A.O. Smith 100 Series Скачать руководство пользователя страница 35

35

MOTOR WILL NOT RUN

1. Confirm 120V AC to the controller. Also, to verify correct polarity, check

for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it connects to
the controller.

2. If there is 120 volts to the controller, check for loose connections or a

locked rotor. If the rotor cannot be freed the motor and blower assembly
must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check for

blockage in the intake and exhaust venting or at the vent hoods. If no
blockage is found, check vinyl tubing for cuts or crimps. If this tubing is
damaged it must be replaced. If these steps do not eliminate the problem,
replace the pressure switches.

5. Check to see if there is resistance across the igniter terminal with an

OHM meter. If there is no continuity, the igniter is broken and should be
replaced.

If the igniter appears to function properly, then verify that the inlet
pressure is within the range shown in Table 4. The gas valve supplied
on the appliance is not designed to open against a higher inlet pressure
of 10.5"WC (2.59kPa) for natural gas and 14.0"WC (3.45kPa) for propane
gas. At this time, also check to make sure the inlet pressure is not lower
than 4.0"WC (.98kPa) for natural gas and 11.0"WC (2.74kPa) for propane
gas. If the inlet pressure is not within these limits then adjust the supply
pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify that the
manifold pressure, when the gas is fully open, with the heater running,
is as called out in Table 4: that is, 4.0"WC (.98kPa) for natural gas and
10.0"WC (2.46kPa) for propane gas for the 120 and 150 models and
0"WC (0kPa) for both natural and propane gas 199 and 250 models. If
the manifold pressure is not correct then adjust accordingly. See
"ADJUSTMENT PROCEDURE" in "OPERATING INSTRUCTIONS" sections
for manifold pressure adjustment procedure.

6. If the inlet and manifold pressures are within the limits specified in step

5, then reset the appliance. Verify 24V AC at the gas valve during the
three (3) second ignition trial, after the igniter reaches operating
temperature. If 24V AC at the gas valve is not seen during this period,
the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition trial
and the manifold pressure does not increase above 0" W.C. then verify
that the manual gas control valve is in the “ON” position (see page 20).
If the valve is in the “ON” position and the previous voltage and gas
pressure conditions are met, then the gas valve is defective and must
be replaced.

Note that a positive manifold pressure reading of approximately
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the ignition
cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air has been

purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition, verify that

the inlet pressure is not greater than 10.5""WC (2.59 kPa) for natural
gas and 14.0"WC (3.45 kPa) for propane gas or lower than the minimal
supply pressure which is 4.0"WC (.09kPa) for natural gas and 11.0"WC
(2.74 kPa) for propane gas. Also, verify that the manifold pressure is
correct, that is, 4.0"WC (.98kPa) for natural gas and 10.0"WC (2.46kPa)
for propane gas for the 120 and 150 models and 0"WC (0kPa) for both
natural and propane gas 199 and 250 models. If the manifold pressure
is not correct then adjust accordingly. See "ADJUSTMENT PROCEDURE"
in "OPERATING INSTRUCTIONS" sections for manifold pressure
adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller is

polarity sensitive. If the hot and neutral supply wires are reversed, the
controller will not sense flame. Reverse the supply wires and try to fire
the unit.

NOTE:  

Always turn off and disconnect main supply wiring before servicing

the unit.

4. Check connecting wire to the flame sensor. Verify that the flame sensor

has not been damaged in any way.

5. Verify that the air supply is adequate. The air inlet screen or blower

wheel may be restricted. Also, check the installation for proper ventilation.
See AIR REQUIREMENTS.

6. Check the venting system for the correct sizing, excess or insufficient.

See VENTING.

7. Check for maximum inlet pressure of 10.5"WC (2.59 kPa) for natural

gas and 14.0"WC (3.45 kPa) for propane gas and the manifold pressure
which is 4.0"WC (.98 kPa) for natural gas and 10.0"WC (2.46 kPa) for
propane gas for the 120 and 150 models and 0"WC (o kPa) for both
natural and propane gas 199 and 250 models. Please note that the
manifold pressure listed is the maximum value for the manifold pressure.
Do not set the manifold pressure higher than the value show in Table 4.
OVER FIRING the heater will result in a rough ignition and/or noisy
operation.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.

 

 

CAUTION

Do not reach into the burner housing or combustion chamber if the heater
is still hot. Allow the heater to cool and always use gloves as the combustion
chamber and the burner sleeve and housing can become very hot after
operation. OVER FIRING is a dangerous condition that must be corrected
immediately.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect,
replace.

REPLACEMENT PARTS

Replacement parts may be ordered through A.O. Smith dealers, authorized
servicers or distributors. Refer to the Yellow Pages for where to call or
contact the A.O. Smith Water Products Company, 500 Tennessee Waltz
Parkway, Ashland City, TN 37015, 1-800-433-2515. When ordering parts
be sure to state the quantity, part number and description of the items
including the complete model and serial number as it appears on the product.
Refer to the parts list for more information.

Содержание 100 Series

Страница 1: ...E INSTALLING AND USING THISAPPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result...

Страница 2: ...e Natural Gas and Propane Installation Code and CSAC22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44...

Страница 3: ...ABLE OF CONTENTS ROUGH INDIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 5 INSTALLATIONINSTRUCTIONS 4 12 R...

Страница 4: ...s above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow regulating co...

Страница 5: ...result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction wit...

Страница 6: ...NGERSAREUSED THISPREVENTS ANYVIBRATIONS FROM BEINGTRANSMITTED INTOTHE LIVING SPACES HARDWATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended...

Страница 7: ...ntally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEPCLEAR OFALLOBSTRUCTIONS INSPECTION The stat...

Страница 8: ...U S POWER VENT CANADIAN POWER VENT FIGURE 5b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THEAIR INTAKE IN WINDY COLDAREAS THE MAXIMUM PRACTICALDISTANCE BETWEEN THESE TWO TERMINALS IS R...

Страница 9: ...U S DIRECT VENT CANADIAN DIRECT VENT FIGURE 6b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THEAIR INTAKE IN WINDY COLDAREAS THE MAXIMUM PRACTICALDISTANCE BETWEEN THESE TWO TERMINALS IS...

Страница 10: ...OLLOWED 1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent t...

Страница 11: ...same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust vent t...

Страница 12: ...adhesives or ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY INAWELL...

Страница 13: ...t the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut the u...

Страница 14: ...WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TOTHE NATIONALFUELGAS CODE FIGURE 13 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only Note Do not use wrench on...

Страница 15: ...with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WATER HEATER THE RELIEF V...

Страница 16: ...upply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously use...

Страница 17: ...y the desktop screen if there are no active faults or warnings An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank The...

Страница 18: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Страница 19: ...an occur during operation These are Warnings and Faults Warnings This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optimal...

Страница 20: ...rmation about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE...

Страница 21: ...input Once the unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper opera...

Страница 22: ...cutout at 202 F 94 C The controller must be manually reset by depressing the reset button on front of the control when water temperature drops to below 160 F 71 C TABLE 4 HIGH ALTITUDE INSTALLATIONS...

Страница 23: ...3 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 120 MODELS ONLY...

Страница 24: ...FORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 150 MODELS ONLY OPERATINGINSTRUCTIONS...

Страница 25: ...FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BTH 199 250 MODELS ON...

Страница 26: ...eater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater...

Страница 27: ...may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a closed syste...

Страница 28: ...N OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALLINACCORDANCEWITH LOCALCODES INST...

Страница 29: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Страница 30: ...DANGER TEMPERATURE SETTING SHOULD NOTEXCEED SAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE4 IF HIGHERPREHEATTEMPERATURESARENECESSARYTOOBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCAL...

Страница 31: ...LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATER TEMPERATURE...

Страница 32: ...LDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER...

Страница 33: ...units with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be adde...

Страница 34: ...valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valv...

Страница 35: ...purge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOMENTARILY THEN LOCKS OUT 1 Reset the appliance two more times to ensure that all of the air has be...

Страница 36: ...effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEAND REPA...

Страница 37: ...37 NOTES...

Страница 38: ...38 NOTES...

Страница 39: ...39 NOTES...

Страница 40: ...40 A O SMITH WATER PRODUCTS COMPANY 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 PHONE 1 800 433 2545 FAX 1 800 433 2515 www aosmithwaterheaters com email parts hotwater com...

Отзывы: