Notice: Please make sure you are running a 

Johnson controller (page 20) before you con-

tinue to the next page. If you are running a PLC 

(Programmable Logic Controller) skip to the 

directions starting on page 22.

FUNCTION RANGES & SETTINGS

Some of the A421 controllers settings are preprogrammed 
by AO Smith before shipment. These settings along with 
parameter ranges have been provided for your reference in the 
Parameter Settings table below.

SCREEN NAVIGATION

The A421 control buttons and display operate the same in 
both Basic and Advanced mode.

• 

When in Menu screens the parameters and values will 
fl ash on and off .

• 

Use the Arrow keys to navigate through all of the parameters 
and values

• 

To select a parameter press MENU

• 

To save a selected value, press MENU.

• 

This will automatically bring you to the next settable parameter

• 

To exit menus and return to the main screen press both 
arrow keys simultaneously.

Note: 

 If you do not press MENU to save a new value, the 

control reverts to the last saved value.

After 30 seconds of inactivity, while in any screen, the control 
reverts to the Main screen.

Saved settings remain in the control’s memory during power 
interruptions.

BASIC MODE

In this mode you can adjust the OFF, On, SF and ASd Parameters 
ONLY. Most adjustments that are needed to run your unit will 
be performed in this mode.

Basic Mode Menu: 

From the main screen press MENU once. 

The screen will display the fl ashing OFF parameter indicating 
that you have entered the menu.

OFF:

 This parameter indicates your desired high temperature. 

When this temp is reached the unit will enter a cool down 
mode until the On value is reached. WARNING: Never set 
above 160°F.

ON

:

 This parameter indicates your desired low temperature. 

When this temperature is reached the unit will enter heating 
mode until it reaches the OFF value again.

ASd

:

 The Anti-Short Cycle Delay indicates the time required 

for the unit to wait before running again. This parameter is set 
to 0 min because AO Smith units come equipped with safety 
timers already in place.

SF

Sensor Failure indicates that the temperature sensor has 

failed.

bLL: 

Black Light Level indicates the brightness of the LCD 

screen.

ADVANCED MODE

In Advanced mode you can adjust all of the basic parameters 
as well as; Un, Tsb, So, HtS and LtS. The main function of this 
mode is to add more control over your unit and to set restrictions 
for parameters in basic mode.

Advanced Mode Menu: 

From the main screen press and hold both 

arrow keys simultaneously. The screen will display the fl ashing 
Un parameter to indicate that you have entered the menu.

Un: 

Indicates the temperature units. This can be in either Fahrenheit 

(°F) or Celsius (°C).

LtS:

 Low Temp. Stop indicates the lowest temperature that the 

On or OFF parameters can be set to in Basic Mode.

HtS: 

High Temp. Stop indicates the highest temperature that 

the On or OFF parameters can be set to in Basic Mode.

tSb:

 Temp Setback indicates the value for setting back the On 

and OFF temperature values. Default to 0°F because it is not 
applicable to the application of this unit type.

Содержание AHPW-25

Страница 1: ...CSA C22 2 NO 236 2015 User s Information Manual Series 100 Models AHPW 25 AHPW 60 AHPW 90 AHPW 125 AHPW 185 AHPW 250 Water Source Commercial Heat Pump Water Heating Systems http waterheatertimer org...

Страница 2: ......

Страница 3: ...VE 12 TANK SELECTION 12 SOLAR TANKS 12 STORAGE HANDLING 12 STORAGE RECOMMENDATIONS 13 TABLE OF CONTENTS INSTALLATION 13 REQUIRED ABILITY 13 GENERAL 13 REQUIRED TOOLS MATERIALS 13 INSTALLATION START UP...

Страница 4: ...CREEN DISPLAYING ALARM STATUS 25 SINGLE UNIT ALARM SCREEN 25 SINGLE UNIT PIPE CONFIGURATION SCREEN 25 SINGLE UNIT TANK CONFIGURATION SCREEN 25 SINGLE UNIT IP ADDRESS CONFIGURATION 25 SINGLE UNIT HEAT...

Страница 5: ...hers who install use or service this heat pump water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoi...

Страница 6: ...cy 1 External fire 2 Damage 3 Running without water GROUNDING INSTRUCTIONS This heat pump water heater must be grounded in accordance with the National Electrical Code and or local codes These must be...

Страница 7: ...AGE Thismanualcontainsinstructionsfortheinstallation operation and maintenance of the heat pump water heater HPWH It also contains warnings throughout the manual that you must read and be aware of All...

Страница 8: ...mer provided Water Pump circulates water through the condenser Refrigerant leaving the condenser is a medium temperature high pressure liquid It flows through the Liquid Line to the Thermostatic Expan...

Страница 9: ...Component Refrigeration Circuit Compressor Condenser Heat Exchanger Receiver Thermostatic Expansion Valve TXV Evaporator Heat Exchanger Accumulator Refrigerant State Gas Gas to Liquid Liquid Liquid Li...

Страница 10: ...6 WATER TO WATER CYCLE...

Страница 11: ...GPM Performance Dimensions Weight Water Heating Capacity Cooling Capacity Inlet Outlet Water FPT Length A Width B Height C Dry Weight LBS Operating Weight LBS BTUH BTUH AHPW 25 4 5 4 28 600 22 275 38...

Страница 12: ...st conform to these instructions and all local and national code authority having jurisdiction Costs to diagnose perform service and repair damage caused by installation errors are not covered under t...

Страница 13: ...ical Code CSA C22 1 Voltage applied to the HPWH should not vary more than 5 to 10 of the voltage requirement listed on the HPWH rating label for satisfactory operation TABLE 2 VOLTAGE AMPERAGE RATINGS...

Страница 14: ...e heat pump water heaters are two wire circuits Three phase heaters are three wire circuits In addition to the foregoing a grounded conductor is required Not more than three conductors in raceway cabl...

Страница 15: ...s must be taken In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed upstream from the building fixtures or at t...

Страница 16: ...sistance in sizing of a temperature and pressure relief valve Follow the storage tank manufacturer s instructions regarding the proper installation of these products TANK SELECTION The HPWH unit is no...

Страница 17: ...al components are not moisture tolerant Note The limited warranty does not cover damage to the unit or controls due to negligence during storage The pictures may appear different than your actual unit...

Страница 18: ...e hangers Structural channels in a field provided frame should be mounted perpendicular to the unit s footing channels The following critical points must be observed when the HPWH unit is suspended fr...

Страница 19: ...ater on two tank preheat systems See Piping Diagram on page 30 9 A T P valve must be installed in the designated opening onthestoragetankperthetankmanufacturer srequirements See Temperature Pressure R...

Страница 20: ...lel to prevent hot water short circuiting 5 When the HPWH is connected to a storage tank ensure the storage tank is equipped with a properly rated and sized Temperature and Pressure T P relief valve R...

Страница 21: ...d temperature control opening in the mid lower portion of the storage tank Ensure the supplied Temperature Sensor is coated with a suitable heat transfer compound paste PRE STARTUP CHECKLIST 1 Before...

Страница 22: ...s If not there is a good chance the system is air bound and the air needs to be removed before starting the compressor Turn power back on and the heat pump will start within 5 minutes if there is a ca...

Страница 23: ...STARTING SOUND During the very brief start up a clicking sound is audible resulting from initial contacting of the spirals and is normal Nostartassistdevicesarerequiredforsingle phasecompressors even...

Страница 24: ...rate through the condenser by using the lower limit input WHY Every piping system is different therefore they have different head losses in the system In order for the AO Smith heatpumptooperateeffici...

Страница 25: ...ng OFF parameter indicating that you have entered the menu OFF This parameter indicates your desired high temperature When this temp is reached the unit will enter a cool down mode until the On value...

Страница 26: ...now in restricted mode Securely replace the cover before reconnecting power to the controller Lock out You can format your parameters to completely restrict all user adjustment of the control when in...

Страница 27: ...Pump Time Delay indicates remaining time in pump countdown when the count down starts the pump turns on Indicator Box indicates if the unit has been called to run green means run red means on standby...

Страница 28: ...and then permanently attach them to their respective tanks 4 Connect all of the member units to the router in the junction box 5 Under the configuration screen press the SEARCH FOR UNITS button to fin...

Страница 29: ...id Valve indicates the position of the LLSV open or closed Comp Compressor indicates the status of the compressor on or off Blower Blower Overload Status indicates if the blower motor starter is tripp...

Страница 30: ...urs of the compressor Purge button this button will run the pump relay for 2 minutes to allow you to purge the system without turning on the units Tank Pipe Unit call probe location probe is recommend...

Страница 31: ...to eliminate other potential problems before checking the refrigerant charge CHECK WATER TEMPERATURE RISE Always check water temperature rise through the HPWH unit s internal heat exchanger before ch...

Страница 32: ...28 TABLE 10 FIGURE 12...

Страница 33: ...d Shut off valves are partially closed Thermostat setting should not exceed 160 F Keep heat pump off until room temperature is back in operating range Low water ow corrections Replace unit pump Reduc...

Страница 34: ...K ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER THERMAL...

Страница 35: ...TION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO HP WATER HEATER THERMOWELL THERMAL STORAGE...

Страница 36: ...GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER HP WATER HEATER MASTER CONTROL PANEL RECOMMENDED FOR MU...

Страница 37: ...HECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING HP WATER HEATER THERMOWELL THERMAL STORAGE COLD WATER SUPPLY...

Страница 38: ...TER SINGLE HEATER MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOURCE W...

Страница 39: ...HEATER REVERSE RETURN MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOUR...

Страница 40: ...en the heat pump water heater is installed in accordance with local plumbing and building codes ordinances and regulations the warrantor s printed instructions provided with it and good industry pract...

Страница 41: ...37 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...

Страница 42: ...38 Service Log Issue Description Date Servicer...

Страница 43: ...39 Service Log Issue Description Date Servicer...

Страница 44: ......

Отзывы: