A.O. Smith AHPM-270 Скачать руководство пользователя страница 16

12

CLOSED WATER SYSTEMS 

Water supply systems may, because of code requirements or 
such conditions as high line pressure, among others, have 
installed devices such as pressure reducing valves, check 
valves, and back fl ow preventers. Devices such as these cause 
the water system to be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed 
system the volume of water will grow when it is heated. As the 
volume of water grows there will be a corresponding increase 
in water pressure due to thermal expansion. Thermal expansion 
can cause premature failure (leakage) of storage tanks, water 
heaters and HPWH components such as the condenser. Leakage 
caused by thermal expansion is not covered under the HPWH 
limited warranty.

Thermal expansion can also cause intermittent Temperature- 
Pressure Relief Valve operation: water discharged due to 
excessive pressure build up. The Temperature-Pressure Relief 
Valve is not intended for the constant relief of thermal expansion.

A properly sized thermal expansion tank must be installed on 
all closed systems to control the harmful eff ects of thermal 
expansion. Contact a local plumbing service agency to have a 
thermal expansion tank installed on all closed water systems.

MIXING VALVES

Water heated to a temperature which will satisfy clothes washing, 
dish washing, and other sanitizing needs can scald and cause 
permanent injury upon contact. See Table 5, page 13.

Some people are more likely to be permanently injured by 
hot water than others. These include the elderly, children, the 
infi rm and the physically/mentally disabled.  Table 5 shows 
the approximate time-to-burn relationship for normal adult 
skin. If anyone using hot water provided by the water heater 
being installed fi ts into one of these groups or if there is a local 
code or state law requiring a certain water temperature at the 
point of use, then special precautions must be taken.

In addition to using the lowest possible temperature setting 
that satisfi es the demand of the application a Mixing Valve 
should be installed upstream from the building fi xtures or at 
the hot water taps to further reduce system water temperature.

WATER PIPING 

Read all installation requirements in this manual before 
installation begins

.

The water piping installation must conform to these instructions 
and to all local and national code authority having jurisdiction.

Costs to diagnose, perform service and repair damage caused 
by installation errors are not covered under the limited warranty.

Costs to correct installation errors are not covered under the 
limited warranty.

MINIMUM PIPE SIZE

The inlet (return) and outlet (supply) water piping installed 
between the HPWH unit and the storage tank must not be 
smaller than the water connection sizes on the HPWH. See 
Table 4, below, for water line connection sizes and water fl ow 
rates.

Water line sizing is a critical installation requirement. Installing 
undersized water piping between the storage tank and the 
HPWH unit will cause insuffi

  cient water fl ow and will have an 

adverse impact on performance and equipment life.

TABLE 4

PIPE SUPPORT

All water piping must be properly supported per local code 
requirements.

PIPE INSULATION

All piping installed between the HPWH unit and the storage 
tank must be insulated.

COLD WATER SUPPLY

Cold water supply lines should not be connected directly to 
the HPWH inlet or T fi tted into the inlet (return) water piping. 
The cold water supply lines should be connected directly to 
the storage tank only. See Inlet & Outlet Water Temperature 
on page 9 and Figure 7 and Figure 8 on pages 16 & 17.

WATER PRESSURE

System water pressure should be maintained between 40 and 
60 PSI. Local code may require, and the manufacturer recommends, 
installing a pressure reducing valve (PRV) in the cold water 
supply to the building to maintain consistent water pressure.

Water Connection and Flow

Unit

Water Flow Rate

(GPM)

Connection Size

(Inches)

AHPM-270

50

2”

AHPM-540

100

2”

AHPM-810

150

2”

AHPM-1080

200

2”

AHPM-1350

250

2”

AHPM-1620

300

2”

AHPM-1890

350

2”

AHPM-2160

400

2”

Содержание AHPM-270

Страница 1: ...ion Manual Series 100 Models AHPM 270 AHPM 540 AHPM 810 AHPM 1080 AHPM 1350 AHPM 1620 AHPM 1890 AHPM 2160 Modular Water Source Commercial Heat Pump Water Heating Systems Certified UL 1995 2015 CSA C22...

Страница 2: ......

Страница 3: ...O MEMBER UNITS 22 MASTER CONTROL UNIT SUPPORT CALL SEQUENCE OF OPERATIONS 22 MEMBER SCREENS 23 SAFE INSTALLATION USE AND SERVICE 1 GENERAL SAFETY INFORMATION 2 PRECAUTIONS 2 GROUNDING INSTRUCTIONS 2 I...

Страница 4: ...DDRESS CONFIGURATION 23 SINGLE UNIT HEAT BANK SCREEN 23 MEMBER SCREEN TERMINOLOGY 24 HOME SCREEN 24 ALARM SCREEN 24 CONFIGURATION SCREEN 24 STOP SCREEN 24 IP CONFIGURATION 24 MAINTENANCE AND SERVICE 2...

Страница 5: ...hers who install use or service this heat pump water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoi...

Страница 6: ...External fire 2 Damage 3 Running without water GROUNDING INSTRUCTIONS This heat pump water heater must be grounded in accordance with the National Electrical Code and or local codes These must be foll...

Страница 7: ...AGE Thismanualcontainsinstructionsfortheinstallation operation and maintenance of the heat pump water heater HPWH It also contains warnings throughout the manual that you must read and be aware of All...

Страница 8: ...ustomer provided Water Pump circulates water through the condenser Refrigerant leaving the condenser is a medium temperature high pressure liquid It flows through the Liquid Line to the Thermostatic E...

Страница 9: ...Circuit Heated Water Inlet Condenser Heat Exchanger Heated Water Outlet Figure 1 FEATURES COMPONENTS PRODUCT ILLUSTRATION Component Source Water Circuit Source Water Inlet Evaporator Heat Exchanger S...

Страница 10: ...6 Thermostatic Expansion Valve TXV Condenser Paddle Wheel Flow Sensor Accumulator Receiver...

Страница 11: ...7 WATER TO WATER CYCLE...

Страница 12: ...H AHPM 270 50 50 277 100 210 000 2 34 36 68 1 150 1 300 AHPM 540 100 100 554 200 414 450 2 64 36 68 2 300 2 600 AHPM 810 150 150 831 300 632 500 2 99 36 68 3 450 3 900 AHPM 1080 200 200 1 108 400 843...

Страница 13: ...st conform to these instructions and all local and national code authority having jurisdiction Costs to diagnose perform service and repair damage caused by installation errors are not covered under t...

Страница 14: ...0 or the Canadian Electrical Code CSA C22 1 Voltage applied to the HPWH should not vary more than 5 to 10 of the voltage requirement listed on the HPWH rating label for satisfactory operation TABLE 2...

Страница 15: ...e heat pump water heaters are two wire circuits Three phase heaters are three wire circuits In addition to the foregoing a grounded conductor is required Not more than three conductors in raceway cabl...

Страница 16: ...ion to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to fur...

Страница 17: ...sistance in sizing of a temperature and pressure relief valve Follow the storage tank manufacturer s instructions regarding the proper installation of these products TANK SELECTION The HPWH unit is no...

Страница 18: ...omponents are not moisture tolerant Note The limited warranty does not cover damage to the unit or controls due to negligence during storage The pictures may appear different than your actual unit all...

Страница 19: ...g channels on the bottom of the unit See Table 1 on page 8 for unit dimensions and weights Note A qualified engineer should design and size the structural components of the mounting frame Structural c...

Страница 20: ...ntrolled by a field supplied thermostat installed in the building recirculation return line near the storage tank or back up heater The thermostat should stop pump operation the moment the recirculati...

Страница 21: ...line on the HPWH to help prevent scale build up in the heat exchanger Service costs to clear blockages from the HPWH unit s heat exchanger due to debris are not covered under the limited warranty ELEC...

Страница 22: ...ey on the Touchscreen Monitor the refrigerant pressure hot water in and out temperatures and cold water in and out temperatures Itmaybehelpfultorecordtheoperatingdatainitiallyevery10 to15minutesjustto...

Страница 23: ...ince they will always start and run in the proper direction Three phase compressors will rotate in either direction depending upon phasing of the power to L1 L2 and L3 Since there is a 50 50 chance of...

Страница 24: ...inimum of water piping between the HPWH and the water system or tank Throttling should be done in small increments no more than 1 8 turn of the valve handle at a time The HPWH must be allowed to run f...

Страница 25: ...TER PANEL ALARM SCREEN MASTER PANEL CONFIGURATION SCREEN MASTER SCREEN TERMINOLOGY HOME SCREEN LP Low Pressure indicates the suction line pressure on the low side of the system HP High Pressure indica...

Страница 26: ...pDiff Temperature Difference sets the difference below the setpoint where the master will give a call for members to run SAVE button Saves the Tank Diff Set and System Timer parameters Master IP Addre...

Страница 27: ...ME SCREEN OPERATING AS A SINGLE UNIT IN DEFROST SINGLE UNIT HOME SCREEN DISPLAYING ALARM SINGLE UNIT ALARM SCREEN SINGLE UNIT PIPE CONFIGURATION SCREEN SINGLE UNIT TANK CONFIGURATION SCREEN SINGLE UNI...

Страница 28: ...n short cycling OUTLET FLOW indicates if the unit has alarmed out on condenser water flow Evap Flow indicates if the evaporator has flow M PROTECTION indicates if the unit has alarmed out on motor pro...

Страница 29: ...l from the insulation using a vacuum device with a HEPA filter 99 97 efficient at 0 3 micron particles Be careful not to tear the insulation during the cleaning procedure 4 Apply the microbial cleanin...

Страница 30: ...ould be 8 F to 12 F 4 4 C to 6 7 C BRAZE PLATE CLEANING INSTRUCTIONS In some applications the heat exchanger may be subjected to severe fluid conditions including high temperature hard water condition...

Страница 31: ...d Shut off valves are partially closed Thermostat setting should not exceed 160 F Keep heat pump off until room temperature is back in operating range Low water ow corrections Replace unit pump Reduc...

Страница 32: ...K ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER THERMAL...

Страница 33: ...TION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO HP WATER HEATER THERMOWELL THERMAL STORAGE...

Страница 34: ...GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER HP WATER HEATER MASTER CONTROL PANEL RECOMMENDED FOR MU...

Страница 35: ...HECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING HP WATER HEATER THERMOWELL THERMAL STORAGE COLD WATER SUPPLY...

Страница 36: ...SINGLE HEATER MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOURCE WATE...

Страница 37: ...HEATER REVERSE RETURN MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOUR...

Страница 38: ...en the heat pump water heater is installed in accordance with local plumbing and building codes ordinances and regulations the warrantor s printed instructions provided with it and good industry pract...

Страница 39: ...35 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...

Страница 40: ...36 Service Log Issue Description Date Servicer...

Страница 41: ...Service Log Issue Description Date Servicer 37...

Страница 42: ...Notes 38...

Страница 43: ......

Страница 44: ......

Отзывы: