Refrigerated Air Dryer 

Operating Manual for Option 

IDF4E-10-T

IDF11E-10-T 

IDF4E-20-T

IDF11E-20-T 

IDU3E-10-T

IDU6E-10-T 

IDU3E-20-T

IDU6E-20-T

 

This operating manual is for optional specifications.  

For the other parts than the options, refer to the 

standard operation manual. 

1.  Specification 

(1) Run signal, Alarm signal, and terminal block   

2.

 

  About the signal, the Alarm signal, and the terminal block 

        (1) Please remove the Riyapanel fixation screw, and detach Riyapanel. 

             

IDF4E,6E

5 pieces

IDF8E,11E

6 pieces

 

 (2) Please pass the power supply cable through the Grommet 1 with membrane with the film and 

connect it. 

(3) Please pass the signal cable through the Grommet 2 with membrane with the film and connect it. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.    Signal sensing and remote control 

Signal is no-voltage contact, and contact capacity is AC200V.    The minimum current value for 1A is 
AC10mA, and DC30mA.   

For remote controlling, turn on/ off the power supply after turning on the switch with light at the main 
body.  

For remote controlling, start the operation after stopping for 3 minutes or more. 

In addition, frequency of start/ stop shall not be more than 5 times per hour (for preventing motor 

trouble). 

Connections for customer 

Terminal thread size : M3 

Applicable crimped terminal : 1.25-3

(Terminal width: 6.5mm or less)

 

 Riyapanel fixation screw

 