background image

RT-3000 SeRieS

NEMA 4X TYPE 4X ENCLOSURE WATERTIGHT 

CORROSION RESISTANT DUCT SMOKE DETECTORS

RT-3000-N

Ionization Type, 4-Wire Duct Smoke Detector  

RT-3000-P

Photoelectric Type, 4-Wire Duct Smoke Detector

iNSTALLATiON AND MAiNTeNANCe

 iNSTRUCTiONS  

NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product, 

and is subject to change without notice.  Future references should always be made to the most current revision of this document.  The 
information contained in all this document should be considered before installing or using the product. Any example applications shown 
are subject to the most current enforced local/national codes, standards, approvals, certifications, and/or the authority having jurisdic-
tion.  All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment, should be consulted 
prior  to  any  implementation.  For  further  information  or  assistance  concerning  this  product,  contact Air  Products  and  Controls  Inc.   

Air Products and Controls Inc. reserves the right to change any and all documentation without notice.

© Air Products and Controls Inc. 2009

A  COPY  OF THESE  INSTRUCTIONS SHOULD  BE LEFT WITH THE  EQUIPMENT  UNTIL 

INSTALLATION BY ALL TRADES IS FULLY COMPLETE. FOLLOWING FINAL INSPECTION,  

A COPY SHOULD BE LEFT WITH THE OWNER/USER.

FOR TECHNICAL SUPPORT CALL TOLL FREE 888-332-2241 OR 248-332-3900 

Summary of Contents for RT-3000-N

Page 1: ...t Any example applications shown are subject to the most current enforced local national codes standards approvals certifications and or the authority having jurisdic tion All of these resources as well as the specific manufacturer of any shown or mentioned related equipment should be consulted prior to any implementation For further information or assistance concerning this product contact Air Pr...

Page 2: ...d into the HVAC duct Air flowing through the duct is forced into the air intake inlet tube via the air intake holes facing the airflow and passes over the detector head The air will be drawn out via the exhaust tube back into the HVAC duct A 7 exhaust tube is provided in the installation kit When the concentration of smoke particles suspended in the air stream reach the alarm threshold of the dete...

Page 3: ...be into place against the spring loaded retainer and turn to the correct position allowing the key to Mechanical Installation lock the tube in the desired orientation For front side installation simply rotate the tube retainer so that the tube may be inserted and oriented properly Once the tube is installed rotate the retainer back into place to lock down the tube Ensure air intake sampling tube i...

Page 4: ...VER REMOVAL and the unit will be energized The green pilot LED will be illuminated and when pressing the test reset button TEST RESET the red alarm LED will be illuminated This test confirms the correct basic operation of the duct smoke unit excluding the detector head see functional testing Shut down WIRING Example In alarm NC and COM will open interrupting voltage supply to fan NC COM NO ALARM 1...

Page 5: ...nly no tools single point cover assembly when the unit cover is on and the latch is in closed position the RT 3000 is secure and weathertight Patented Maintenance Mode offers 3 minute interval for test and maintenance functions with no extra trouble reports to the system automatically shuts off when cover latch engages Patented tether holds cover to unit and allows hands free reference to wiring d...

Page 6: ...ACU Alarm COM NO COM NO COM NO COM NO facu alarm trouble NO com nc com NO C NC C form A Alarm form b trouble 30vdc 1 0a 30vdc 7 0a SAMPLE CONTROL unit WIRING STYLE d CLASS A IDC Supervised A fault condition will not inhibit an alarm response Trouble contacts are shown in energized condition Under normal operation contacts will be held as shown msr remote accessory wiring ms remote accessory wiring...

Page 7: ...interconnect al1 al2 t r s h common alarm link common link reference common test reset in alarm out alarm out common alarm horn strobe options The following diagrams show interconnection of the RT 3000 Series to other duct smoke detectors manufactured by Air Products and Controls specifically the SL 2000 Series the HS 100 Special Application Series and the SM 501 Series Up to 30 Air Products units...

Page 8: ...afe to perform test maintenance functions without extra reports to the system Determine Correct Operation ofthe Head MagnetTest 1 Place the square short sided end of the magnet provided with the installation kit on the grey section of the housing inline with the area designated Test Magnet Allow at least five seconds for alarm initiation 2 Upon alarm initiation both the detector head LED and redAL...

Page 9: ...combination Strobe Visual and Sounder Audible MSR 50SA X C Module Clear Lens with color Double Gang Cover Plate MSR 50SA X O Module Opaque Lens with color Double Gang Cover Plate MS and SHP SERIES REMOTE ACCESSORIES MS RA Remote Alarm MS RA R Remote Alarm push button Test Reset Switch MS RA P R Remote Alarm Pilot push button Test Reset Switch MS KA R Remote Alarm key operated Test Switch MS KA P R...

Reviews: