FV541 Rev. T 7/18/2018
Page 10
STEP 6.11 (For Hardwired Only)
Route 10’ power supply cable throught the wall escutcheon, wire
supply tube, and the opening on the back of the metal sensor
cap.
Hand-tighten wire supply tube into the back of the sensor cap.
Slide wall escutcheon along wire supply tube until it is against the
sensor cap.
Connect the power supply cable to the sensor lens via the
RED
connectors by aligning the arrows and pressing together.
Figure 25
STEP 6.12
Align set screw hole in sensor cap with key way in ring insert and
place sensor cap on valve body.
Rotate sensor cap counter clockwise until the set screw is visible
in the sensor cap hole and the sensor is facing forward. Using
the 3/32” allen wrench(provided) rotate the set screw clockwise
to secure the cap.
Figure 26
STEP 1
A courtesy flush can be enabled for the ZTR flushometer where
the valve will automatically flush at a specified interval based on
customer preference. Simply manipulate Dipswitches #2 and #3
located on the Sensor Lens found on the inside of the Sensor Cap
to change the courtesy flush interval.
Figure 27
Courtesy Flush Settings (when necessary)
Courtesy Flush Interval
Dipswitch #2
Dipswitch #3
Disabled (Default Setting)
ON
ON
24 hours
ON
OFF
48 hours
OFF
ON
72 hours
OFF
OFF