background image

Model 803 SEA Deluxe

-1-

Installation &

Maintenance Manual

M 803 E

NOTICE!

Thermostatic Water Controllers will not work satisfactorily if improperly installed. 

Read these instructions carefully before installing and follow directions as outlined. 

Checking Cold Water Shut-Off

Turn on full hot and cold water supply to the valve 

and let it run for one minute. Then shut off the hot 

water stop and check valve only. Cold water should 

flow through the controller momentarily then be re-

duced to a negligible amount. 
Failure to do so indicates that:

a. Plunger is sticking and requires cleaning or 

replacement. 

at the outlet temperature stamped on the label. 

Standard setting is 110°F. If the outlet temperature 

is different than that shown on the label, readjust 

valve according to “TEMPERATURE ADJUST-

MENT” procedure on page 2.

2.  If after adjusting the outlet temperature the wa- 

ter stays below the set temperature, see “CHECK-

ING  COLD WATER SHUT-OFF.” If the tem-

perature  stays above the set temperature, see 

“CHECKING HOT WATER SHUT-OFF.”

Caution:

 When maintaining and adjusting the 

mixing  valve,  all  fixtures  should  be  isolated  from 

use. Lawler Manufacturing Co., Inc. recommends 

that you work safely at all times and in a manner 

consistent with the OSHA Lock/Tagout standard,  

29 CFR 1910.147 and other applicable standards. 

WARNING: Opening of the actuator may result in 

electrical shock.

General Description

The Model 803 water temperature controller is care-

fully assembled and tested at the factory to mix hot 

and cold water to any desired temperature within 

range. The temperature of the hot water should be 

at least 20°F higher than the maximum valve setting. 

The major safety features are:
1.  Failure of cold water supply causes the hot water 

ports to reduce hot water flow.

2.  Failure of hot water supply causes the cold water 

ports to reduce cold water flow.

3.  Failure of the thermostat allows both ports to 

reduce flow of hot and cold water.

At each inlet of the controller is a union end stop and 

check valve with removable strainer. Stop and check 

valves are to prevent water from bypassing between 

hot and cold water supply lines. These valves should 

be fully open when in operation.

Maximum Inlet Conditions

Pressure: 125 psi

Temperature: 200°F

Maintenance

The controller should be checked periodically and, 

if needed, cleaned as outlined in “INSPECTING and 

CLEANING VALVE.” To test for proper setting and 

operation - proceed as follows:
1.  Turn on full hot and cold water supply to the 

valve. The mixing valve should deliver water 

5330 East 25

th

 Street

Indianapolis, Indiana 46218

Phone (317) 261-1212

Fax (317) 261-1208

       ASSE 1017 Approved

C

®

U P C

Certified to  

CSA B125.3

CAPACITIES – MODEL 803

Pressure Drop PSI

5

10

20

30

45

60

80

Valve Number

Capacity

803-GPM 

43

60

85 103 125 144 165

803-LPM

163  227 322 390 473 545 624

www.temperedwater.com

Reviews: