2958 Operational Description (NFPA-101)

The 2958 operation complies with the following building and fire codes:  NFPA 101; NFPA 1-UFC; UBC; IBC; IFC; 

SBC; California Building Code.  Listings: UL Listed: Special Locking Arrangements and Auxiliary Locks; California 

State Fire Marshal (CSFM) Listed.

The door is normally closed & secured and/or latched.  The model 2958 secures the door in the locked condition, 

and the display shows the preset delay time.  

Activation of the 2958 is made by releasing the door latch and applying up to 15 lbs. of pressure to the door, 

giving a pre-activation warning tone.  (A 1 or 2 second nuisance delay will prevent false activation of the alarm). 

When the nuisance delay time has been exceeded, the 2958 begins the irreversible door release cycle.  At this 

time the display continues to count down, the verbal warning continues and an alarm output is provided to alert 

personnel of an unauthorized exit.

The integral digital countdown display and voice commands inform the person intending to exit of the seconds 

remaining to unlock. The 2958 will release the door after the 15 or 30 second delay cycle has expired, allowing 

free egress.  A steady warning tone with the voice command “Exit Now” will sound until the MagLock is reset by 

authorized personnel. 

2958 Operational Description (BOCA/Chicago)

The 2958 operation complies with BOCA National Building Code and the Chicago Building Code:  UL Listed, 

Special Locking Arrangements and Auxiliary Locks.

The releasing operation of the 2958 is the same as described above, with the exception that the door relocks 

automatically 30 seconds after closure.  Each time the door is open before 30 seconds has elapsed the relock 

timer resets and relocks the door in 30 seconds.

INSTALLATION INSTRUCTIONS

 

DELAYED EGRESS MAGLOCK

2958 / 2958T

 PUSH UNTIL ALARM

SOUNDS. DOOR CAN BE

OPENED IN 15 SECONDS.

Application

When unauthorized egress is initiated, the 2958 delays egress through the door for 15 or 30 seconds.  

Meanwhile, the person exiting must wait while personnel or security respond. An integral digital countdown 

display and voice commands inform the person intending to exit of the  seconds remaining to unlock. The door 

unlocks after 15 or 30 seconds have elapsed, permitting egress.  A signal from the fire/life safety system will 

release the lock for uninhibited egress in an emergency.

Applications include:

· 

Restricting the egress of patients for their own safety.

· 

Restricting the egress of commercial center patrons for security application needs.

· 

Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs

California Building 

Code Compliant

KEEP PUSHING. THIS DOOR 

WILL OPEN IN 15 SECONDS. 

ALARM WILL SOUND.

2958 Delayed Egress MagLock

Installation Instructions

S-EA00051

3/28/12

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 ● (800) 325-9995

1

Summary of Contents for 2958 Delayed Egress MagLock

Page 1: ...peration complies with BOCA National Building Code and the Chicago Building Code UL Listed Special Locking Arrangements and Auxiliary Locks The releasing operation of the 2958 is the same as described above with the exception that the door relocks automatically 30 seconds after closure Each time the door is open before 30 seconds has elapsed the relock timer resets and relocks the door in 30 secon...

Page 2: ...TED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Note Machine screws provided for applications with heavier gauge material Drill 21 and tap for 10 32 screw PLACE AGAINST LOCK JAMB FOR L H DOORS 1 4 DIA GUIDE PIN HOLE 9 16 DEEP PLACE AGAINST LOCK JAMB FOR R H DOORS PLACE AGAINST DOOR Center punch on mark 2958 Delayed Egress MagLock Installat...

Page 3: ...MAKE PROPER ADJUSTMENTS OF THE LOCK S POSITION PRIOR TO MARKING DRILLING AND TAPPING THE FOUR PERMANENT MOUNTING PLATE HOLES 1 2 DIA FOR WIRE First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations FOLD ON DOTED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Not...

Page 4: ...ting screws using a soft hammer to avoid damage to the lock case ARMATURE MOUNTING INSTRUCTIONS Figure 2B HOLLOW METAL DOOR From sexnut side of door drill exactly 1 2 hole through one metal thickness only From armature side of door drill 5 8 hole to insert reinforcement tube Press in sexnut reinforcement tube all the way and mount armature to door using hardware provided per Figure 2B Figure 2A SO...

Page 5: ...TECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 3 or 5 conductors 8 or 10 conductors Power Supply To Fire Panel AC Mains 2 conductors PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Key Switch or Access Control Optional To Smoke Detection System 2 conductors Digital Keypad 2958 Delayed Egress MagLock Installation Instructions S EA00051 2900 Series Power Supply Key Switch Reset Station Remote Speaker...

Page 6: ...rs Model 2958T REMOVE J6 ONLY IF A FIRE PANEL OR SMOKE DETECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 SLAVE To Smoke Detection System 2 conductors TB2 TB1 LOCK IN PWR TB5 TB6 TB4 TB3 DPS BAS TB7 NO C NC NO C NC NO C NC NO C Z4 D1 Z1 D2 R7 RLY1 J1 R9 C4 BAS DPS C1 J4 TB8 ATS TRIG OUT C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NO C NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK FP PWR J6 J7...

Page 7: ... 2 Whenever the IBO input is closed and held the 2958 will instantly relock and rearm Egress is possible as the normal 15 30 sec delayed unlock 3 Releasing the IBO input will return the 2958 to the Bypass mode 4 Releasing the REX input will rearm the system 5 Upon power up you must manually reset the lock to activate the IBO input System Operation OPTIONAL RED GRN BLK WHT BLK BLU RED L3 OPTI ON C ...

Page 8: ... GRN RLY RED RLY RM TRIG RESET REX 12 VDC OR 24 VDC TO CLOSED FIRE SMOKE DETECTOR CONTACT SLAVE TANDEM LOCK POWER TERMINALS LOCK SECURE OUTPUT ALARM OUTPUT EXTERNAL TRIGGER SWITCH INPUT EXTERNAL RESET SWITCH INPUT REQUEST TO EXIT INPUT IBO INSTANT BYPASS OVERRIDE INPUT N O COM JUMPER J6 SEE PG 9 C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NOC NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK ...

Page 9: ...ype is selectable to MSG1 or MSG2 MSG1 Female Voice Exit in 12 seconds facility staff has been notified Exit in 5 seconds exit now MSG2 Male Voice Exit in 12 seconds security has been alerted Exit in 5 seconds exit now Both messages repeat Exit now until the lock is reset WARNING CONTACT AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO SELECTING DELAY TIME OR PWR UP SETTINGS OFF MESSAGE TYPE VO...

Page 10: ...se the door and apply power to the lock The digital display will show a two bars indicating that the lock is in the Manual Power Up mode Push on the door to verify that the door is unlocked Reset the lock at this time by turning the built in key switch clockwise or by triggering the remote reset input The lock should now secure the door and the LED display will show the delay time You may change t...

Page 11: ...ptional Alarm Output Lock Status Relay Output Door Secure Door Unlocked Specifications Interior Applications Only Input Voltage Requirements Dual Voltage Auto Sensing 12 24 VDC 10 Use with a UL 294 Standard Power Supply Power Consumption Standard Model 1650 lbs 2958 820 500 mA 12 24 VDC 2958T 1500 850 mA 12 24 VDC Energy Saver 1200 lbs E Option 2958 452 274 mA 12 24 VDC 2958T 660 686 mA 12 24 VDC ...

Page 12: ...CONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Systems Applications Reference Activation by a remote trigger for doors with or without latching hardware Activation by applying pressure to doors with latching hardware 2958 Delayed Egress MagLock ...

Reviews: