SOURCE WATER TEMPERATURE

ENTERING SOURCE WATER TEMPERATURE

The entering source water temperature range of operation for 
the unit is 40° - 100°F (4.4°C to 38°C). The source temperature 
drop (Delta T - ΔT) through the evaporator (heat exchanger) 
will be approximately 8°F to 12°F (-13°C to -12°C).

If the source water temperature is outside this operating 
range  the HPWH unit’s Limit Thermostat will discontinue 
heating operation until the entering source water temperature 
returns to this operating range. 

LOCATING THE WATER HEATER

INDOOR/OUTDOOR  INSTALLATION                                                          
(Milder Climates)

Carefully choose a location for the HPWH unit. Placement is a very 
important consideration for optimal performance and safety.

Locate the HPWH near a floor drain. The unit should be 
located in an area where leakage from the HPWH unit or the 
storage tank it is connected to will not result in damage to the 
area adjacent to the water heater or to lower floors of the 
structure. See Unit Placement on page 14.

FREEZING TEMPERATURES

The HPWH unit must not be installed in space where freezing 
temperature will occur, without a low ambient air kit. Exposure 
to freezing ambient temperatures below 32°F (0° C) may result 
in severe damage to internal components. Damage caused by 
exposure to freezing temperatures is not covered under the 
limited warranty.

COASTAL REGIONS

When the HPWH will be installed within 5 miles of a seacoast 
the optional Corrosive Duty Package is recommended. The 
corrosive duty package includes a stainless steel cabinet, 
(Ecoating is standard on the evaporator). Damage caused to 
units not equipped with the corrosive duty package in coastal 
regions is not covered under the limited warranty.

HEAT SOURCE

The HPWH unit should be located where there is adequate 
source water from which to extract waste heat and where the 
source water cooling benefi t can be utilized when possible.

INSTALLATION REQUIREMENTS

Read all installation requirements in this manual before 
installation begins.

 The installation must conform to these 

instructions and all local and national code authority having 
jurisdiction.

Costs to diagnose, perform service and repair damage caused 
by installation errors are not covered under the limited warranty.

Costs to correct installation errors are not covered under the   
limited warranty.

WATER TEMPERATURE

MAXIMUM SYSTEM TEMPERATURE

The HPWH units covered in this manual are capable of maintaining 
a maximum system/storage tank temperature of 150°F (66°C). 
Some commercial water heating applications may require 
higher temperatures. Install a booster water heater downstream 
from the storage tank for temperatures above 150°F (66°C). 
See Figure 8 on page 16.

INLET & OUTLET WATER TEMPERATURE

The inlet (entering) water temperature operating range for 
the HPWH is 40°F to 140°F (4.4°C to 60°C). The water temperature 
rise (Delta T - ΔT) through the condenser (heat exchanger) will 
be approximately 8°F to 12°F (4°C to 7°C).

Outlet water temperatures up to 152°F (67°C) are possible 
during normal operation. Exposure to water temperatures 
this high can cause serious bodily injury or death. See Mixing 
Valves and Table 5 on pages 11 & 12.

Service & Installation Notes:

If the inlet (entering) water temperature is outside the operating 
temperature range for extended periods the control 
system may lock out on high or low refrigerant pressure 
switch events/trips.

When the control system locks out on a refrigerant pressure 
switch event the compressor will stop running, the blower and 
circulation pump (on models equipped with factory installed 
pump) will continue to operate. This is a hard lock out condition. 
The control system is manually reset by cycling power to the 
HPWH off  and then on again.

The tank thermostat must not be set any higher than 

150°F 

(66°C) to prevent control system lock outs.

Ground water temperatures can fall below 50°F (10°C) 
for extended periods during winter months in many regions. 
For this reason the cold water supply lines and should not 
be connected directly to the HPWH inlet or T fi tted into the 
inlet (return) water piping. The cold water supply lines should 
be  connected  directly  to  the  storage  tank  only.  See  the  Piping                 
Diagrams on page 30 in this manual for more information.

Содержание AHPW-25

Страница 1: ...CSA C22 2 NO 236 2015 User s Information Manual Series 100 Models AHPW 25 AHPW 60 AHPW 90 AHPW 125 AHPW 185 AHPW 250 Water Source Commercial Heat Pump Water Heating Systems http waterheatertimer org...

Страница 2: ......

Страница 3: ...VE 12 TANK SELECTION 12 SOLAR TANKS 12 STORAGE HANDLING 12 STORAGE RECOMMENDATIONS 13 TABLE OF CONTENTS INSTALLATION 13 REQUIRED ABILITY 13 GENERAL 13 REQUIRED TOOLS MATERIALS 13 INSTALLATION START UP...

Страница 4: ...CREEN DISPLAYING ALARM STATUS 25 SINGLE UNIT ALARM SCREEN 25 SINGLE UNIT PIPE CONFIGURATION SCREEN 25 SINGLE UNIT TANK CONFIGURATION SCREEN 25 SINGLE UNIT IP ADDRESS CONFIGURATION 25 SINGLE UNIT HEAT...

Страница 5: ...hers who install use or service this heat pump water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoi...

Страница 6: ...cy 1 External fire 2 Damage 3 Running without water GROUNDING INSTRUCTIONS This heat pump water heater must be grounded in accordance with the National Electrical Code and or local codes These must be...

Страница 7: ...AGE Thismanualcontainsinstructionsfortheinstallation operation and maintenance of the heat pump water heater HPWH It also contains warnings throughout the manual that you must read and be aware of All...

Страница 8: ...mer provided Water Pump circulates water through the condenser Refrigerant leaving the condenser is a medium temperature high pressure liquid It flows through the Liquid Line to the Thermostatic Expan...

Страница 9: ...Component Refrigeration Circuit Compressor Condenser Heat Exchanger Receiver Thermostatic Expansion Valve TXV Evaporator Heat Exchanger Accumulator Refrigerant State Gas Gas to Liquid Liquid Liquid Li...

Страница 10: ...6 WATER TO WATER CYCLE...

Страница 11: ...GPM Performance Dimensions Weight Water Heating Capacity Cooling Capacity Inlet Outlet Water FPT Length A Width B Height C Dry Weight LBS Operating Weight LBS BTUH BTUH AHPW 25 4 5 4 28 600 22 275 38...

Страница 12: ...st conform to these instructions and all local and national code authority having jurisdiction Costs to diagnose perform service and repair damage caused by installation errors are not covered under t...

Страница 13: ...ical Code CSA C22 1 Voltage applied to the HPWH should not vary more than 5 to 10 of the voltage requirement listed on the HPWH rating label for satisfactory operation TABLE 2 VOLTAGE AMPERAGE RATINGS...

Страница 14: ...e heat pump water heaters are two wire circuits Three phase heaters are three wire circuits In addition to the foregoing a grounded conductor is required Not more than three conductors in raceway cabl...

Страница 15: ...s must be taken In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed upstream from the building fixtures or at t...

Страница 16: ...sistance in sizing of a temperature and pressure relief valve Follow the storage tank manufacturer s instructions regarding the proper installation of these products TANK SELECTION The HPWH unit is no...

Страница 17: ...al components are not moisture tolerant Note The limited warranty does not cover damage to the unit or controls due to negligence during storage The pictures may appear different than your actual unit...

Страница 18: ...e hangers Structural channels in a field provided frame should be mounted perpendicular to the unit s footing channels The following critical points must be observed when the HPWH unit is suspended fr...

Страница 19: ...ater on two tank preheat systems See Piping Diagram on page 30 9 A T P valve must be installed in the designated opening onthestoragetankperthetankmanufacturer srequirements See Temperature Pressure R...

Страница 20: ...lel to prevent hot water short circuiting 5 When the HPWH is connected to a storage tank ensure the storage tank is equipped with a properly rated and sized Temperature and Pressure T P relief valve R...

Страница 21: ...d temperature control opening in the mid lower portion of the storage tank Ensure the supplied Temperature Sensor is coated with a suitable heat transfer compound paste PRE STARTUP CHECKLIST 1 Before...

Страница 22: ...s If not there is a good chance the system is air bound and the air needs to be removed before starting the compressor Turn power back on and the heat pump will start within 5 minutes if there is a ca...

Страница 23: ...STARTING SOUND During the very brief start up a clicking sound is audible resulting from initial contacting of the spirals and is normal Nostartassistdevicesarerequiredforsingle phasecompressors even...

Страница 24: ...rate through the condenser by using the lower limit input WHY Every piping system is different therefore they have different head losses in the system In order for the AO Smith heatpumptooperateeffici...

Страница 25: ...ng OFF parameter indicating that you have entered the menu OFF This parameter indicates your desired high temperature When this temp is reached the unit will enter a cool down mode until the On value...

Страница 26: ...now in restricted mode Securely replace the cover before reconnecting power to the controller Lock out You can format your parameters to completely restrict all user adjustment of the control when in...

Страница 27: ...Pump Time Delay indicates remaining time in pump countdown when the count down starts the pump turns on Indicator Box indicates if the unit has been called to run green means run red means on standby...

Страница 28: ...and then permanently attach them to their respective tanks 4 Connect all of the member units to the router in the junction box 5 Under the configuration screen press the SEARCH FOR UNITS button to fin...

Страница 29: ...id Valve indicates the position of the LLSV open or closed Comp Compressor indicates the status of the compressor on or off Blower Blower Overload Status indicates if the blower motor starter is tripp...

Страница 30: ...urs of the compressor Purge button this button will run the pump relay for 2 minutes to allow you to purge the system without turning on the units Tank Pipe Unit call probe location probe is recommend...

Страница 31: ...to eliminate other potential problems before checking the refrigerant charge CHECK WATER TEMPERATURE RISE Always check water temperature rise through the HPWH unit s internal heat exchanger before ch...

Страница 32: ...28 TABLE 10 FIGURE 12...

Страница 33: ...d Shut off valves are partially closed Thermostat setting should not exceed 160 F Keep heat pump off until room temperature is back in operating range Low water ow corrections Replace unit pump Reduc...

Страница 34: ...K ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER THERMAL...

Страница 35: ...TION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO HP WATER HEATER THERMOWELL THERMAL STORAGE...

Страница 36: ...GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER HP WATER HEATER MASTER CONTROL PANEL RECOMMENDED FOR MU...

Страница 37: ...HECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING HP WATER HEATER THERMOWELL THERMAL STORAGE COLD WATER SUPPLY...

Страница 38: ...TER SINGLE HEATER MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOURCE W...

Страница 39: ...HEATER REVERSE RETURN MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOUR...

Страница 40: ...en the heat pump water heater is installed in accordance with local plumbing and building codes ordinances and regulations the warrantor s printed instructions provided with it and good industry pract...

Страница 41: ...37 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...

Страница 42: ...38 Service Log Issue Description Date Servicer...

Страница 43: ...39 Service Log Issue Description Date Servicer...

Страница 44: ......

Отзывы: