Regulation

EASY CLIMA

USER MANUAL

9120206.03

05/2016

bit.ly/rdzwebsite

1.6

V

ERSION

Summary of Contents for EASY CLIMA

Page 1: ...Regulation EASY CLIMA USER MANUAL 1 6 VERSION ...

Page 2: ......

Page 3: ...ectricalandelectronic equipment in addition to waste disposal The symbol of the crossed out wheely bin as shown on the product indicates that at the end of its useful life it must be disposed of separately from other waste The user must therefore dispose of the above equipment at the end of its useful life at an appropriate centre for the collection of electronic and electro technical waste or ret...

Page 4: ...7 USER SET POINT 8 MAIN VALUES SHOWN ON THE DISPLAY 9 3 TIME BAND MANAGEMENT 10 EVENTS 10 PROFILES 10 PARAMETERS 10 ENABLING 12 PRIORITY 12 BLACK OUT 12 EXAMPLE OF TIME BANDS PROGRAMMING 13 4 EASY CLIMA CONTROLLER 16 DESCRIPTION 16 DESCRIPTION OF KEYS 16 DESCRIPTION OF SYMBOLS AND ICONS 16 DESCRIPTION OF DISPLAY 17 SET POINT MODIFICATION 17 TIME BAND MANAGEMENT 17 5 DIAGNOSTICS 18 ...

Page 5: ...t index will be displayed using the and keys it will be possible to display the alarm codes present at the same time If the fundamental value is also in error mode the Alarm icon will be displayed along with the Err string or Outr DISPLAY KEY Num Description 1 Alarm icon 2 Mode icon 3 Economy icon 4 Clock icon 5 Unit of measurement of the value displayed 6 Menu navigation icon 7 Resources icon 8 V...

Page 6: ... stopped Modulating mixing valve VMIXcompletelyOPEN Pos 100 LED off VMIX completely CLOSED Pos 0 VMIX in OPENING or CLOSURE mode howeverinpositiondifferent to 100 or 0 and in movement 3 point mixing valve VMIX in OPENING mode indicates the opening direction of the servomotor NOT the duration of the impulse towards the actuator VMIX in CLOSING mode indicates the closing direction of the servomotor ...

Page 7: ... increase From the main display the room set adjustment is activated at the current time heating or cooling comfort or economy with flashing set value to be adjusted Long press From main display the operating condition is changed from heating to cooling and vice versa DOWN key Short press Scrolling the folders and parameters display downwards Parameter value decrease if in parameter value modifica...

Page 8: ...ode 4 S_cr Economy temperature set in summer mode 5 S_um Humidity set 2 cf 1 mode Setting the ON or OFF operating mode to control the LT Area and the HT Area The VALUE field means ON or OFF If OFF is set the main display will show OFF 3 time 1 te00 Setting TIME BAND or NORMAL operation The VALUE field means ON or OFF If ON is set the symbol switches on 4 hour 1 ore Display of the operating hours o...

Page 9: ...ew seconds If the room probe is configured but not connected or in short circuit conditions flashing will be shown Outr on the DISPLAY If the humidity sensor IS NOT configured this screenshot will not be displayed 4 mand The flow temperature value will start to flash after a few seconds If the flow probe is configured but not connected or in short circuit conditions flashing will be shown err on t...

Page 10: ... up to a maximum of 4 events for every profile The profile to be associated can be specified for every day of the week The default association will be profile 1 Note as the events available for every profile are HOWEVER 4 to disable an event i e to reduce the number of time bands for a specific profile it will be sufficient to give them the same start point and the same operating mode as the previ...

Page 11: ...file 1 mm 0 59 30 te33 Operating mode from event 4 profile 1 Num 0 2 0 Comfort 1 Economy 2 Stand by 2 PROFILE 2 te38 Event 1 start hours profile 2 hh 0 23 7 te39 Event 1 start minutes profile 2 mm 0 59 30 te40 Operating mode from event 1 profile 2 Num 0 2 0 Comfort 1 Economy 2 Stand by 0 te45 Event 2 start hours profile 2 hh 0 23 13 te46 Event 2 start minutes profile 2 mm 0 59 30 te47 Operating mo...

Page 12: ... from ON Comfort to ON Economy and vice versa The mode change procedure always takes place with the rules times etc envisioned by the basic adjustment The time band management is an exclusive function of the parameters set PRIORITY In the time band management ambit the change events mode has the same priority as the local change mode via keyboard and serial port clearly limited to ON Comfort ON Ec...

Page 13: ...ER N B Dehumidification is only enabled in the summer Its operation is forced in Stand By dehumidifier off in concomitance with the stand by event set In the other cases dehumidification is controlled with the set in the s_um parameter EXAMPLE OF TIME BANDS PROGRAMMING Below find and example of the structure of profile 1 containing 4 events Event 1 start time 06 30 ON Comfort operating mode Event ...

Page 14: ...ontaining 4 events Event 1 start time 06 30 ON Comfort operating mode Event 2 start time 09 30 ON Economy operating mode Event 3 start time 06 30 ON Comfort operating mode Event 4 start time 22 00 Stand By operating mode Below find and example of the structure of profile 3 containing 4 events Event 1 start time 06 30 ON Comfort operating mode Event 2 start time 22 00 Stand By operating mode events...

Page 15: ...15 PROFILE 1 PROFILE 2 PROFILE 3 ...

Page 16: ...ptional device that can be coupled to Easy Clima controller The interface allows you to remote control the information on the Easy Clima controller in the room Fitted with temperature and humidity probe it allows to control the winter temperature the summer temperature and dehumidification DESCRIPTION OF KEYS DESCRIPTION OF SYMBOLS AND ICONS Summary table of the symbols and icons Icon Description ...

Page 17: ...s ON or OFF If OFF is set the main display will show OFF 7 time Setting TIME BAND or NORMAL operation The VALUE field means ON or OFF If ON is set the symbol switches on 8 hour Display of the operating hours of the LT Area Pump the timer is shown on the DISPLAY up to a maximum of 9999 hours 9 orol 1 Hour Hour set 2 Min Minutes set 3 gior Day set 4 Mese Month set 5 Anno Year set 10 all Display of a...

Page 18: ... or with 4 20 mA probe in AIL3 Analogue Er04 Area 1 Room Humidity Probe Error from AIL3 Operating only with humidistat in DIL5 Analogue Er05 Clock fault error Operating without automatism of the time bands reset date time Digital Er06 Exceeding humidity maximum threshold in progress Dehumidifier switch off with Chiller and system HT or LT remaining in operating mode Digital Er07 Automatic stand by...

Page 19: ......

Page 20: ...9120206 03 05 2016 bit ly rdzwebsite ...