11
MENU 6 – Setting insensitivity in three-position regulation
–. .Shortly.press.P.to.select.value.1.–.10.%.
(1 – 10x blinking of LED2)
.and.keep.pressing.push-button.P.to.store..
the.parameter.to.memory.
MENU 7 – Response in case of losing control signal in three-position regulation
–. Shortly.press.P.to.select.value.. ......OPEN..
-.1x.blinking.of.LED2,.
.
.
..or.CLOSE..
-.2x.blinking.of.LED2,.
.
.
..or.STOP..
-.3x.blinking.of.LED2,.
.
and.keep.pressing.push-button.P.to.store.the.parameter.to.memory.
MENU 8 – Way of switching off in end-limit positions in 3P regulation
–. Shortly.press.P.to.select.value..........TORQUE..
-.1x.blinking.of.LED2,.
.. .
.or..PO..
-.2x.blinking.of.LED2,.
.. .
.or..PZ..
-.3x.blinking.of.LED2,.
.
.
......PO.+.PZ.. -.4x.blinking.of.LED2,
.
And.keep.pressing.push-button.P.to.store.the.parameter.to.memory..
7.3 PROCEDURE OF SETTING PARAMETERS BY PROGRAM DMS2
–. .Before.starting.the.actuator,.it.is.necessary.to.set.some.parameters.of.the.system.by.means.of.program.
DMS2.on.PC.
–. .For. safety. reasons,. the. system. is. delivered. in. the. state. of. induced. error. of. Calibration. when. the. functions. are.
limited.in.order.to.reduce.the.risk.of.damaging.the.actuator.by.wrong.wiring..In.controlling.the.actuator.from.program.
DMS2,.its.run.is.stopped.when.any.torque.is.induced.
Working torque
–. Check.and,.if.necessary,.set.the.value.of.working.torque.50.–.100.%.in.program.DMS2.
Record of positions OPEN, CLOSED and AUTOCALIBRATION
The.actuator.should.be.adjusted.so.that.the.recorded.position.would.stop.the.actuator.before.it.is.switched.
off.by.torque..The.actuator.is.shifted.manually.or.electrically..The.actuator.in.version.CONTROL.can.be.started.
from.menu.MOTOR.in.program.DMS2..In.this.case,.the.actuator.does.not.respond.to.the.set.position.and.is.
switched.off.by.torque..In.controlling.from.menu.MOTOR,.no.torque.may.be.induced..The.torque.should.be.left.
manually..
Main window of setting program
Selection of electronics