Description
The Master Smoke detector with integral voice sounder does not require
any additional products, but may connect to other products in the Cig-
Arrête product range to provide a Master Slave System
The CSA-GDV may be battery powered or may be connected to a power
supply unit, other Slave Detectors in the Cig-Arrête range, and in addition—
a combined sounder beacon unit to warn supervisors of a smoking breach.
Coverage area approx 3m x 3m x 3m **
Multi-Lingual Product
Installation
By default the stand alone module is factory set to DIP switch 2 and 8 in the ON position. (see table below for configuration)
Voice Message No 1 –
“This is a no smoking area. Please extinguish your cigarette. Staff have been contacted.”
Full volume
Adjustable via potentiometer
1 message Play -
(DIP Switch 3 and 4 OFF)
Set for 4 x AA batteries -
The preferred battery size due to longevity of the product (DIP Switch 8 ON)
Battery Operation Instructions
Remove detector head, by rotating anti-clockwise. Remove battery holder from the rear of detector. Insert 4 x good quality AA alka-
line batteries into battery holder - observing polarity and replace holder (or 1 x 9V PP3 battery) . Fix to ceiling using appropriate fixing
screws. Either accept factory default settings or configure as required and refit detector head and lock into position using anti-
tamper screwdriver. Fit anti-vandal cage (part no. CSA-AVC2) if additional protection is considered necessary.
Note: Detector can be locally powered if necessary, using optional plug-in daughter board. (see PIN CSA-DBD)
AFTER POWERING THE SYSTEM PLEASE WAIT UNTIL THE DETECTOR LED HAS STOPPED FLASHING BEFORE TESTING THE SYSTEM
WITH CIGARETTE SMOKE
Cig-Arrête Master Smoke Module with Voice Alarm (Part No CSA-GDV)
Fault Indication
Low Battery
0.5 (S) blip, once every 150 seconds - high tone
Head Removal
0.5 (S) blip, once every 150 seconds - low tone
Specification
Temperature -10
to
+50
C
Humidity
0 – 95% non condensing
Operating Voltage
4 to 12V dc
Operating Current
60µA standby, 100mA during alarm
@6V dc
Battery Life based on quality DURACELL alkaline batteries
.
Note:
The life of the battery is dependant on the number of message plays. In areas
where smoking occurs frequently then utilise the D Cell battery box (Part No
CSA—EBB) or purchase a plug in power supply e.g. (Part No CSA—246)
Detector Sensitivity Adjustment
High Sensitivity
= SW1 OFF + SW2 OFF + SW3 OFF
Medium High Sensitivity
= SW1 ON + SW2 OFF + SW3 OFF
Normal Sensitivity
= SW1 OFF + SW2 ON + SW3 OFF
Low Sensitivity
= SW1 ON + SW2 ON + SW3 ON
1 2 3 4 5 6 7 8
Infra Red Remote
Enabled
ON
Disabled
OFF
Sound Output
Alert Tone
OFF
Speech
ON
Message Repeats
1
OFF OFF
(or tone)
3
OFF
ON
5
ON
OFF
Silent
(no tone or speech)
Relay On 20 Secs
ON
ON
Message Select
1
OFF OFF OFF
2
OFF OFF
ON
3
OFF
ON
OFF
4
OFF
ON
ON
5
ON
OFF OFF
6
ON
OFF
ON
7
ON
ON
OFF
Battery Monitor
9V Battery
OFF
6V Battery
ON
DIL SWITCH SETTINGS
Duracell
AA 6V
PP3 9V
D 6V
Capacity
2.85 A/hr
0.58 A/hr
15.00 A/hr
Standby Time
5 Years
1 Year
10 Years
Max No of Plays (10 secs)
10,000
2,000
50,000