![A & T International 1 Скачать руководство пользователя страница 12](http://html2.mh-extra.com/html/a-and-t-international/1/1_service-manual_3066834012.webp)
12
WCP ELECTRICAL SPECIFICATIONS
Model #
Volts/HZ/Phase
Fan
Total
Amps
Min.
Volt
Min.
Ampacity
(1)
Max
Fuse (1)
FLA
HP
12
115/60/1
0.64
0.03
0.64
104
0.8
15
208/230/60/1
0.34
0.02
0.34
197
0.43
15
18
115/60/1
1.2
0.083
1.2
104
1.5
15
208/230/60/1
0.56
0.07
0.56
197
0.7
15
30
115/60/1
1.2
0.083
1.2
104
1.5
15
208/230/60/1
0.56
0.07
0.56
197
0.7
15
(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.
WCP ELECTRIC HEAT OPTIONS
Model
Voltage
KW
Heater
Amps
Total
Amps
Min. Cir.
Amps
Max
Fuse
12
230
3
13.1
13.5
16.8
20
18
230
3
13.1
13.6
17
20
30
230
5
21.7
22.3
27.9
30
WCP CAPACITIES
Model
Nominal
Capacaties
Total
Capacity
Sensible
Capacity
Fluid
Temp.
Fluid
Flow
PD
Ft. H
2
0
12
9,000
7,375
6,732
45
1
0.8
10,801
8,272
45
2
3.8
13,270
9,279
45
3
8.0
12,000
8,387
7,189
40
1
0.8
12,481
8,950
40
2
3.9
15,643
10,304
40
3
8.1
18
15,000
15,624
13,477
45
2
4.4
19,761
15,367
45
3
9.1
18,000
17,724
14,379
40
2
4.5
23,073
16,763
40
3
9.3
30
24,000
20,563
17,564
45
3
2.3
29,031
21,178
45
6
8.3
32,320
22,539
45
9
17.7
30,000
23,600
18,887
40
3
2.4
34,400
23,423
40
6
8.4
38,790
25,351
40
9
17.9
DISCHARGE AIR SPEED AND FLOW
(230V High Speed Fan)
Model CFM Coil FPM Throw/Ft.
12
310
Dry
960
16
18
600
Dry
1412
26
30
750
Dry
1400
25
WCP OBSERVED
SOUND VALUES
(230V High Speed Fan)
Model
DbA
12
48
18
51
30
54
CONNECTIONS
WCP
Model
Chilled
Line Size Drain Size
12
1/2” I.D.
1/2”
I.D.
18
5/8” I.D.
1/2”
I.D.
30
5/8” I.D.
1/2”
I.D.
WCP DIMENSIONS AND SPECIFICATIONS