background image

KWMIOM-3

Installation:

•  Kickster Wall-Mount hydronic fan coils are suitable for 

connection to a hot water supply at any pressure up to 300 

psi with a maximum water temperature of 200°F.

•  Building codes and plumbing regulations may vary.  

Check local codes and regulations before determining 

proper application and installation.

•  Examine unit for shipping damage. 

   13 13

16

351mm

  

   14 5

16

363mm

  

   13 21

32

347mm

  

   13 5

32

334mm

  

  

19

32

15mm

  

  

4 19

32

117mm

  

   3 15

32

88mm

  

WIRING INPUT

INLET

1/2" COPPER TUBING

OUTLET

1/2" COPPER TUBING

CAT-09853-TUR

Figure 1 

- KWM6

•  Unit is designed to be mounted under sheetrock for proper 

fit of the cover. Install at least 6" - 8" above the floor for 

best performance. Unit will fit between standard 16" studs 

on center.

•  For unit dimensions on the KWM6 refer to Figure 1, 3 & 6.  

For KWM11 refer to Figure 2, 4 & 7.

•  Secure unit in proper position. Unit must be level to assure 

proper drainage and operation.

Kickster Wall-Mount Fan Coil

Installation Instructions

Model KWM All Sizes

Summary of Contents for KWM6

Page 1: ... 21 32 347mm 13 5 32 334mm 19 32 15mm 4 19 32 117mm 3 15 32 88mm WIRING INPUT INLET 1 2 COPPER TUBING OUTLET 1 2 COPPER TUBING CAT 09853 TUR Figure 1 KWM6 Unit is designed to be mounted under sheetrock for proper fit of the cover Install at least 6 8 above the floor for best performance Unit will fit between standard 16 studs on center For unit dimensions on the KWM6 refer to Figure 1 3 6 For KWM1...

Page 2: ... NOTE When using mono flo or venturi fittings we suggest placement of a ball valve just after the supply take off and before the return is connected Piping Hot Water Boiler The unit supply line should be taken from the boiler side beyond any flo control valve If the system being used is a gravity flow or cast iron hot water system a separate circuit must be installed Piping Water Heater To install...

Page 3: ... 10 32 X 1 2 SCREW NYLON WASHER INCLUDED KWM6 RECESSED COVER KWM6 UNIT CAT 09853 TUR KWM11 UNIT KWM11 RECESSED COVER 4X 10 32 X 1 2 SCREW AND NYLON WASHER INCLUDED CAT 09853 TUR 4X 10 32 X 1 2 SCREW NYLON WASHER INCLUDED KWM11 RECESSED COVER KWM11 UNIT CAT 09853 TUR Figure 3 KWM6 Figure 4 KWM11 ...

Page 4: ...Z LINE FUSED CIRCUIT ONLY 120V 60Hz LINE WHITE WHITE BLACK GREEN GROUND SCREW YELLOW HEYCO YELLOW GREEN BLACK 2 SPEED SWITCH RED WHITE 2 1 OFF BLACK WHITE AQUASTAT AQUASTAT STANDARD WIRING STANDARD WIRING WITH AQUASTAT DISABLE IMPENDENCE PROTECTED 2 SPEED 2P MOTOR HEAVY DUTY BEARINGS FROM FIELD 120V 60HZ LINE FUSED CIRCUIT ONLY NOTE ALL WIRING SHALL MEET ALL LOCAL AND NATIONAL CODE 15 00 4 06 2 50...

Reviews: