz zling or f...

Страница 20: ...24 Volt Damper Models The 24 Volt control valve is in constant communications with the different components that are connected to it ensuring all components are in the proper positions and in working...

Страница 21: ...This lockout is required to allow the control to reset itself If the gas control valve is submerged under water for any length of time the gas control valve assembly should be replaced LED FLASH SEQU...

Страница 22: ...ing to be shut down for an extended period the drain valve should be left open Important Condensation may occur when refilling tank and should not be confused with a tank leak The following maintenanc...

Страница 23: ...or 6 Restart the water heater following the Operating Instructions 7 If the pilot burner does not stay lit after several attempts it is possible that the TCO embedded in the safety switch opened due t...

Страница 24: ...ngage the pins on the valve module 4 Re assemble in the reverse order Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly Valv...

Страница 25: ...ressure with the hand on the valve pins Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly When re installing the gas control...

Страница 26: ...those used for boiler treatment into the potable water used for space heating 3 Do not use this heater as a replacement for an existing boiler installation 4 If the space heating water system requires...

Страница 27: ...OO SMALL 1 Pilot line or orifice clogged 2 Low gas pressure 3 Defective pilot 1 Clean locate source and correct 2 Check with gas utility company 3 Replace pilot INSUFFICIENT HOT WATER 1 Thermostat set...

Страница 28: ...tat 2 Low gas pressure 3 Orifice not properly installed 1 Replace gas control thermostat 2 Check with gas utility company 3 Reinstall the orifice 1 Air in gas line 2 Defective pilot electrode 3 Cold d...

Страница 29: ...Y QUICK CONNECT LEADS Figure 33 Repair Parts Heaters without 24V vent damper 12 11 13 15 14 10 9 16 4 8 5 3 6 7 2 1 IX REPAIR PARTS ILLUSTRATION 1 NIPPLE HOT OUTLET 2 NIPPLE COLD INLET 3 DRAFTHOOD 4 T...

Страница 30: ...D TUBE 17 PILOT THERMOCOUPLE ASSEMBLY 18 VIEWPORT 19 TWO PIECE GROMMET WITH CLIP 20 MANIFOLD DOOR 21 GAS MANIFOLD 22 PILOT TUBE 23 GAS ORIFICE 24 MANIFOLD DOOR GASKET 25 BURNER Figure 36 Manifold Door...

Страница 31: ...31 This page intentionally left blank May be used for notes or to record other installation information...

Страница 32: ...599 Hill Street West Fergus ON Canada N1M 2X1 PHONE 1 888 479 8324 www hotwatercanada ca email techsupport hotwater com...

Отзывы: