REL 356

AN-55A-00

Quick Start Guide For The DNP Orion To ABB REL 356 Relays Using
Modbus

This Quick Start Guide shall enable the user to attach a REL 356 protective relay to the ORION unit
communicating over a 485 physical cable connection.
Required equipment:
A.

 

ORION UNIT (TABLE TOP or RACK MOUNT)

B.

 

ONE ABB REL 356 PROTECTIVE RELAY

C.

 

IBM Compatible PC with Windows 95, or  98 installed.

D.

 

ONE  PONI –M Modbus PONI Card.

E.

 

ONE COMSET UTILITY DISK TO SET THE MODBUS PONI CARD ADDRESS

F.

 

ONE RS 232 to RS 485 PHYSICAL INTERFACE CONVERTER.

G.

 

ONE CABLE ASSEMBLY KIT WHICH CONTAINS:

a.

 

One RS 485 Cable.

b.

 

One Troubleshooting Diskette.

1.

 

It is imperative to realize that the ORION is available in two formats, a 19” rack mount version and a
Table Top version.  Please refer to the appropriate diagrams when using this guide.  Apply power to
the universal power supply according to the markings on the unit as shown in Figure 1 or Figure 1A
as depicted in illustration 1. The unit accepts voltages from 55 to 200  V a.c. or  20 to 280 V  d.c.

 ORION Rack Mount Connector Location

FUSE

SCADA

   PC

DIAG

IED

MODEL # _____

SERIAL # _____

TEST DATE ___

PWR

POS NEG GND

Illustration 3

Illustration 4

Illustration 1

OR

MODEL # _____

SERIAL # _____

TEST DATE

      A   B   Shld

IED

Illustration 2

Illustration 3a

Figure 1 – Orion Rack Mount Connector Diagram

ABB

 

Application Note

Substation Automation and Protection Division

www 

. ElectricalPartManuals 

. com

Summary of Contents for REL 356

Page 1: ...Diskette 1 It is imperative to realize that the ORION is available in two formats a 19 rack mount version and a Table Top version Please refer to the appropriate diagrams when using this guide Apply p...

Page 2: ...st to the ORION SCADA MASTER RS 232 port with a 9 pin D shell connector The cable end should mate with the ORION s male connector The unit is a DTE pinout and a custom cable may have to be developed f...

Page 3: ...hld IED 55 56 57 58 59 60 61 RS 485 AUX COM Isolated Port Shield Bare Wire Relay Pin 55 to Orion Terminal B TX RX Relay Pin 56 to Orion Terminal A TX RX Relay Pin 57 to Orion Terminal Shld Ground Illu...

Page 4: ...tor termination Breakouts of each of the jumper locations are shown in Illustration 1 and Illustration 2 The position of the jumpers in the open or closed positions are highlighted FOR AN ORION TABLE...

Page 5: ...cation through the AUX COM PORT Its location is shown in Figure 2 illustration 6 and Illustration 5 or Illustration 2 depending upon the physical connection type or Figure 2A illustration 5 Connect th...

Page 6: ...uide For The DNP Orion To ABB REL 356 Relays Using Modbus 6 Figure 4 PC Port Menu Selection VI A Comset Figure 5 MODBUS PONI M Configuration Menu Presentation w w w E l e c t r i c a l P a r t M a n u...

Page 7: ...ion RS 485 To Modbus PONI PONI M Port E C NORMAL FAIL PICKUP RECLOSEROUT SYSTEM RESET T I M E INSTANTANEOUS FREQUENCY NEGATIVE SEQUENCE TARGET RESET STATUS T A R G E T S A B C N DPU 2000R Network Part...

Page 8: ...Select the parameters as shown The Port selection however should be modified to match your computer systems hardware configuration After selection of all parameters simultaneously depress the CONTROL...

Page 9: ...select the PROTCONV CONITEL Setup submenu selection until the following screen is displayed The parameters listed in Figure 6 match those in the CONITEL Host After selection of all parameters simultan...

Page 10: ...everal choices is displayed Select the ADD INPUTS selection NovaTech Conitel Modbus Configuration Program PRINTER READY FILE NAME TEST CTL File Setup Memory Map Transfer About 10 37 30 Standard Add In...

Page 11: ...AME TEST CTL File Setup Memory Map Transfer About 10 38 33 Standard Modbus Conitel Input Conitel Data Type AI Point Description Analog Input 1 Conitel Group 1 Conitel Point Start 1 Number of Conitel P...

Page 12: ...US CONITEL OFF ADDR 1 MODBUS OFF 1 TOGGLE CONITEL PORT DISPLAY CURRENTLY OFF 2 TOGGLE MODBUS PORT DISPLAY CURRENTLY OFF M MODEM SETUP and TEST MENU S DISPLAY COMMUNICATION STATISTICS Please enter your...

Page 13: ...menu Step 10 Figure 4 4 The ORION Amber CONFIG LED flashes A The ORION has not been configured Download the saved configuration file from the configuration terminal Step 15 Figure 9 5 Communication d...

Page 14: ...istors are configured in the IED protective relay Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 9 Communications Strings are not visible when the RUN MMI and submenu 1 Toggle DNP 3 0 Port Di...

Page 15: ...Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 Optional Information The RS 232 Cables and RS 485 Cable diagrams are included below for reference ORION RS 232 C CABLE Personal Computer OR ORIO...

Page 16: ...ardType 8 Card MODBUS EMULATION COM 3 DB9 Female DB 9 Male to Phoenix Connector Adapter Assembly 1 TX RX 2 TX RX 7 Common REL 356 PONI END UNIT INSTALL TERMINATION RESISTOR 120 OHMS J 15 Closed A B Sh...

Reviews: