When the level is above the problematic part, you can switch back to filling
the tank with portions of 10 liters.
When the tank is full, you should have a tank calibration table that looks like
the following example.
Fig. 41 Tank is full and table is ready
If in your case the level cannot reach the 1023 or 4095 because you cannot fill
the tank completely, don’t worry about that. It is fine if your table ends up looking
like the following one although the range is from 1 to 1023.
33