INTRODUCTION

Thank you for purchasing this heat pump water heater. Properly 
installed and maintained, it should give you years of trouble 
free service.

Abbreviations found In this Instruction Manual include:

   • HPWH - Heat Pump Water Heater
   • ANSI - American National Standards Institute
   • ASME - American Society of Mechanical Engineers
   • NEC - National Electrical Code
   • NFPA - National Fire Protection Association
   • AHRI - Air-conditioning, Heating and Refrigeration Institute

QUALIFICATIONS 

QUALIFIED INSTALLER OR SERVICE AGENCY:

Installation and service of this water heater requires ability 
equivalent to that of a Qualifi ed Agency (as  defi ned by ANSI 
below) in the fi eld involved Installation skills such as plumbing, 
electrical supply are required in addition to electrical testing 
skills when performing service. 

This heat pump water heater contains R-134a refrigerant and 
is regulated as a stationary refrigeration appliance under Section 
608 of the Clean Air Act. Servicing of the refrigeration circuit 
must only be performed by agencies or individuals possessing 
Type II or Universal certifi cation as defi ned in Section 608 of 
the Clean Air Act.

ANSI Z223.1 2006 Sec. 3.3.83: “Qualifi ed  Agency”  -  “Any                          
individual, fi rm, corporation or company that either in person 
or through a representative is engaged in and is responsible 
for (a) the installation, testing or  replacement of gas piping or 
(b) the connection, installation, testing,  repair or servicing of 
appliances and equipment; that is experienced in such work; 
that is familiar with all precautions required; and that has complied 
with all the requirements of the authority having jurisdiction.”

PREPARING FOR THE INSTALLATION 

1.  Read  the  “General  Safety  Information”  section  of  this                     
manual First and then the entire manual carefully. If you don’t 
follow the safety rules, the heat pump water heater may not 
operate safely. It could cause DEATH, SERIOUS BODILY INJURY 
AND/OR PROPERTY DAMAGE.

This manual contains instructions for the installation, operation, 
and maintenance of the heat pump water heater (HPWH). It 
also contains warnings throughout the manual that you must 
read and be aware of. All warnings and all instructions are 
essential to the proper operation of the HPWH and your safety. 

READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL 
OR OPERATE THIS WATER HEATING APPLIANCE.

Detailed  installation  diagrams  are  in  this  manual.  These                       
diagrams will serve to provide the installer with a reference 
for the materials and suggested methods of piping. IT IS 
NECESSARY THAT ALL WATER PIPING AND THE ELECTRICAL 
WIRING  BE  INSTALLED  AND  CONNECTED  AS  SHOWN  IN  THE               
DIAGRAMS.

Particular attention should be given to the installation of the 
system (tank) temperature control. See page 16.

Be sure to turn off  power when working on or near the electrical 
system of the heat pump. Never touch electrical components 
with wet hands or when standing in water. When replacing 
fuses always use the correct size for the circuit.

The principal components of the HPWH are identifi ed in the 
Features And Components section of this manual on page 5. 
The rating label on the HPWH also provides useful information. 
These references should be used to identify the heat pump, its 
components and optional equipment.

2.   The installation must conform with these instructions and the 
local code authority having jurisdiction and the requirements of 
the power company. In the absence of local codes, the installation 
must comply with the latest editions of the National Electrical 
Code, ANSI/NFPA 70 or the Canadian Electrical Code CSA C22.1. 
The National Electrical Code may be ordered from: National 
Fire Protection Association, 1 Batterymarch Park, Quincy, MA 
02269.

The Canadian Electrical Code is available from the Canadian 
Standards Association, 8501 East Pleasant Valley Road, Cleveland, 
OH 44131.

3.   If after reading this manual you have any questions or do 
not understand any portion of the instructions DO NOT proceed 
with the installation. Call the toll free number listed on the 
back page of this manual for technical assistance.

Содержание AHPW-25

Страница 1: ...CSA C22 2 NO 236 2015 User s Information Manual Series 100 Models AHPW 25 AHPW 60 AHPW 90 AHPW 125 AHPW 185 AHPW 250 Water Source Commercial Heat Pump Water Heating Systems http waterheatertimer org...

Страница 2: ......

Страница 3: ...VE 12 TANK SELECTION 12 SOLAR TANKS 12 STORAGE HANDLING 12 STORAGE RECOMMENDATIONS 13 TABLE OF CONTENTS INSTALLATION 13 REQUIRED ABILITY 13 GENERAL 13 REQUIRED TOOLS MATERIALS 13 INSTALLATION START UP...

Страница 4: ...CREEN DISPLAYING ALARM STATUS 25 SINGLE UNIT ALARM SCREEN 25 SINGLE UNIT PIPE CONFIGURATION SCREEN 25 SINGLE UNIT TANK CONFIGURATION SCREEN 25 SINGLE UNIT IP ADDRESS CONFIGURATION 25 SINGLE UNIT HEAT...

Страница 5: ...hers who install use or service this heat pump water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoi...

Страница 6: ...cy 1 External fire 2 Damage 3 Running without water GROUNDING INSTRUCTIONS This heat pump water heater must be grounded in accordance with the National Electrical Code and or local codes These must be...

Страница 7: ...AGE Thismanualcontainsinstructionsfortheinstallation operation and maintenance of the heat pump water heater HPWH It also contains warnings throughout the manual that you must read and be aware of All...

Страница 8: ...mer provided Water Pump circulates water through the condenser Refrigerant leaving the condenser is a medium temperature high pressure liquid It flows through the Liquid Line to the Thermostatic Expan...

Страница 9: ...Component Refrigeration Circuit Compressor Condenser Heat Exchanger Receiver Thermostatic Expansion Valve TXV Evaporator Heat Exchanger Accumulator Refrigerant State Gas Gas to Liquid Liquid Liquid Li...

Страница 10: ...6 WATER TO WATER CYCLE...

Страница 11: ...GPM Performance Dimensions Weight Water Heating Capacity Cooling Capacity Inlet Outlet Water FPT Length A Width B Height C Dry Weight LBS Operating Weight LBS BTUH BTUH AHPW 25 4 5 4 28 600 22 275 38...

Страница 12: ...st conform to these instructions and all local and national code authority having jurisdiction Costs to diagnose perform service and repair damage caused by installation errors are not covered under t...

Страница 13: ...ical Code CSA C22 1 Voltage applied to the HPWH should not vary more than 5 to 10 of the voltage requirement listed on the HPWH rating label for satisfactory operation TABLE 2 VOLTAGE AMPERAGE RATINGS...

Страница 14: ...e heat pump water heaters are two wire circuits Three phase heaters are three wire circuits In addition to the foregoing a grounded conductor is required Not more than three conductors in raceway cabl...

Страница 15: ...s must be taken In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed upstream from the building fixtures or at t...

Страница 16: ...sistance in sizing of a temperature and pressure relief valve Follow the storage tank manufacturer s instructions regarding the proper installation of these products TANK SELECTION The HPWH unit is no...

Страница 17: ...al components are not moisture tolerant Note The limited warranty does not cover damage to the unit or controls due to negligence during storage The pictures may appear different than your actual unit...

Страница 18: ...e hangers Structural channels in a field provided frame should be mounted perpendicular to the unit s footing channels The following critical points must be observed when the HPWH unit is suspended fr...

Страница 19: ...ater on two tank preheat systems See Piping Diagram on page 30 9 A T P valve must be installed in the designated opening onthestoragetankperthetankmanufacturer srequirements See Temperature Pressure R...

Страница 20: ...lel to prevent hot water short circuiting 5 When the HPWH is connected to a storage tank ensure the storage tank is equipped with a properly rated and sized Temperature and Pressure T P relief valve R...

Страница 21: ...d temperature control opening in the mid lower portion of the storage tank Ensure the supplied Temperature Sensor is coated with a suitable heat transfer compound paste PRE STARTUP CHECKLIST 1 Before...

Страница 22: ...s If not there is a good chance the system is air bound and the air needs to be removed before starting the compressor Turn power back on and the heat pump will start within 5 minutes if there is a ca...

Страница 23: ...STARTING SOUND During the very brief start up a clicking sound is audible resulting from initial contacting of the spirals and is normal Nostartassistdevicesarerequiredforsingle phasecompressors even...

Страница 24: ...rate through the condenser by using the lower limit input WHY Every piping system is different therefore they have different head losses in the system In order for the AO Smith heatpumptooperateeffici...

Страница 25: ...ng OFF parameter indicating that you have entered the menu OFF This parameter indicates your desired high temperature When this temp is reached the unit will enter a cool down mode until the On value...

Страница 26: ...now in restricted mode Securely replace the cover before reconnecting power to the controller Lock out You can format your parameters to completely restrict all user adjustment of the control when in...

Страница 27: ...Pump Time Delay indicates remaining time in pump countdown when the count down starts the pump turns on Indicator Box indicates if the unit has been called to run green means run red means on standby...

Страница 28: ...and then permanently attach them to their respective tanks 4 Connect all of the member units to the router in the junction box 5 Under the configuration screen press the SEARCH FOR UNITS button to fin...

Страница 29: ...id Valve indicates the position of the LLSV open or closed Comp Compressor indicates the status of the compressor on or off Blower Blower Overload Status indicates if the blower motor starter is tripp...

Страница 30: ...urs of the compressor Purge button this button will run the pump relay for 2 minutes to allow you to purge the system without turning on the units Tank Pipe Unit call probe location probe is recommend...

Страница 31: ...to eliminate other potential problems before checking the refrigerant charge CHECK WATER TEMPERATURE RISE Always check water temperature rise through the HPWH unit s internal heat exchanger before ch...

Страница 32: ...28 TABLE 10 FIGURE 12...

Страница 33: ...d Shut off valves are partially closed Thermostat setting should not exceed 160 F Keep heat pump off until room temperature is back in operating range Low water ow corrections Replace unit pump Reduc...

Страница 34: ...K ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER THERMAL...

Страница 35: ...TION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO HP WATER HEATER THERMOWELL THERMAL STORAGE...

Страница 36: ...GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER HP WATER HEATER MASTER CONTROL PANEL RECOMMENDED FOR MU...

Страница 37: ...HECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING HP WATER HEATER THERMOWELL THERMAL STORAGE COLD WATER SUPPLY...

Страница 38: ...TER SINGLE HEATER MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOURCE W...

Страница 39: ...HEATER REVERSE RETURN MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOUR...

Страница 40: ...en the heat pump water heater is installed in accordance with local plumbing and building codes ordinances and regulations the warrantor s printed instructions provided with it and good industry pract...

Страница 41: ...37 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...

Страница 42: ...38 Service Log Issue Description Date Servicer...

Страница 43: ...39 Service Log Issue Description Date Servicer...

Страница 44: ......

Отзывы: