10
Note:
Each unit is made of multiple AHPM-270 units. the above data is based on each unit having its own disconnect. the total
incoming MCA and MFS are used for the power needed in the building if all units were run off of one disconnect.
CLEARANCES
To ensure optimal performance a minimum of 30 inches
clearances required from the back, left and right sides of the
HPWH unit and any wall obstruction. A minimum of 36 inches
clearance on the front of the unit for access to the control box.
ELECTRICAL REQUIREMENTS
Ensure the power supply voltage and phase at the job site
matches the power supply ratings listed on the HPWH data
sticker label BEFORE INSTALLATION BEGINS.
The installation must conform with these instructions and the
local code authority having jurisdiction and the requirements
of the power company. In the absence of local codes,
the installation must comply with the current editions of
the National Electrical Code, ANSI/NFPA 70 or the Canadian
Electrical Code CSA C22.1.
Voltage applied to the HPWH should not vary more than +5%
to -10% of the voltage requirement listed on the HPWH rating
label for satisfactory operation.
TABLE 2 - VOLTAGE & AMPERAGE RATINGS
Model
Volts/Phase/HZ
Compressor
MCA
MOCP/MFS
LRA
RLA
AHPM-270
208-230/3/60
560
92.9
116
125
440-480/3/60
270
49.3
62
70
575/3/60
198
28.2
35
40
AHPM-540
208-230/3/60
560
92.9
209
225
440-480/3/60
270
49.3
111
125
575/3/60
198
28.2
63
92
AHPM-810
208-230/3/60
560
92.9
302
350
440-480/3/60
270
49.3
160
225
575/3/60
198
28.2
92
100
AHPM-1080
208-230/3/60
560
92.9
395
400
440-480/3/60
270
49.3
210
225
575/3/60
198
28.2
120
125
AHPM-1350
208-230/3/60
560
92.9
488
500
440-480/3/60
270
49.3
259
300
575/3/60
198
28.2
148
150
AHPM-1620
208-230/3/60
560
92.9
Based on Confi guration
440-480/3/60
270
49.3
575/3/60
198
28.2
AHPM-1890
208-230/3/60
560
92.9
Based on Confi guration
440-480/3/60
270
49.3
575/3/60
198
28.2
AHPM-2160
208-230/3/60
560
92.9
Based on Confi guration
440-480/3/60
270
49.3
575/3/60
198
28.2
LRA: Locked Rotor Amps
RLA: Rated Load Amps
MCA: Maximum Current Ampacity
MOCP: Minimum Overcurrent Protection
Содержание AHPM-270
Страница 2: ......
Страница 10: ...6 Thermostatic Expansion Valve TXV Condenser Paddle Wheel Flow Sensor Accumulator Receiver...
Страница 11: ...7 WATER TO WATER CYCLE...
Страница 39: ...35 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...
Страница 40: ...36 Service Log Issue Description Date Servicer...
Страница 41: ...Service Log Issue Description Date Servicer 37...
Страница 42: ...Notes 38...
Страница 43: ......
Страница 44: ......