PREVENTIVE MAINTENANCE

RECOMMENDED PROCEDURE FOR PERIODIC

REMOVAL OF LIME DEPOSITS FROM COIL

TYPE COMMERCIAL WATER HEATERS

The amount of calcium carbonate (lime) released from water is in
direct proportion to water temperature and usage, see fig. 17.

 CAUTION

DO NOT USE A NYLON BRUSH OR OTHER STATIC CREATING
MATERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM
HEATING SURFACES AND VENT.

SUCH DEPOSITS ARE FLAMMABLE AND MAY BE IGNITED
BY STATIC ELECTRICITY.  USE A METAL BRUSH TO MINIMIZE
THE DANGER OF EXPLOSION.

1. Turn off the electrical power and main manual gas shutoff valve.

Allow heater parts and vent to cool before disassembly.

2. Remove the heater draft diverter and vent pipe running to the

chimney.

Check parts and chimney for obstructions and clean as
necessary.

Replace any damaged or deteriorated parts of the venting
system.

3. Remove burners from heater and other metal parts as required

to clean and vacuum the heat exchangers and combustion
coils.

Refer to parts list supplied with this manual for disassembly
aid.

4. Reinstall the parts removed in steps 2 and 3.

Be sure the vent pipe has a minimum upward pitch of one
quarter inch per foot of length and is sealed as necessary.

5. Restore electrical power and gas supply to heater.

Check for gas leaks and proper heater and vent operation.

Upon reassembly, a negative draft must be produced by the
system.  Check for proper draft by holding a lit match near the
draft hood opening while the heater is operating.  The flame should
be drawn into the draft hood opening indicating proper draft.

GAS PRESSURE REGULATOR

The gas pressure regulator is included in the combination gas
valve, fig.14, and is set to operate on the gas specified on the
heater model and rating plate.

Periodically check main burner, fig. 13, and pilot flame, fig. 15, for
proper operation.  This should be checked every six months.

Do not subject the gas valve to inlet gas pressure of more than
10.5" W.C. - natural gas, 13.0" W.C. - propane gas.  If higher gas
pressures are encountered, a service regulator is necessary.

Check for a minimum inlet gas pressure value shown on the Rating
Plate before making any adjustment of the regulator.

Attempts to adjust the regulator during periods of low gas supply
pressure could result in overfiring of the heater when the gas
supply pressure returns to normal.

DO NOT INCREASE PRESSURE ABOVE THAT SPECIFIED AS
OVERFIRING WILL RESULT IN DAMAGE TO THE HEATER
.
If gas pressure regulator cannot be adjusted to correct pressure

with sufficient gas pressure at the valve, replace with new gas
valve.

RELIEF VALVE

At least twice a year the system relief valves should be checked
to ensure that they are in operating condition.  To check a relief
valve, lift the lever at the end of the valve several times.  The
valve should seat properly and operate freely.

 CAUTION

BEFORE MANUALLY OPERATING A RELIEF VALVE, MAKE
SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE
VALVE TO DIRECT DISCHARGE TO AN OPEN DRAIN.
FAILURE TO TAKE THIS PRECAUTION COULD MEAN
CONTACT WITH EXTREMELY HOT WATER EXITING THE
VALVE DURING THE CHECK OPERATION.

If a relief valve discharges periodically or continuously, it may be
due to thermal expansion of water in a closed water supply system,
or, it may be due to a faulty relief valve.

Thermal expansion is the normal response of water when it is
heated.  In a closed system, thermal expansion will cause the
system pressure to build until the relief valve actuation pressure
is equaled.  Then the relief valve will open allowing some water to
escape, slightly lowering the pressure.

Installation of a properly sized thermal expansion tank will usually
correct this problem. Contact your water supplier or local plumbing
inspector for information on how to best correct this situation.

ABOVE ALL DO NOT PLUG ANY RELIEF VALVE.  THIS IS NOT
A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION.

CIRCULATING PUMP

The circulating pump may require occasional lubrication.  Refer
to circulator manufacturer’s instructions for lubrication procedures,
and lubrication frequency.

ELECTRICAL SERVICE

 

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS.  WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

REPLACEMENT PARTS

Replacement parts may be ordered through A. O. Smith dealers,
authorized servicers or distributors.  Refer to the Yellow Pages
for where to call or contact the A. O. Smith Water Products
Company, 5621 West 115th Street, Alsip, IL 60803,
1-800-433-2545,  or on the web at www.hotwater.com/parts.  When
ordering parts be sure to state the quantity, part number and
description of the item including the complete model and serial
number as it appears on the product.  Refer to the parts list for
more information.

The higher the water temperature or water usage, the more lime
deposits are dropped out of the water.  This is the lime scale
which forms in pipes, heaters and on cooking utensils.

Lime accumulation not only reduces the life of the equipment,
but also reduces efficiency of the heater and increases fuel
consumption.

Содержание 160M

Страница 1: ...structions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity o...

Страница 2: ...0 3 4 527 E 5 1 2 140 5 1 2 140 5 1 2 140 5 1 2 140 F 10 254 10 254 10 254 10 254 G 11 13 16 300 11 13 16 300 11 13 16 300 11 13 16 300 H 6 152 7 178 7 178 7 178 J 26 11 16 678 26 11 16 678 26 11 16 6...

Страница 3: ...io M3B 2R3 Canada TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 3 GENERAL SAFETY INFORMATION 3 Precautions 3 4 Grounding Instructions 4 Chemical Vapor Corrosion 4 Liquid Petroleum Models 4 High Alt...

Страница 4: ...F THE BURNER ORIFICE IN ACCORDANCE WITH SECTION 8 1 2 OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 FOR CANADIAN INSTALLATIONS CONSULT CANADIAN INSTALLATION CODES AND CAN CGA B149 FAILURE TO REPLACE THE O...

Страница 5: ...t remove the protector switch cover and push the reset button after the coil surface temperature cools to less than 2000 F 93 3 C FIGURE 2 DO NOT RESET THIS SWITCH WITHOUT PERFORMING THE SYSTEM CHECKS...

Страница 6: ...lectrical requirements of the system Typically the thermostat should have motor full load and locked rotor current ratings which exceed the total amount of current required to drive the pump s control...

Страница 7: ...s exactly when inserting this switch into a pipe tee This is necessary in order to assure positive action of the switch with water flow Once the minimum flow rate Table 5 through the heater is reached...

Страница 8: ...ADJACENT TO THE HEATER OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER For appliance installation in locations with elevations above 2 000 feet 600M...

Страница 9: ...ted A special vent cap may be required FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS If the back draft cannot be corrected by the normal methods or if a suitable dra...

Страница 10: ...ent relief valve operation This is not a warranty failure An expansion tank may be necessary in the cold water supply to alleviate this situation Contact the local plumbing authority WATER LINE CONNEC...

Страница 11: ...TEMPERATURE ONLY FIGURE 7 DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY T...

Страница 12: ...SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VA...

Страница 13: ...TTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCA...

Страница 14: ...HEATER AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1 2 PSIG THE GAS SUPPLY LINE MUST BE CAPPED WHEN NO...

Страница 15: ...connection All piping diagrams include an electrical wiring diagram to assist the installer in properly wiring of the additional components required to assure correct system operation Figures 11 and...

Страница 16: ...16 ELECTRICAL WIRING DIAGRAMS FOR THE HW 120M 160M AND 200M WATER HEATERS I I D SYSTEM PROPANE FIGURE 12 NOTES...

Страница 17: ...Y PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE TO AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND...

Страница 18: ...SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER E DO NOT OPERATE APPLIANCE UNLESS UNIT IS FILLED WITH WATER AN...

Страница 19: ...to OFF See page 18 2 Attach a pressure gauge or a manometer to the outlet pressure tap figure 14 and refer to table 3 for correct manifold pressure 3 Fire the heater by turning the gas valve control...

Страница 20: ...arp metal objects to clean blocked orifices as they will damage the soft brass orifice Remove any soot or carbon deposits with a rag making sure to remove any lint left on burner by vacuuming again MA...

Страница 21: ...ontrol is out of calibration replace control AUTOMATIC GAS SHUTOFF CONTROL The automatic gas shutoff control fig 1 is an automatic device which is wired in series with the gas valve and intermittent i...

Страница 22: ...pressure regulator cannot be adjusted to correct pressure with sufficient gas pressure at the valve replace with new gas valve RELIEF VALVE At least twice a year the system relief valves should be ch...

Страница 23: ...upper deliming tee Open drain cock and drain heater Install standpipe in lower deliming tee or in tee from which pressure relief valve has been removed 4 Close drain valve 5 Slowly pour 3 gallons of...

Страница 24: ...burner shut remain on differential wide tank water temperature off With thermal Tank temperature control Replace balancer pump off defective delay of approx imately 2 minutes System wiring is incorre...

Страница 25: ...y plugged into module Is green ground wire firmly attached to mounting screw and GND terminal on module Ensure ground strap is the closest metal to the igniter sensor rod electrode to prevent the spar...

Страница 26: ...l on module Is pilot burner ignition cable in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor rod electrode to prevent the spark from shortin...

Страница 27: ...d in good condition not broken or cracked Are the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the installation...

Страница 28: ...r charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and administrative charges for forwarding the new heater or replacement pa...

Отзывы: