2VV.

 Creating innovative solutions for you and your business since 1995.

Description

Unit 

behaviour

Likely problem

Solution

44 – Fan 

error

Unit 

out of order

Overheated fan or defect on thermal 

contact of inlet fan

Determine the cause of the overheating (defective 

bearing, short-circuit...) or replace the motor. Check the 

thermal contacts from the motor to the regulator.

45 – Mandatory 

maintenance/filter 

clogged

Unit 

operational

Filter clogged or the time to replace 

it has come

Replace filters. After replacing, do not forget to reset the 

MENU 1616 – FILTER TIMER

46 – Heater 

malfunction

Unit 

out of order

Heater malfunction

Check the heater and the condition of the safety 

thermostat Does the heater have proper cooling?

Check engine running.

47 - malfunction in 

external temperature 

sensor (45,46)

Unit 

out of order

Temperature sensor malfunction on 

terminals 45,46

Check that the sensor is correctly connected to the 

electronics or test it measuring its resistance (the 

resistance value at +20°C is around 10k

W

)

48 – Outlet temperature 

sensor malfunction 

(49,50)

Unit 

out of order

Temperature sensor malfunction on 

terminals 49,50

Check that the sensor is correctly connected to the 

electronics or test it measuring its resistance (the 

resistance value at +20°C is around 10k

W

)

49 – Inlet temperature 

sensor malfunction 

(51,52)

Unit 

out of order

Temperature sensor malfunction on 

terminals 51,52

Check that the sensor is correctly connected to the 

electronics or test it measuring its resistance (the 

resistance value at +20°C is around 10k

W

)

60 – Exchanger’s 

return sensor 

malfunction (53,54)

Unit 

out of order

Temperature sensor malfunction on 

terminals 53,54

Check that the sensor is correctly connected to the 

electronics or test it measuring its resistance (the 

resistance value at +20°C is around 10k

W

)

61 – Room temperature 

sensor malfunction 

(55,56)

Unit 

out of order

Temperature sensor malfunction on 

terminals 55,56

Check that the sensor is correctly connected to the 

electronics or test it measuring its resistance (the 

resistance value at +20°C is around 10k

W

)

62 - malfunction in 

external temperature 

sensor from BMS

Limited 

operation of 

the device

Temperature sensor malfunction in 

BMS

Check that in the BMS that the address where the 

sensors sends the data is properly set 

(on the right regulator) Check the function of the sensor 

in the BMS

63 - malfunction in room 

temperature sensor 

from BMS

Limited 

operation of 

the device

Temperature sensor malfunction in 

BMS

Check that in the BMS that the address where the 

sensors sends the data is properly set 

(on the right regulator) Check the function of the sensor 

in the BMS

79 – Heating reduced 

due to low air flow

Unit 

operational

Only information

The air flow settings were reduced, limiting the heater 

output to prevent overheating

65 – Communication 

error

Unit out of 

order

Communication error

Check the communication cable for damages and if it 

is properly connected Observe the wiring diagram to 

prevent occurrences that may disrupt communication 

(wiring near high tension, phenomena on site causing 

disruptions)

Unit’s not working

Unit 

out of order

Power supply interrupted

Check that the power supply is not interrupted

Cracked fuse

Check the fuse in side the control module

The heating switches 

off automatically

Unit 

operational 

but not 

heating

The heater overheats

The heater overheats due to insufficient air flow. Check 

that the ventilators are in good order and that the air 

supply is not disrupted.

6. MAINTENANCE

6.1 CLEANING

   CAUTION!

• 

Do not use compressed air, chemicals, solvents or water to clean the unit.

• 

Use a soft brush or a vacuum cleaner to clean the suction cover and the inside of the unit.

• 

See the installation manual of the ESSENSSE NEO curtain

7. SERVICE

7.1 IF YOU ARE UNABLE TO REPAIR THE UNIT

If you were unable to solve a problem, contact the supplier or the representative of 2VV. Warranty and post-warranty 

service are provided by the supplier or an authorised service included in the list available at the supplier’s.

Give the following information to the supplier or service:

– type designation of the air curtain

– accessories in use

– place of installation

- serial number

– conditions of the installation (incl. electrical)

– period of operation

– detailed description of the malfunction

7.2 – DECOMMISSIONING THE PRODUCT – LIQUIDATOIN

Before scrapping the product, make it unusable. Old products still have raw materials that can be reused. Take them to 

a collection centre for secondary raw materials. It is preferable to have the product liquidated by a specialist so that the 

recyclable materials may be reused. Take the unusable parts to an appropriate waste disposal site.

The liquidation of materials must observe the applicable waste management regulations.

Содержание FINESSE

Страница 1: ...FINESSE STANDESSE SUPERIOR control Installation instruction EN v 1 20 05 20 ...

Страница 2: ......

Страница 3: ...od order In case of doubt contact the vendor Do not install a damaged unit If you will not unpack the product immediately after de livery store it indoors in a dry place with ambient tem peratures between 5 C and 40 C PACKAGE CONTENTS 5 o C 40 o C All the packaging material is environmentally friendly and can be reused or recycled Contribute actively to the protection of the environment and ensure...

Страница 4: ...ím a musí být objednávány zvlášť vá clona je připojena k řídícímu modulu Rychlých připojovacích konektorů žte řídící modul do vzduchové clony 17 STALACE Vzduchová clona musí být chráněna vhodným jističem v souladu s jeho elektrick Z bezpečnostních důvodů se nedoporučuje předimenzovaná ochrana Vzduchová clona musí bý zapojena pomocí systému TN S což znamená že neut být vždy zapojený Hlavní spínač v...

Страница 5: ...usiness since 1995 1 2 3 4 5 6 CANL 30 CANH 29 12V 27 GND 28 1 INSTALLATION 1 2 CONNECTING THE CONTROL Connection to the regulation control panel and accessories 3 a b c d Connect the remote control and accesso ries to the terminals on the electronic board ...

Страница 6: ... 16 2 3 4 7 12 13 14 8 9 10 PL IT CS Układ mieszający zasilanie Punto di miscelazione alimentazione SMU napájení Sygnał sterujący do nastawienia SMU heater cooler Segnale di controllo impostabile SMU heater cooler Řídící signál nastavitelné SMU heater cooler Czujnik przestrzenny Sensore ambientale Prostorové čidlo teploty GND GND R CE RAL ERROR ttable DX DEFROST settable GND 2 1 V 0 10 VDC CO2 RH ...

Страница 7: ...4 CONTACT EXTERNE ON OFF CONTACT INCENDIE CMSI 62 61 BOOST BOOST 57 58 boitier de commande J1 J2 20 21 22 23 24 7 76 75 74 73 25 26 27 28 29 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 31 33 35 36 37 38 39 40 41 42 43 9 44 45 46 47 48 49 50 30 32 34 72 71 70 69 LO N GND GND 0 10V SSR SSR GND 0 10V 230VAC W PUMP ALARM HEATER RUN OUTPUT COOL HEAT HEAT PUMP HEAT PUMP ERROR DEFROST EXTERNAL ...

Страница 8: ...ASTER SLAVE no 1 The total length of all chained air curtains must not exceed 150 m ELECTRICAL DRAWINGS CHAINING SLAVE no 2 SLAVE no 10 SLAVE SLAVE MASTER A A A A B B B B GND GND GND GND SLA VE no 1 1 no 2 2 no 3 3 no 4 4 no 5 5 SLA VE no 6 6 no 7 7 no 8 8 no 9 9 no 10 A SLAVE A B GND ...

Страница 9: ...break or switching contact CAUTION Not included with the product 2 1 2 DK 1 DK B3 door contact TECHNICAL INFORMATION Isolated switching contact with maximum voltage 12V Cable Two core cable with a cross section of 0 5 mm2 Maximum length 50 m CAUTION Not included with the product 2 1 3 Thermostatic valve TV1 1 TECHNICAL INFORMATION Thermostatic valve to regulate the water exchanger Suitable for all...

Страница 10: ... the following Did you leave inside tools or objects that could damage the unit Is the supply of energy and heating water if applicable adequate Is the unit well closed Is the control module properly connected Does the unit have adequate protection according to the applicable standards CAUTION Interventions or changes to the internal connections are forbidden and shall result in the loss of warran...

Страница 11: ...he control panel so up to 2 control panels may be connected to the MASTER regulator Options CP 1 control panel s address is 1 CP 2 control panel s address is 2 Electric connection Option 1 CP 1 CP 2 CAUTION Each panel must have its own address otherwise it may result in the malfunction of the regulator Terminals must be set if multiple panels are to be connected They are found in the main electron...

Страница 12: ...round 10kW 60 Exchanger s return sensor malfunction 53 54 Unit out of order Temperature sensor malfunction on terminals 53 54 Check that the sensor is correctly connected to the electronics or test it measuring its resistance the resistance value at 20 C is around 10kW 61 Room temperature sensor malfunction 55 56 Unit out of order Temperature sensor malfunction on terminals 55 56 Check that the se...

Страница 13: ...d in the list available at the supplier s Give the following information to the supplier or service type designation of the air curtain accessories in use place of installation serial number conditions of the installation incl electrical period of operation detailed description of the malfunction 7 2 DECOMMISSIONING THE PRODUCT LIQUIDATOIN Before scrapping the product make it unusable Old products...

Страница 14: ... 24 IN 1 IN 2 L L H1 H2 ERR ALARM HEAT L L Fu 57 58 59 60 61 62 31 56 55 54 53 52 51 50 48 49 47 46 45 44 43 42 27 28 29 30 25 26 W PUMP I BUS OUTPUT JTAG JP4 JP3 JP2 JP1 CANL CANH GND 12V B A PWM NOT USED REF OUT NOT USED INLET AIR OUTLET AIR NOT USED RELAY RELAY zdroj 12V N L 1 2 3 Out AC3 v1 SSR 4 1 2 3 SSR 4 1 3 2 NTC 10K CANL CANH GND 12V B A SD SLOT 4 65 66 63 64 GND 12V B A 8 7 6 5 4 3 2 1 ...

Страница 15: ...24 12V ALARM HEAT N ROOM OUT WATER HEAT H2 L H1 MODBUS RTU SLAVE UNIT INLET GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RTU USED MASTER UNIT OUTLET AIR POWER ROOM EXT NOT NTC 10K 2 MODRÁ BÍLÁ 1 6 7 8 2 3 4 5 1 RUDÁ 4 6 8 7 5 3 8 7 6 5 4 3 2 1 3 2 1 NTC 10K Název VCS R4 SU E SL AC Firma 2VV 1 2 3 4 5 6 7 8 9 33 35 37 34 36 38 10 11 39 40 41 42 19 14 13 2...

Страница 16: ...XT RUN USED 0 10V ROOM RELAY RELAY GND 1 2 3 4 5 6 7 8 9 11 10 12 13 14 15 16 17 18 19 20 21 22 23 24 IN 1 IN 2 L L H1 H2 ERR ALARM HEAT L L Fu 57 58 59 60 61 62 31 56 55 54 53 52 51 50 48 49 47 46 45 44 43 42 27 28 29 30 25 26 W PUMP I BUS OUTPUT JTAG JP4 JP3 JP2 JP1 CANL CANH GND 12V B A PWM NOT USED REF OUT NOT USED INLET AIR OUTLET AIR NOT USED RELAY RELAY 1 2 3 Out AC3 v1 4 65 66 63 64 GND 12...

Страница 17: ...9 30 ANALOG HEAT L 19 20 16 17 18 GND GND 25 26 27 28 B A GND 21 22 23 24 12V ALARM HEAT N ROOM OUT WATER HEAT H2 L H1 MODBUS RTU SLAVE UNIT INLET GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RTU USED MASTER UNIT OUTLET AIR POWER ROOM EXT NOT NTC 10K zdroj 12V N L 6 7 8 2 3 4 5 1 8 7 6 5 4 3 2 1 zdroj 24V N L 1 2 3 4 5 6 7 19 9 8 10 25 13 11 12 20 21 22 ...

Страница 18: ...0V ROOM RELAY RELAY GND 1 2 3 4 5 6 7 8 9 11 10 12 13 14 15 16 17 18 19 20 21 22 23 24 IN 1 IN 2 L L H1 H2 ERR ALARM HEAT L L Fu 57 58 59 60 61 62 31 56 55 54 53 52 51 50 48 49 47 46 45 44 43 42 27 28 29 30 25 26 W PUMP I BUS OUTPUT JTAG JP4 JP3 JP2 JP1 CANL CANH GND 12V B A PWM NOT USED REF OUT NOT USED INLET AIR OUTLET AIR NOT USED RELAY RELAY 1 2 3 Out AC3 v1 4 65 66 63 64 GND 12V B A Název VCS...

Страница 19: ...6 27 28 B A GND 21 22 23 24 12V ALARM HEAT N ROOM OUT WATER HEAT H2 L H1 MODBUS RTU SLAVE UNIT INLET GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RTU USED MASTER UNIT OUTLET AIR POWER ROOM EXT NOT NTC 10K NTC 10K zdroj 12V N L 6 7 8 2 3 4 5 1 2 3 1 Název VCS R4 SU S SL AC Firma 2VV 1 4 5 6 7 3 13 15 8 Kreslil Konvalina Datum 27 11 2019 Verze 1 Číslo 2 60...

Страница 20: ...d your business since 1995 9 CONCLUSION 9 CONCLUSION In case of any doubt or query do not hesitate to contact our sales or technical support departments CONTACT Address 2VV s r o Fáblovka 568 533 52 Pardubice Česká republika Internet http www 2vv cz ...

Отзывы: