D400-29-00

1

I56-580-04R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

5451 Plug-in Rate-of-Rise 

Thermal Detector with 

Fixed Temperature Alarm

Specifications

Diameter:

4.1 inches (104 mm)

Height:

2.1 inches (53 mm)

Weight:

5 ounces (150 g)

Installation Temperatures:

32° to 100°F (0° to 38°C)

Operating Humidity Range:

10% to 93% Relative Humidity

Latching Alarm:

Reset by momentary power interruption

Sensitivity

135°F (57°C) Fixed or 15°F/min rate-of-rise

Operating Voltage:

15-35 VDC

Standby Current:

100 µA

Before Installing

This detector must be installed in compliance with the con-
trol panel installation manual and meet the requirements of
the authority having jurisdiction. In addition, the National
Fire Protection Association has published codes, standards,
and recommended practices for the installation and use of
detectors, NFPA 72. 

Therefore, the installer must be familiar with these require-
ments, with local codes, and any special requirements of
the authority having jurisdiction.

NOTICE

: This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

This detector must be tested and maintained

regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

General Description

Model 5451 is a rate-of-rise with fixed temperature alarm
thermal detector utilizing a state-of-the-art dual thermistor
sensing circuit. These detectors are designed to provide
open area protection with 50-foot spacing capability, and
are to be used with compatible control panels only.

Two LEDs on each detector light to provide 360° visibility
of the detector indication. Remote LED annunciator capa-
bility is provided as standard, and the RA400Z remote LED
annunciator is available as an optional accessory.

Base Selection and Wiring Guide

Refer to the installation instructions for the plug-in detec-
tor bases for base selection and wiring instructions. System
Sensor has available a variety of detector bases for these
heat detectors, including 2-wire applications with and
without relays and/or current limiting resistors for use with
control panels that require one. This detector is only to be
used with 400 and 400B series bases.

Install the System Sensor  plug-in base to be used with the
detector following the instructions in the base manual.

Summary of Contents for 5451

Page 1: ...this equipment IMPORTANT This detector must be tested and maintained regularly following NFPA 72 requirements The detector should be cleaned at least once a year General Description Model 5451 is a rate of rise with fixed temperature alarm thermal detector utilizing a state of the art dual thermistor sensing circuit These detectors are designed to provide open area protection with 50 foot spacing ...

Page 2: ...per Resistance The detector bases include a feature that when activated prevents removal of the detector without the use of a tool Refer to the installation instruction manual of the detector base to make use of this capability Testing Before testing notify the proper authorities that the heat detector system is undergoing maintenance and therefore the system will temporarily be out of service Dis...

Page 3: ...d be cleaned as described under MAINTENANCE and retested If the detec tors still fail these tests they should be returned for repair Maintenance The 5451 detector has been designed to be as maintenance free as possible Normal air borne dust however can accu mulate on the detector s sensing elements and cause them to become less sensitive All detectors should be tested and cleaned at least once a y...

Page 4: ...OR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alte...

Reviews: