Installation & Operation Manual
2
Venting
22
TABLE - 2B
VERTICAL VENT/AIR KITS
MODEL
HORIZONTAL KIT*
VERTICAL KIT*
400
9910113000
9910111000
500
9910113000
9910111000
650
9910113001
9910111001
750
9910113001
9910111001
1000
9910113002
9910111002
1250
9910113003
9910111003
1450
9910113003
9910111003
1800
9910113003
9910111003
2100
9910113003
9910111003
*The SVK kits include a DV box adapter and sidewall air inlet cap. The VDK kits include a DV box adapter and a rooftop air inlet cap.
IMG00586
12"
MIN
3'
MIN
Figure 2-8_Vertical Vent/Ducted Air
Installation w/Rooftop Combustion Air Inlet
WARNING
Only use a sidewall air inlet cap supplied by the appliance
manufacturer or a rooftop air inlet cap supplied by either the vent
or appliance manufacturer. Using any other air inlet cap for single
unit installations or using a common air inlet cap for multiple
units with insufficient free area and/or protections from wind and
weather may result in operational problems and the spillage of
flue products. Spillage of flue products can cause personal injury
or death due to carbon monoxide poisoning.
For single unit installations with sidewall air inlet you must order the sidewall air
inlet kit from the appliance manufacturer. The part number for each SVK kit is
listed by unit size in Table 2B.
For single unit installations with rooftop air inlet (see FIG. 2-8), you must order
the rooftop air inlet kit from the appliance manufacturer. The part number for
each VDK kit is listed by unit size in Table 2B. Purchase the flue pipe, rooftop
flue termination, and air inlet pipe locally.
There is no vent kit for combined air supply systems for multiple units. Make
sure the air inlet cap is properly sized. You must purchase this cap locally.
Venting of flue products
For venting flue products vertically to the outdoors, follow all requirements in
the installation instructions for conventional venting in this manual.
Follow all clearance requirements in Vertical Vent Termination Clearances and
Location on page 18.
A barometric damper is not required in the flue on Vertical Vent/Air
installations if the draft is within the negative 0.02 to 0.08 inches w.c. required
for proper operation. If the draft exceeds this range, install a barometric damper.