background image

FILLING THE HOT WATER AND HEATING CIRCUITS

IMPORTANT 
It is essential that the water tank is under pressure
before the heating circuit is filled.

1.

Fill the hot water circuit and pressurise it.

2.

Fill the heating circuit - do not exceed a pressure of 2 bar.

3.

Vent the air in the top of the boiler.

4.

Once you have vented the system, return the pressure to static
pressure plus 0.5 bar.

Height of the heating system:
• 10 m 

heating circuit pressure = 1.5 bar

• 15 m 

heating circuit pressure = 2 bar

USING THE BOILER FOR THE FIRST TIME

1.

Check the gas supply connection and ensure that it is free from
leaks.

2.

Check the electrical connection to the boiler and the boiler room
ventilation, and ensure that the flue gas discharge pipes and the
burner chamber plate are properly gas tight.

3.

Set the boiler thermostat or potentiometer to between 60 and
90°C.

4.

Move the Summer/Winter switch to the required position.

5.

Move the main switch to “ON”.

6.

Carry out the necessary venting operations, measurements and
settings.

RECOMMENDATION

ACV recommends that you have the boiler serviced at least once a
year. Boiler servicing and checking must be carried out by a qualified
engineer.

BOILER MAINTENANCE 

(refer to Figs. 1 and 2 on Page 4)

1.

Isolate the boiler from the electrical supply at the
switch on the external control box, and close the gas supply valve.

2.

Move the main switch on the control panel to “OFF”.

3.

Remove the boiler cover (2) and dismantle the upper section of
the chimney reducer (3).

4.

Remove the baffles (24) from the flue ways (23) and clean them.
Replace these items if worn.

5.

Remove the burner cover and burner.

6.

Brush the flue ways (23).

7.

Clean the combustion chamber (20) and the burner.

8.

Check the condition of the seal on the burner chamber plate.

MAINTENANCE OF SAFETY EQUIPMENT

- Check that all thermostats and safety devices operate correctly:

boiler thermostat/potentiometer, thermal reset high limit thermostat
and manual reset high limit thermostat.

- Check the safety valves in both the heating circuit and the

hot water circuit.

DRAINING THE BOILER

The water draining from the drain cock is very
hot and can cause serious burns. Keep all
persons away from running hot water.

Draining the heating circuit 

(refer to Fig. 8 on Page 8)

1.

Move the main switch on the control panel to “OFF”, isolate the
boiler from the electrical supply at the switch on the external
control box and close the gas supply valve.

2.

Close the isolating valves (8) in the heating circuit.

3.

Connect a flexible tube to the drain cock (9).

4.

Open the drain cock (9) to drain the heating circuit.

Draining the hot water circuit 

(refer to Fig. 9 on Page 8)

1.

Move the main switch on the control panel to “OFF”, isolate the
boiler from the electrical supply at the switch on the external
control box and close the gas supply valve.

2.

Release the pressure in the heating circuit until the pressure
gauge reads zero.

3.

Close the tap (7) and the isolating valve (11).

4.

Open the drain cock (9) and air vent (10) (first 9 then 10).

5.

Allow the hot water circuit to discharge to the drain.

The drain cock (9) must be at ground level for the
circuit to drain fully.

MAINTENANCE

20

COMMISSIONING

Summary of Contents for Delta

Page 1: ...mney reducer 3 4 Remove the baffles 24 from the flue ways 23 and clean them Replace these items if worn 5 Remove the burner cover and burner 6 Brush the flue ways 23 7 Clean the combustion chamber 20 and the burner 8 Check the condition of the seal on the burner chamber plate MAINTENANCE OF SAFETY EQUIPMENT Check that all thermostats and safety devices operate correctly boiler thermostat potentiom...

Page 2: ... restart the burner if it has shut down 6 Burner indicator lamp This lamp tells the user whether the burner has shut down lamp on or not lamp off 7 Controller optional Refer to the instructions supplied with the controller if you have this option Gauge pressure in the heating system Your system must be equipped with a heating safety valve calibrated to 3 bar and fitted with a pressure gauge Ensure...

Page 3: ...ore removing the front panel of the casing 3 Reset the manual reset high limit thermostat on the top of the boiler Wait until the boiler temperature has fallen to below 60 C then refit the front panel of the casing 5 If the problem persists please contact your installer for advice Starting the burner In normal operation the burner starts automatically if the temperature of the boiler is below setp...

Page 4: ...397 21473398 A03 Left hand side panel 21472397 21472398 A04 Right hand side panel 21471397 21471398 A05 Rear panel 21474397 21474398 A06 Large top cover 21475397 21475397 A07 Small top cover 21478397 21478398 A08 Burner cover 21476397 21476397 A09 Control panel 21477342 21477342 A02 A09 A03 A01 A08 A07 A04 A05 A06 ...

Page 5: ...pper turbulator Type A 507F2009 507F2009 507F2009 507F2009 B12 Lower turbulator Type B 507F2010 507F2010 507F2010 507F2010 B13 Chimney reducer 507F3037 507F3042 507F3037 507F3042 Balanced flue adapter Ø 80 125 mm 507F3038 507F3038 B14 Balanced flue adapter Ø 100 150 mm 507F3043 507F3043 B15 Cérablanket insulation 51305000 51305000 51305000 51305000 B16 Master Neo tube Ø 80 L 2 m 537D6137 537D6137 ...

Page 6: ...ies 53402088 53402088 53402088 53402088 Orifice 52 propane 537D4020 537D4020 B37 Orifice 68 propane 537D4037 537D4037 B38 Pressure tapping 53437039 53437039 53437039 53437039 B39 Circular seal flame inspection window 55412000 55412000 55412000 55412000 B40 Fan door seal 55700026 55700026 55700026 55700026 B41 Tube seal Ø 107 x 1 mm 55700028 55700028 55700028 55700028 B42 Ignition electrode seal 55...

Page 7: ...26 SPARE PARTS B01 B03 B04 B02 B05 B07 B08 B06 B09 B11 B12 B10 B13 B15 B16 B14 B17 B19 20 B18 B21 B23 B24 B22 ...

Page 8: ...27 SPARE PARTS B25 B27 B28 B26 B29 B31 B32 B30 B33 B35 B36 B34 B37 B39 B40 B38 B41 B43 B44 B42 B45 B47 B48 B46 ...

Page 9: ...28 SPARE PARTS B49 B51 B52 B50 B53 B55 B54 ...

Page 10: ... T Efficiency Gas pressure SERVICE NOTES Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 ...

Page 11: ...ice date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Na...

Page 12: ...ice date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Na...

Page 13: ...ice date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Name and signature Flue gas T Efficiency Gas pressure Service date CO2 min load CO2 max load Gas Propane Comments Na...

Page 14: ......

Page 15: ... USA TEL 1 856 228 8881 FAX 1 856 228 3584 E MAIL sales triangletube com excellence in hot water www acv world com ARGENTINA TECNOPRACTICA ALFEREZ BOUCHARD 4857 1605 CARAPACHAY BUENOS AIRES TEL 54 11 47 65 33 35 FAX 54 11 47 65 43 07 E MAIL jchas tecnopractica com AUSTRALIA HUNT HEATING PTY LTD 10 GARDEN BOULEVARD 3172 VICTORIA AUSTRALIA TEL 61 3 9558 7077 FAX 61 3 9558 7027 E MAIL enquiries hunth...

Reviews: