GAS CONNECTIONS

 WARNING

THE INLET GAS PRESSURE MUST NOT EXCEED THE VALUE
SPECIFIED BY THE MANUFACTURER ON THE RATING PLATE
(10.5" W.C. - NATURAL GAS, 13.0" W.C. - PROPANE GAS).
EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE
DAMAGE TO THE GAS VALVE WHICH COULD RESULT IN FIRE
OR EXPLOSION.  IF OVERPRESSURE HAS OCCURRED SUCH
AS THROUGH IMPROPER TESTING OF GAS LINES OR
EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE
GAS VALVE MUST BE CHECKED FOR SAFE OPERATION.  MAKE
SURE THAT THE OUTSIDE VENTS ON THE SUPPLY
REGULATORS AND  THE  SAFETY  VENT  VALVES ARE
PROTECTED AGAINST BLOCKAGE.  THESE ARE PARTS OF
THE GAS SUPPLY SYSTEM, NOT THE HEATER.  VENT
BLOCKAGE MAY OCCUR DURING ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS
PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT
TRAP OR DRIP LEG), MUST BE INCORPORATED IN THE
PIPING. 

 SEE PIPING DIAGRAMS.  THE DIRT LEG MUST BE

READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING
CONDITIONS.  INSTALL IN ACCORDANCE WITH
RECOMMENDATIONS OF SERVING GAS SUPPLIERS.  IN THE
UNITED STATES REFER TO ANSI Z223.1-1999 OR MOST
RECENT EDITION OF THE NATIONAL FUEL GAS CODE. IN
CANADA, THE CANADIAN INSTALLATION CODE CAN/CGA
B 149 (LATEST EDITION).

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve gas inlet.

Fittings and unions in the gas line must be metal to metal type.

Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints.  Do not apply compound to the first two
threads.  Use compounds resistant to the action of liquefied
petroleum gases.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE.  Use soap and water solution or other material

acceptable for the purpose in locating gas leaks.  DO NOT USE
MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION FOR THIS PURPOSE.

DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING
ANY PRESSURE TESTING OF THAT SYSTEM AT TEST
PRESSURES IN EXCESS OF 1/2 PSIG.  THE GAS SUPPLY
LINE MUST BE CAPPED WHEN NOT CONNECTED TO
HEATER.

THE HEATER MUST BE ISOLATED FROM THE GAS SUPPLY
PIPING SYSTEM BY CLOSING ITS MANUAL GAS SHUTOFF
VALVE DURING ANY PRESSURE TESTING OF THE GAS
SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO
OR LESS THAN 1/2 PSIG (3.44kPa).

CORRECT GAS

MAKE SURE the gas on which the heater will operate is the same
as that specified on the heater model and rating plate.  Do not
install the heater if equipped for a different type gas - contact the
heater supplier.

SIZING GAS SUPPLY LINE

The iron pipe or equivalent pipe sizes in Table 6 are derived from
Table C-3 in the NATIONAL FUEL GAS CODE.  The pipe sizes
are based on a supply line gas pressure drop of 0.3 inches of
water column from the gas meter to the point of installation of the
heater(s).  For natural gas, a heating value of 1050 Btu/ft

3

 and a

specific gravity of 0.60 has been assumed.  A heating value of
2500 Btu/ft

3

 and a specific gravity of 1.53 has been assumed for

L.P. (propane) gas.

Where it is necessary to use an excess number of pipe fittings,
i.e., elbows, tees and valves, in the gas supply line, use pipe at
least one size larger than that recommended in Table 2 to
compensate for the increased pressure drop.

If the service pressure is 4.5 inches W.C. (1.12kPa) (11 inches
(1.74kPa) for L.P. gas) of water column or less, use pipe size
larger than specified in Table 6 to minimize pressure drop in the
line.

GAS METER SIZE - City Gases Only

Be sure that the gas meter has sufficient capacity to supply the
full rated gas input of the heater as well as the requirements of all
other gas fired equipment supplied by the meter.  If gas meter is
too small, ask the gas company to install a larger meter having
adequate capacity.

 

TABLE 6

  GAS SUPPLY PIPE SIZES (IN INCHES)

                                NATURAL GAS (1050 Btu/ft

3

)

PROPANE GAS (2500 Btu/ft

3

)

Distance To Heater

From Meter (FT./M)

HW-120M

HW-160M

HW-200M

HW-225M

HW-120M

HW-160M

HW-200M

10 (3M)

1/2

3/4

3/4

3/4

1/2

1/2

1/2

30 (9.1M)

3/4

3/4

1

1

1/2

3/4

3/4

50 (15.2M)

3/4

1

1

1

3/4

3/4

1

80 (24.4M)

1

1

1 1/4

1 1/4

3/4

1

1

100 (30.5M)

1

1 1/4

1 1/4

1 1/4

3/4

1

1

150 (45.7M)

1

1 1/4

1 1/4

1 1/4

1

1

1 1/4

200 (61M)

1 1/4

1 1/4

1 1/4

1 1/2

1

1 1/4

1 1/4

Содержание 160M

Страница 1: ...structions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity o...

Страница 2: ...0 3 4 527 E 5 1 2 140 5 1 2 140 5 1 2 140 5 1 2 140 F 10 254 10 254 10 254 10 254 G 11 13 16 300 11 13 16 300 11 13 16 300 11 13 16 300 H 6 152 7 178 7 178 7 178 J 26 11 16 678 26 11 16 678 26 11 16 6...

Страница 3: ...io M3B 2R3 Canada TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 3 GENERAL SAFETY INFORMATION 3 Precautions 3 4 Grounding Instructions 4 Chemical Vapor Corrosion 4 Liquid Petroleum Models 4 High Alt...

Страница 4: ...F THE BURNER ORIFICE IN ACCORDANCE WITH SECTION 8 1 2 OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 FOR CANADIAN INSTALLATIONS CONSULT CANADIAN INSTALLATION CODES AND CAN CGA B149 FAILURE TO REPLACE THE O...

Страница 5: ...t remove the protector switch cover and push the reset button after the coil surface temperature cools to less than 2000 F 93 3 C FIGURE 2 DO NOT RESET THIS SWITCH WITHOUT PERFORMING THE SYSTEM CHECKS...

Страница 6: ...lectrical requirements of the system Typically the thermostat should have motor full load and locked rotor current ratings which exceed the total amount of current required to drive the pump s control...

Страница 7: ...s exactly when inserting this switch into a pipe tee This is necessary in order to assure positive action of the switch with water flow Once the minimum flow rate Table 5 through the heater is reached...

Страница 8: ...ADJACENT TO THE HEATER OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER For appliance installation in locations with elevations above 2 000 feet 600M...

Страница 9: ...ted A special vent cap may be required FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS If the back draft cannot be corrected by the normal methods or if a suitable dra...

Страница 10: ...ent relief valve operation This is not a warranty failure An expansion tank may be necessary in the cold water supply to alleviate this situation Contact the local plumbing authority WATER LINE CONNEC...

Страница 11: ...TEMPERATURE ONLY FIGURE 7 DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY T...

Страница 12: ...SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VA...

Страница 13: ...TTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 19 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCA...

Страница 14: ...HEATER AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1 2 PSIG THE GAS SUPPLY LINE MUST BE CAPPED WHEN NO...

Страница 15: ...connection All piping diagrams include an electrical wiring diagram to assist the installer in properly wiring of the additional components required to assure correct system operation Figures 11 and...

Страница 16: ...16 ELECTRICAL WIRING DIAGRAMS FOR THE HW 120M 160M AND 200M WATER HEATERS I I D SYSTEM PROPANE FIGURE 12 NOTES...

Страница 17: ...Y PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE TO AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND...

Страница 18: ...SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER E DO NOT OPERATE APPLIANCE UNLESS UNIT IS FILLED WITH WATER AN...

Страница 19: ...to OFF See page 18 2 Attach a pressure gauge or a manometer to the outlet pressure tap figure 14 and refer to table 3 for correct manifold pressure 3 Fire the heater by turning the gas valve control...

Страница 20: ...arp metal objects to clean blocked orifices as they will damage the soft brass orifice Remove any soot or carbon deposits with a rag making sure to remove any lint left on burner by vacuuming again MA...

Страница 21: ...ontrol is out of calibration replace control AUTOMATIC GAS SHUTOFF CONTROL The automatic gas shutoff control fig 1 is an automatic device which is wired in series with the gas valve and intermittent i...

Страница 22: ...pressure regulator cannot be adjusted to correct pressure with sufficient gas pressure at the valve replace with new gas valve RELIEF VALVE At least twice a year the system relief valves should be ch...

Страница 23: ...upper deliming tee Open drain cock and drain heater Install standpipe in lower deliming tee or in tee from which pressure relief valve has been removed 4 Close drain valve 5 Slowly pour 3 gallons of...

Страница 24: ...burner shut remain on differential wide tank water temperature off With thermal Tank temperature control Replace balancer pump off defective delay of approx imately 2 minutes System wiring is incorre...

Страница 25: ...y plugged into module Is green ground wire firmly attached to mounting screw and GND terminal on module Ensure ground strap is the closest metal to the igniter sensor rod electrode to prevent the spar...

Страница 26: ...l on module Is pilot burner ignition cable in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor rod electrode to prevent the spark from shortin...

Страница 27: ...d in good condition not broken or cracked Are the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the installation...

Страница 28: ...r charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and administrative charges for forwarding the new heater or replacement pa...

Отзывы: