LOW GAS PRESSURE SWITCH

(SEE FIGURE 12)

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch
that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa)  W.C.
is encountered. The contacts will open when the pressure falls below the
fixed set point of 4.8"WC (1.18Kpa) for natural gas models and 8.5"WC
(2.08Kpa) for propane models. The LGS monitors the gas supply pressure
to the  heater. If the gas supply falls below 4.8"WC (1.18Kpa), the main
burner is extinguished (if heater is running) or the heater will not start up.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch. This
switch provides 120V from the line source to the heater.

 CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL WIRE
TO GROUND CHECK INDICATES ZERO VOLTAGE.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high
temperature (>1800°F or >982°C). When 120VAC is applied to the igniter,
sufficient heat is generated to ignite the main burner. Although improvements
have been made to strengthen the igniter, it is still fragile and care must be
taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas
service is available and to review applicable installation codes for your
area.

Size the main gas line in accordance with Table 3. The figures shown are
for straight lengths of pipe at 0.5" (125Pa) W.C. pressure drop, which is
considered normal for low pressure systems Note that fittings such as
elbows and tees will add to the pipe pressure drop.

 CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET

OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5") Water Column and 0.6
Specific Gravity Gas and max. gas pressure of 0.5 psig)

CONTROLS AND SWITCHES

All BTH models are provided with four pressure switches. These switches
are essential to the safe and proper operation of the unit. All switches are
wired in series. The controller is set up to shut the unit down whenever
there is a failure of any of the switches. It is important to understand the
purpose of each switch.

FIGURE 12.

BLOWER PROVER SWITCH

(SEE FIGURE 12)

The Blower Prover Switch is provided on the heater to verify that the fan is
operating. It is a positive pressure switch whose electrical contacts are
normally open. When the fan increases the pressure in the burner, the
pressure switch will allow the electrical contacts to close. The pressure
switch is connected to the burner tap by a piece of tygon tubing. This
tubing must be connected in order for the switch to change the electrical
contacts. The controller requires that the electrical contacts on this air flow
switch be open before it will allow the blower to come on.

BLOCKED OUTLET PROVER SWITCH

(SEE FIGURE 12)

The Blocked Outlet Prover Switch is set up to shut the unit off when a build-
up of positive pressure in the exhaust vent pipe occurs. This switch is a
positive pressure switch that requires an increase in pressure to change
the electrical contacts from normally closed to open. When this switch
prevents the unit from igniting, most likely the exhaust is blocked by some
means Check to see if the condensate is allowed to flow freely from the
exhaust elbow and for obstructions in the exhaust venting and exhaust
vent terminal. Also verify that there is no more than fifty equivalent feet
(15.2 m)  of three inch PVC vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH

(SEE FIGURE 12)

The Blocked Inlet Prover Switch is set up to shut the unit off when a build-
up of negative pressure in the intake vent pipe occurs. This switch is a
negative pressure switch that requires an increase in negative pressure to
change the electrical contacts from normally closed to open. The switch is
connected to the pressure tap on the PVC flange connected to the inlet of
the blower. When this switch prevents the unit from igniting, most likely the
intake is blocked by some means. Check to see if there is no more than fifty
equivalent feet (15.2 m) of three inch PVC vent pipe on the intake. Also
verify that the intake and intake vent terminal is free of obstructions that
may prevent air from entering the unit.

  LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

    INPUT IN THOUSANDS BTU/HR

 FEET

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175

360

680

1400

2100

3960

6300

11000 23000

20

120

250

485

950

1460

2750

4360

7700

15800

30

97

200

375

770

1180

2200

3520

6250

12800

40

82

170

320

660

990

1900

3000

5300

10900

50

73

151

285

580

900

1680

2650

4750

9700

60

66

138

260

530

810

1520

2400

4300

8800

70

61

125

240

490

750

1400

2250

3900

8100

80

57

118

220

460

690

1300

2050

3700

7500

90

53

110

205

430

650

1220

1950

3450

7200

100

50

103

195

400

620

1150

1850

3250

6700

125

44

93

175

360

550

1020

1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

  LENGTH

NORMAL IRON PIPE SIZES (INCHES)

 IN

                  INPUT IN KW

  METERS 1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

3.0

51

105

199

410

615

1160

1845

3221

6735

6.1

35

73

142

278

428

805

1277

2255

4626

9.1

28

59

110

225

346

644

1031

1830

3748

12.2

24

50

94

193

290

556

878

1552

3192

15.2

21

44

83

170

264

492

776

1391

2840

18.3

19

40

76

155

237

445

703

1259

2577

21.3

18

37

70

143

220

410

659

1142

2372

24.4

17

35

64

135

202

381

600

1083

2196

27.4

16

32

60

126

190

357

571

1010

2108

30.5

15

30

57

117

182

337

542

952

1962

38.1

13

27

51

105

161

299

483

864

1757

45.7

12

25

47

95

146

278

439

776

1610

53.3

11

23

42

88

135

249

401

717

1464

61.0

10

21

40

82

126

234

375

688

1347

Содержание 100 Series

Страница 1: ...E INSTALLING AND USING THISAPPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result...

Страница 2: ...e Natural Gas and Propane Installation Code and CSAC22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44...

Страница 3: ...ABLE OF CONTENTS ROUGH INDIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 5 INSTALLATIONINSTRUCTIONS 4 12 R...

Страница 4: ...s above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow regulating co...

Страница 5: ...result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction wit...

Страница 6: ...NGERSAREUSED THISPREVENTS ANYVIBRATIONS FROM BEINGTRANSMITTED INTOTHE LIVING SPACES HARDWATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended...

Страница 7: ...ntally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEPCLEAR OFALLOBSTRUCTIONS INSPECTION The stat...

Страница 8: ...U S POWER VENT CANADIAN POWER VENT FIGURE 5b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THEAIR INTAKE IN WINDY COLDAREAS THE MAXIMUM PRACTICALDISTANCE BETWEEN THESE TWO TERMINALS IS R...

Страница 9: ...U S DIRECT VENT CANADIAN DIRECT VENT FIGURE 6b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THEAIR INTAKE IN WINDY COLDAREAS THE MAXIMUM PRACTICALDISTANCE BETWEEN THESE TWO TERMINALS IS...

Страница 10: ...OLLOWED 1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent t...

Страница 11: ...same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust vent t...

Страница 12: ...adhesives or ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY INAWELL...

Страница 13: ...t the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut the u...

Страница 14: ...WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TOTHE NATIONALFUELGAS CODE FIGURE 13 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only Note Do not use wrench on...

Страница 15: ...with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WATER HEATER THE RELIEF V...

Страница 16: ...upply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously use...

Страница 17: ...y the desktop screen if there are no active faults or warnings An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank The...

Страница 18: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Страница 19: ...an occur during operation These are Warnings and Faults Warnings This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optimal...

Страница 20: ...rmation about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE...

Страница 21: ...input Once the unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper opera...

Страница 22: ...cutout at 202 F 94 C The controller must be manually reset by depressing the reset button on front of the control when water temperature drops to below 160 F 71 C TABLE 4 HIGH ALTITUDE INSTALLATIONS...

Страница 23: ...3 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 120 MODELS ONLY...

Страница 24: ...FORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 150 MODELS ONLY OPERATINGINSTRUCTIONS...

Страница 25: ...FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 199 250 MODELS ON...

Страница 26: ...eater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater...

Страница 27: ...may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a closed syste...

Страница 28: ...N OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALLINACCORDANCEWITH LOCALCODES INST...

Страница 29: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Страница 30: ...DANGER TEMPERATURE SETTING SHOULD NOTEXCEED SAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE4 IF HIGHERPREHEATTEMPERATURESARENECESSARYTOOBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCAL...

Страница 31: ...LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATER TEMPERATURE...

Страница 32: ...LDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER...

Страница 33: ...units with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be adde...

Страница 34: ...valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valv...

Страница 35: ...purge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOMENTARILY THEN LOCKS OUT 1 Reset the appliance two more times to ensure that all of the air has be...

Страница 36: ...effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEAND REPA...

Страница 37: ...37 NOTES...

Страница 38: ...38 NOTES...

Страница 39: ...39 NOTES...

Страница 40: ...40 A O SMITH WATER PRODUCTS COMPANY 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 PHONE 1 800 433 2545 FAX 1 800 433 2515 www aosmithwaterheaters com email parts hotwater com...

Отзывы: