Dry Mode Operation

Dry mode removes humidity from air while maintaining 

specific setpoint temperature. This is done in cooling along 

with electric or hydronic heater. Dry mode will not maintain 

specific humidity level. Unit must be equipped with optional 

electric heat element or hydronic coil.
For Dry Mode operation turn unit on via On/off  button. 

Select Dry mode via Mode button. Room temperature 

is displayed. Then press either Up or Down arrow once, 

setpoint temperature will appear. Setpoint temperature can 

then be changed with each successive press of Up or Down 

arrow or by holding button in.
Place setpoint temperature at desired room temperature. 

Depending on difference between room temperature and 

set point temperature cooling and/or heating will energize. 

If room temperature and setpoint temperature are the 

same unit will operate in cooling and electric heat source 

will also energize.
Should room temperature fall below setpoint temperature 

by two degrees, cooling stops and heating continues to 

boost room temperature back up to stepoint temperature. 

If room temperature rises above setpoint temperature by 

two degrees, heating will stop and cooling will continue 

to bring room temperature back down to stepoint 

temperature. Fan will operate continuously at low speed 

while in Dry Mode.

Optional Electric heat operation

Important: The dip switch 1& 2 must be set to ON

For electric heat operation turn unit on via 

On/Off

  button. 

Select 

Heat 

mode via 

Mode

 button. Room temperature will 

be displayed. Then press either 

Up

 or 

Down

 arrow once, 

setpoint temperature will appear. Setpoint temperature 

can then be changed with each successive press of 

Up

 

or 

Down

 arrow or by holding button in. Place setpoint 

temperature above room temperature. Electric heat will 

energize and heating will continue as long as setpoint 

remains above room temperature. Once room temperature 

is satisfied electric heat cycles off. Fan will operate as 

described in “Fan Operation”

 

(

Figure 5).

Units With Condensate Pumps

EMI Air Handlers are available with optional condensate 

pump. Condensate pumps are recommended when it is 

not possible to gravity drain condensate from indoor unit. 

Depending on pump manufacture maximum lift for pump 

will vary. Consult pump instructions for maximum lift for 

pump being used or refer to specific pump kit information 

and instructions as supplied by EMI. 
Condensate generated by the evaporator will collect in 

pumps’ reservoir. When water level is high enough, float 

switch closes and energizes pump motor clearing water from 

the reservoir. Should the water exceed maximum preset 

level, safety switch will open. This prevents evaporator from 

generating more condensate and spilling out of the unit.

  

OPTIONAL ELECTRIC HEAT OPERATION              

Содержание 1

Страница 1: ...P N 240004373 Rev B 07 15 2013 An ISO 9001 2008 Certified Company ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com CHILLED WATER CEILING SUSPENDED AND HIGH WALL...

Страница 2: ...time without notice and without incurring any obligation whatsoever Unit has been tested and rated in accordance with ANSI AHRI Standards 440 2008 UL 1995 When requesting assistance please have follow...

Страница 3: ...ituation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates information...

Страница 4: ...hors etc Chilled water condensate piping Hot water piping EMI Air Handler is available as wall or ceiling unit two pipe chilled water fan coil model Air handler offers ease of installation operation a...

Страница 5: ...n Audio feedback on control setting changes Fan operation Auto cycling High and Low constant DryMode operatescoolingandelectricheatsimultaneously to remove humidity when optional electric heat is sele...

Страница 6: ...trols 24V control transformer is located in air handler unit This provides low volt control power to air handler Depending on models selected interconnect control wiring may be effected All low Volt i...

Страница 7: ...CH ON RELAY BOARD DIP SWITCH SETTINGS Unit Mount Control Only There are two dip switches on the relay board that offer different modes of operation This allows unit to be matched with either cooling o...

Страница 8: ...e for surface mounting applications If equipped with hydronic heat CCP will only operate as single stage heating unit and not as two stage heating unit Mounting Preparation Choose best location for un...

Страница 9: ...48 1200 Dry 500 19 0 CCP HYDRONIC HEAT SPECIFICATIONS Single stage Heating Only Model EWT F GPM Btuh PD Ft H2 O 12 140 2 14 500 3 4 180 2 22 900 3 4 24 140 4 27 200 5 2 180 4 43 200 5 2 30 140 4 29 8...

Страница 10: ...s manual for more detailes on controls components electrical wiring start up Operation and Cleaning Maintenance HIGH WALL AIR HANDLER WCP Mounting Preparation Mount WCP plumb and level to vertically s...

Страница 11: ...IONS Model Width A Height B Depth C Width D Width E Width F Width G Width H Width I Shipping Wt 12 36 14 10 22 9 24 8 18 16 85 18 47 14 10 32 10 34 8 18 27 115 30 57 14 10 42 10 44 8 27 28 115 WCP DIM...

Страница 12: ...ies Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45 2 3 8 13 270 9 279 45 3 8 0 12 000 8 387 7 189 40 1 0 8 12 481 8 950 40 2 3 9 15 643...

Страница 13: ...e temperature and mode selections have been made they are stored in the microprocessor memory when the unit is switched off Next time unit is switched back on using the On Off switch stored settings a...

Страница 14: ...ture appears Setpoint temperature can be changed with each successive press of Up or Down arrow buttons or by holding button in Place setpoint temperature below room temperature Auto fan mode can only...

Страница 15: ...at low speed while in Dry Mode Optional Electric heat operation Important The dip switch 1 2 must be set to ON For electric heat operation turn unit on via On Off button Select Heat mode via Mode but...

Страница 16: ...chilled water systems coldwater valve opens allowing flow of water Place set point temperature above room temperature CW valve closes while indoor fan remains on for additional sixty seconds Electric...

Страница 17: ...es Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering Air Leaving Air Temperature Split Operating Pressures Compressor S...

Страница 18: ...panels or control covers to expose moving parts of non insulated live electrical components for service disconnect all high volt power supplies to both the indoor unit and outdoor unit Failure to do s...

Страница 19: ...es Refer to low volt interconnect diagram interconnect diagram Figure 1 for unit mounted controls and Figure 2 for remote thermostat connection TROUBLESHOOTING PROCEDURE CONTINUED 24V transformer loca...

Страница 20: ...made according to room and setpoint temperatures Fan will switch to High speed when room temperature deviates by more than two degrees from setpoint Fan will switch to Low speed if deviation is one d...

Страница 21: ...ration or Damages or repairs as a consequence of shipping or handling EMI IS ALSO NOT RESPONSIBLE FOR Damages caused by faulty or interrupted power supply or electrical service Damages caused by acts...

Страница 22: ...22 NOTES...

Страница 23: ...23 NOTES...

Страница 24: ...24 2201 Dwyer Avenue Utica NY 13501 1 800 228 9364 fax 1 800 232 9364...

Отзывы: