14
On/Off Switch
On/Off
switch is used to turn equipment on or off. In
off
mode display will be blank and all LED indicator lights will
be dark. To turn unit on press
On/off
button once. Room
temperature will be displayed and amber LED indicators will
show fan speed and mode selections (
Figure 5).
Fan Operation
Indoor unit utilizes two-speed motor with three operational
fan modes. Fan button allows selection of desired fan
setting. Amber LED indicator lights next to fan speed
selection. If
Auto
fan mode is selected then LED indicator
also lights next to Auto.
High
and
Low
are constant fan settings. Fan will operate
continuous regardless of set point or room temperatures.
Auto
mode is cycling fan setting.
Mode Switch
(System Switch)
Mode
button allows for selection of desired mode of
operation. Colored LED indicators light next to selected
mode. With each successive press of
Mode
button,
selection rotates between
Heat, Cool, Fan or Dry
mode. If dipswitches are set for cooling only (off
–
off)
Heat
and
Dry
are not accessible (
Figure 5).
Cooling Only Operation
For cooling operation, turn unit on via On/off button.
Select Cool mode via Mode button. Room temperature
is displayed. By pressing either Up or Down arrow once,
setpoint temperature appears. Setpoint temperature can be
changed with each successive press of Up or Down arrow
buttons or by holding button in. Place setpoint temperature
below room temperature.
Auto
fan mode can only be selected if unit is in
Heat
or
Cool
mode. In
Auto
mode fan cycles with call for Heat
or Cool. Fan speed is determined by microprocessor
and speed adjustment is made according to room and
setpoint temperatures. Fan will switch to
High
speed when
room temperature deviates by more than two degrees
from setpoint. Fan will switch to low speed if deviation is
one degree. When room temperature reaches setpoint
temperature heat/cool call will then be dropped. Fan will
stay on for additional 60 sec. to purge unit of any residual
energy. After fan has been off for ten minutes, fan will
cycle on for 60 seconds. This is done so microprocessor can
sample room air and also help eliminate room temperature
stratification.
When unit is in
Dry
mode fan speed remains constant at
low
speed. While unit is in
Fan
mode,
Auto
is bypassed
and only
High
or
Low
are available (
Figure 5).
UNIT MOUNTED INFRARED COMPATIBLE CONTROL
Figure 5
1
2
3
4
5
6
7
8
9
1. LCD Display
2. Temp. Set Point Down Button
3. Temp. Set Point Up Button
4. Infrared Sensor
5. Power ON/OFF Button
6. Mode Indicator LEDs (HEAT, COOL, FAN, DRY)
7. Mode Selection Button
8. Fan Operation Button
9. Fan Indicator LEDs (HIGH, LOW, AUTO)
START-UP FOR UNIT MOUNTED INFRARED COMPATIBLE CONTROL (ONLY)