background image

Installation Manual             

 

Last revised: January 2011

         

The technical specifications are subject to change without notice

 

page 1

 

 
Installation manual for PerfectEnergy Solar Modules

 

 

Content 

1.

 

Preface 

2.

 

Technical data/General 

3.

 

Safety instructions 

4.

 

Mechanical Installation 

5.

 

Electrical installation 

6.

 

Grounding 

7.

 

Maintenance 

 

1.

 

Preface 

The solar modules use the photovoltaic principle to turn light into electricity. 
PerfectEnergy solar modules are primarily designed for connection to an inverter to feed the energy into 
the public power grid.  
When connecting to an inverter, please observe the instructions of the inverter-manufacturer. 
When connecting to a charge controller, please observe the instructions of the manufacturer of the charge 
controller and accumulator. 

These instructions contain information about safe handling and about the installation of framed solar 
modules by Perfectenergy in outdoor open spaces (fields) or on flat or tilted roofs. They are only for 
specialists, who are familiar with the installation due to their vocational qualification, and they contain 
safety-relevant instructions for the assembly, connection and maintenance of the solar modules.  
 

Important Notice:

 The installation of the solar modules and especially the electrical installation may only be 

carried out by personnel with electro-technical qualifications. Appropriately qualified technicians must 
always be deployed to service the units or remedy faults during operation. 

 
The installation techniques, handling and use of this product are beyond company control. For this reason, 
Perfectenergy accepts no liability for damage arising through improper use or incorrect installation, 
operation, use and maintenance. 

Please read these instructions carefully before handling the solar modules and familiarize yourself with the 
safety information. After the modules have been installed, hand over these instructions to the operator of 
the PV-system for safe-keeping. 

 

Summary of Contents for PEM-160/X-72M

Page 1: ...les by Perfectenergy in outdoor open spaces fields or on flat or tilted roofs They are only for specialists who are familiar with the installation due to their vocational qualification and they contain safety relevant instructions for the assembly connection and maintenance of the solar modules Important Notice The installation of the solar modules and especially the electrical installation may on...

Page 2: ...e more current and or voltage than reported at standard test conditions Sunny cool weather and reflection from snow or water can increase current and power output Accordingly the values of Isc and Voc marked on this module should be multiplied by a factor of 1 25 when determining component voltage ratings conductor current ratings fuse sizes and size of controls connected to the PV output Our prod...

Page 3: ...glass is broken or the backsheet is torn contact with any module surface or module frame can cause electric shock Cover all modules in the PV array with an opaque cloth or material before making or breaking electrical connections Electrical commissioning of the solar modules may only be carried out by a professional installer Do not connect or disconnect modules when current from the modules or an...

Page 4: ...ast 500m from the sea and sulfur sulfur sources volcanoes The modules may not be exposed to extremely corrosive chemicals e g emissions from manufacturing plants When installed on a roof the module shall be mounted over a fire resistant roof covering rated for the application 4 2Instructions for mounting Assembly work may only be performed by trained and qualified personnel Fasten modules firmly t...

Page 5: ...gn strength of 5400 Pa corresponds approximately to a wind speed of 500 Km h 300 mph PEM 160 X 72M PEM 180 X 72M SCC Screw attachment Secure the module to the structure using the factory mounting holes Four M8 stainless steel bolts with nuts washers and lock washers are recommended per module Refer to the drawing on the right for the module dimensions and mounting hole locations Clamps admissible ...

Page 6: ...resistant cable ties to avoid the pin and socket connections being at a water settlement level The junction boxes are equipped with 3 bypass diodes In the event of clouding these minimize the losses and help to prevent damage to the solar modules When connecting the solar modules to an inverter please observe the information provided by the manufacturer of the inverter 6 Grounding The company inst...

Page 7: ...ng materials such as scouring powder steel wool scrapers blades or other sharp instruments to clean the glass surface of the module Use of such materials will invalidate the product warranty The PV system should be inspected once a year with regard to the following Secure hold and no rust on any of the attachments Secure connection cleanliness and that all cable connections are free of corrosion S...