12
Record.of.position.CLOSED:
–. In.the.required.position,.press.push-button.Z.in.the.program.and.confirm.the.approved.record.
Record.of.position.OPEN:
–. In.the.required.position,.press.push-button.O.in.the.program.and.confirm.the.approved.record.
.The.recorded.values.are.confirmed.by.pressing.push-button.START.in.program.DMS2..For.the.actuator.in.
version.CONTROL,.change.over.the.actuator.to.remote.control.and,.by.pressing.push-button.START,.start.the.
autocalibration.. By. short. starting. of. the. motor. in. both. directions,. the. actuator. measures. inertia. and. changes.
over. to. the. regulating. regime.. Information. on. the. course. of. autocalibration. is. signalized. next. to. push-button.
START..The.autocalibration.cannot.be.started.in.case.the.torque.relay.is.switched.off..The.torque.should.be.left.
manually..
Other parameters
Check.and,.if.necessary,.change.other.parameters:.
Control.signal..
.
4.–.20.mA,.20.–.4.mA,.0.–.20.mA,.20.–.0.mA.
Insensitivity..
.
1.–.10.%
Function.in.case.of.error..
.
open,.close,.stop,.to.position.
Time.of.torque.blocking.in.end-limit.positions..
0.–.20.s
Position.of.torque.blocking.in.end-limit.positions..
1.–.10.%.
Output.of.position.signal.
.
4.–.20.mA,.20.–.4.mA.
Function.READY..
.
combined.error
Note:
Signal READY is brought out as contact of the relay on the terminal board. If the state ERROR or WARNING
is not detected (setting can be made of what is to be evaluated as error or warning), the contact is closed; in case
of error, warning, or if feeding of electronics is interrupted, the contact is opened. The state of the relay READY is
indicated by the LED diode on the source board.
7.4 AUTODIAGNOSTICS
DMS2.ED.performs.continuously.its.diagnostics.and,.if.a.problem.is.detected,.it.reports.warning.or.error..The.warning.
or.error.is.signalized.by.LED.of.the.display.and,.possibly,.by.relay.Ready..The.warning.has.no.effect.on.operation.of.the.
system,.the.error.stops.the.actuator.
Assigning.or.switching.off.of.warnings.and.errors.is.set.in.window.“Warning.and.error”.of.the.setting.program.
(it is
opened by clicking one of parameters Warning 1 – 4 or Error 1 – 4 in window “Parameters”).
The.error.or.warning.are.reported.by.opening.the.relay.READY.and.by.blinking.of.the.red.LED.diode.on.the.control.
unit..Particular.error.is.specified.by.program.DMS2.or.on.the.display.
7.5 RESTORING PARAMETERS FROM BACKUP
With.the.feeding.switched.off,.press.push-buttons.O.and.C.at.the.same.time..Then,.switch.on.feeding.and.wait.until.
red.and.yellow.LED.diodes.light.on..The.backup.parameters.are.read.