CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,
BURNERS AND FLUE TUBES AND CREATES A RISK OF
ASPHYXIATION.

MECHANICAL EXHAUSTING OF ROOM AIR

Where an exhaust fan is installed in the same room with a heater,
sufficient openings for air must be provided in the walls.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN
INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION.  SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction,
unconfined spaces may provide adequate air for combustion,
ventilation, and draft hood dilution.

If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping,
heavy insulation, caulking, vapor barrier, etc.), air for combustion,
ventilation and draft hood dilution must be obtained from outdoors.
The installation instructions for confined spaces in tightly
constructed buildings must be followed to ensure adequate air
supply.

CONFINED SPACE

When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN
OR WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE
IN OR WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM.
Each opening shall have a free area of at least one square inch
per 1000 Btuh of the total input of all appliances in the enclosure,
but not less than 100 square inches.

If the confined space is within a building of tight construction, air
for combustion, ventilation and draft hood dilution must be
obtained from outdoors.  When directly communicating with the
outdoors through vertical ducts, two permanent openings, located
in the above manner, shall be provided.  Each opening shall have
a free area of not less than one square inch per 4000 Btuh of the
total input of all appliances in the enclosure.  If horizontal ducts
are used, each opening shall have a free area of not less than
one square inch per 2000 Btuh of the total input of all appliances
in the enclosure.

VENTING

 WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES.  SUCH CONDITIONS
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Type B venting may be used with these heaters.  All local and
utility regulations on venting should be followed.

BAROMETRIC DRAFT CONTROL ASSEMBLY

A double-acting barometric draft control assembly is provided with
each unit.  The draft control assembly must be installed without
alteration.  This assembly is factory adjusted for horizontal
application only and must be attached to the heater as shown in

figure 4.  The outlet of the draft control assembly may be rotated
to face in direction needed.  The assembly must be fitted to the
jacket cover such that it is plumb and level to the ground.  Fasten
the draft control assembly to the top cover using sheet metal
screws at three locations, or more, as required.

Dampers or other obstructions must not be installed between the
heater and the barometric draft control assembly.

Do not adjust settings on gate.  Counterweight washers are factory
adjusted and should result in breeching pressure measurements
at the combustion test hole (fig. 4) within the range shown in
table 6.

NOTE:

A negative draft must be maintained in the vent piping.

When installed, the damper gate must pivot freely in the ring
guides.  This gate will automatically adjust to regulate the chimney
draft imposed on the heater.

         

PROPER DRAFT CONTROLLER AND

VENT PIPE INSTALLATION

FIGURE 4

VENT CONNECTION

Vent connections must be made to an adequate stack or chimney.
Refer to the National Fuel Gas Code (latest version) or to the
vent pipe manufacturer’s gas vent and chimney sizing table to
properly design and size the venting system.  Refer to Table 3 for
the vent pipe size required for installation to the barometric draft
control assembly outlet.

TABLE 3 - BAROMETRIC DRAFT CONTROL

ASSEMBLY OUTLET SIZE

DRAFT CONTROL

MODEL

OUTLET DIAMETER

***81-140

6”

***81-199

6”

***81-270

8”

***81-370

8”

Where an existing chimney or vent is to be used, be sure that the
chimney or vent has adequate capacity for the number and sizes
of gas appliances being vented through it.  Inspect the chimney
or vent and remove all soot or other obstructions which will retard
free draft.

Vent connectors making horizontal runs must have a minimum
upward slope toward the chimney or vent of 1/4 inch per foot.
Vent connector length should be kept as short as possible.  Be
sure that the vent pipe does not extend beyond the inside wall of
a chimney.

Содержание ***81-140

Страница 1: ...ance PLACETHESEINSTRUCTIONSADJACENTTOHEATERAND NOTIFYOWNERTOKEEPFORFUTUREREFERENCE PRINTED IN U S A 1102 PART NO 195091 000 CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOU...

Страница 2: ...NSUMPTION AND PERFORMANCE DATA STORAGE MAXIMUM MODELS CAPACITY IMPUT RATING RECOVERY RATE RECOVERY RATE AMPERES U S GALLONS BTU HR GPH 100 F RISE GPH 140 F RISE 120V 60Hz 1 81 140 81 140 000 136 97 5...

Страница 3: ...stion 4 Liquid Petroleum Models 4 Extended Non Use Periods 4 Insulation Blankets 4 High Altitude Installation 4 5 FEATURES High Limit Switch E C O 5 Circulating Pump 5 Dishwashing Machine Requirements...

Страница 4: ...injury under these conditions it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system If h...

Страница 5: ...No 70 Only all bronze circulators are used with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please r...

Страница 6: ...ce under the heater with the hollows running continuously and horizontally A 3 16 inch steel plate must cover the concrete blocks see fig 2 NOTE If electrical conduits run under the floor of the propo...

Страница 7: ...TION OF FLUE GASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION Type B venting may be used with these heaters All local and utility regulations on venting should be followed BAROMET...

Страница 8: ...verly tighten the bolts or the cleanout gasket will be damaged Tighten each bolt gradually and alternate between opposed bolts on the cleanout cover BURNER INSTALLATION Remove the factory installed in...

Страница 9: ...HE DRIP LEG MUST BE READILY ACCESSIBLE REFER TO FIG 8 AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVICING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE L...

Страница 10: ...m 3 This unit may NEVER be connected to any existing heating system or component s previously used with a non potable water heating appliance 4 When the system requires water for space heating at temp...

Страница 11: ...11 WIRING FOR 81 140 THRU 81 370 FIGURE 9 SCHEMATIC DIAGRAM WIRING DIAGRAM...

Страница 12: ...GE 17 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW...

Страница 13: ...R WITHOUT RECIRCULATION FOR STORAGE OR INSTANTANEOUS HEATERS ONLY TWO TEMPERATURE TWO PRE HEATERS HIGH TEMPERATURE STORAGE WITH OR WITHOUT RECIRCULATION FOR STORAGE OR INSTANTANEOUS HEATERS ONLY CAUTI...

Страница 14: ...SEE MANIFOLD KIT SPECIFICATIONS WIRING DIAGRAM FOR FIXTURE OR BOOSTER LOOP IF USED OTHER THAN DISHWASHER PIPE RELIEF VALVE TO OPEN DRAIN TEMPERATURE SETTING OF PRE HEATER SHOULD BE 120 F MIN OR 150 F...

Страница 15: ...OR TWO TEMPERATURE ONE HEATER MEDIUM TEMPERATURE STORAGE WITH RECIRCULATED LOOP FOR STORAGE OR INSTANTANEOUS HEATERS ONLY CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE O...

Страница 16: ...d storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kits Dimension...

Страница 17: ...pressure tapping Check voltage at disconnect switch to make certain that it matches that shown on the burner label Apply a few drops of No 20 SAE non detergent oil to motor bearings Drill max 5 16 ho...

Страница 18: ...NFORMATION ABOVE ON THIS LABEL 2 REMOVE APPLIANCE THERMOSTAT COVER ROTATE THE THERMOSTAT DIAL COUNTERCLOCKWISE TO LOWEST SETTING 3 TURN OFF ALL ELECTRIC POWER TO THE APPLIANCE 4 THIS APPLIANCE IS EQUI...

Страница 19: ...altitude up to 2000 feet as it is within 2 of the rated input For installations at higher altitudes the input will be less for the reasons explained in the FOREWORD The input may be adjusted by adjus...

Страница 20: ...is suggested the drain valve be left open during this period Reverse these instructions when restoring hot water service SEDIMENT REMOVAL Waterborne impurities consist of fine particles of soil and s...

Страница 21: ...y lowering the pressure Contact your water supplier or local plumbing inspector on how to control this situation Two common corrections are listed in the Checklist and Service Information which appear...

Страница 22: ...re 4 Colder incoming water temperature will lengthen the time required to heat water to the desired temperature If the heater was installed when incoming water temperature was warm colder water create...

Страница 23: ...y terminal 4 and strip terminal 2 If no voltage motor relay is defective If voltage present motor is defective MOTOR RUNS IN REPEATED CYCLES NO FLAME PRESENT 1 Motor relay drops out due to low voltage...

Страница 24: ...No Decimal 81 140 HSG 200 62459 001 0 24 62459 001 0 209 81 199 HSG 200 62459 001 0 38 62459 001 0 257 81 270 HSG 400 62459 002 0 368 62459 002 0 302 81 370 HSG 400 62459 002 0 532 62459 002 0 386 MAI...

Страница 25: ...659 160659 160659 160659 ASME 68065 68065 68065 68065 California 42985 42985 42985 42985 Caution Electric 98299 98299 98299 98299 Cleanout 97444 97444 97444 97444 Clearance 190105 190105 190105 190105...

Страница 26: ...26 MODELHSG200 400GASBURNER...

Страница 27: ...er 6206 25 17 Air Proving Switch Only 6206 26 18 Air Proving Switch Mounting Plate Slot Cover Assembly 6206 27 19 Thermostat Terminal Strip 6206 28 20 Adjustment Arm Off Cycle Damper 6206 29 21 Off Cy...

Страница 28: ...28...

Отзывы: