background image

 

 

 

Electrical Connection and Power-up 

 

   

  

 DANGER

 

DANGER 

indicates an imminently hazardous situation 

which, if not avoided, will result in death or serious injury. 

 

Note: This operation must be performed by a 
qualified technician or electrician in accordance with 
your local electrical safety code.  

 

Installation Option 1: Connect via supplied input plugs 

1.

 

Have appropriate power whips or busway tap boxes with 

receptacles that match your Z-PDS model deployed and 

tested.  

2.

 

Ensure all Z-

PDS breakers are all in the “off” or “0” position 

during installation. 

3.

 

Consider de-energizing the power input sources for both A 

and B, if possible.  Follow all applicable safety regulations. 

4.

 

Connect the input power to the Z-PDS using the supplied 

input cord plugs.  

5.

 

Safely energize the input power whips or busway tap boxes 

for the Z-PDS A & B inputs.  

6.

 

Toggle “1 / ON” 

for all circuit breakers to ensure all the LEDs 

are illuminated. If any malfunctions occur at this point 

please reference the troubleshooting section of this guide. 

Summary of Contents for Z-PDS Series

Page 1: ...Version 2 3 October 2019 Zonit Power Distribution System Z PDS User Guide ...

Page 2: ...Version 2 3 October 2019 Table of Contents ...

Page 3: ...al Connection Power Up 8 Option 1 Connect via supplied plugs 8 Option 2 Connect via hard wire module 9 Electrical Connection of Output Loads 10 Operation 10 Output Circuit Configurations 11 Line to Neutral Voltage 11 Line to Line Voltage 11 Three Phase Wye 11 Three Phase Delta 11 Controls 12 Maintenance 13 Troubleshooting 13 Warranty 14 Waste Electrical Electronic Equipment WEEE 16 ...

Page 4: ... phases to eliminate manual balancing of the per phase power loads on UPS units and generators It also has individual circuit breaker protection for each hot phase of each output to minimize the impact of any fault While plug strips are typically attached to the outputs of the Z PDS it is possible to connect either plug strips or IT equipment directly All output connections are made via standard p...

Page 5: ...g The symbols below are used to highlight danger indications warnings or notices DANGER DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in minor or moderate injury NOTICE NOTICE indicates no immediate physical injury but can include hazards dama...

Page 6: ...ma L21 30P Outputs 6 L21 20R 4 L21 30R 4 L22 30R 6 L22 30R 4 L21 20R 4 L21 20R 3 5 20R Duplex Internal Overload Protection 18 Circuit Breakers per phase 12 Circuit Breakers per phase 12 Circuit Breakers per phase 18 Circuit Breakers per phase 12 Circuit Breakers per phase 12 Circuit Breakers per phase Physical Dimensions HxWxD 3 57 x 17 619 x 13 5 Note width across brackets 19 17 Weight 67 Lbs TBD...

Page 7: ...ng ZPDS 208V30A L21 4L21 20 12 208V L21 30P L21 20 ZPDS 208V30A L21 4L21 20 CR 12 208V 120V L21 30P L21 5 20 Duplex 20 ZPDS 208V60A HW 6L21 20 18 208V Hard Wire L21 20 ZPDS 208V60A HW 4L21 30 12 208V Hard Wire L21 30 ZPDS 480V60A HW 6L22 20 18 480V Hard Wire L22 20 ZPDS 480V60A HW 4L22 30 12 480V Hard Wire L22 30 ...

Page 8: ...nction properly in its intended application Shipped Items List 1 1 Z PDS w standard attached A B labeled input 10 ft power cords 2 2 Rack Mount Brackets 3 8 Bracket Mounting Screws 4 2 Input Connectors As Ordered either a or b a 2 Plugs on the A B 10 foot input SJTW cords b 2 Hard Wire Assembly Modules attached to the A B 10 ft input SOOW cords 5 1 User Manual ...

Page 9: ...all parts are fastened installed correctly e g ensure all screws are fastened securely 3 Locate appropriate hardware needed to mount Z PDS unit 4 Mount the Z PDS in its intended location for example the rack via the brackets provided see fig 1 fig 2 Use the appropriate mounting hardware that can safely withstand the load of the apparatus and torque the fasteners to the manufacturer s recommended v...

Page 10: ...h receptacles that match your Z PDS model deployed and tested 2 Ensure all Z PDS breakers are all in the off or 0 position during installation 3 Consider de energizing the power input sources for both A and B if possible Follow all applicable safety regulations 4 Connect the input power to the Z PDS using the supplied input cord plugs 5 Safely energize the input power whips or busway tap boxes for...

Page 11: ...nal block securely 5 Ensure the hot and neutral wires from the site power inputs are appropriately matched to the hot Phase X is Black Phase Y is Red Phase Z is Orange and neutral wires from the Z PDS input cords using the provided terminal block 6 Ensure the ground wire is mounted on the ground lug 7 Securely fasten the input cord strain relief so that it is properly attached to the hard wire con...

Page 12: ...the receptacle being energized illuminate to indicate proper function 6 If any malfunction occurs at this point please reference the troubleshooting section of this guide Operation The Z PDS will distribute power through multiple branch circuits depending on the model ordered The number of branch circuits and the amperage rating for each is pre determined by the model ordered The Z PDS can be conf...

Page 13: ...11 Note Examples are implemented via Zonit plug adapters where needed Output Branch Circuit Configurations ...

Page 14: ...ll vary by model DANGER DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury Connectivity Status LED Indicators Front Panel Leg Designation Front Panel Phase Designation Individual Power Phase Circuit Breakers Rear Panel Phase Input Power Designation Output Receptacles A and B Input Power Rear Panel Leg Input Power Designation ...

Page 15: ...er to the Z PDS If any condition exists that would indicate a problem follow this process 1 Check the source power whip or busway tap box circuit breakers Check that the 3 pole circuit breakers feeding the Z PDS are fully closed Toggle to ensure position and check the LED indicators on the Z PDS to ensure that input power is being delivered 2 Use a suitable voltmeter and test for the following Thi...

Page 16: ... to a Zonit product if a surge or spike reaches the product through an unprotected source connected to it It does not apply to any product which has been repaired or altered in any manner by anyone other than Zonit Structured Solutions LLC or to any product which has been installed connected used or otherwise adjusted other than in accordance with written instructions furnished by Zonit Structured...

Page 17: ...ENTIAL INDIRECT OR OTHER SIMILAR DAMAGES INCLUDING BUT NOT LIMITED TO PERSONAL INJURY PROPERTY DAMAGE DAMAGE TO OR LOSS OF EQUIPMENT LOST PROFITS OR REVENUE COSTS OF RENTING REPLACEMENTS AND OTHER ADDITIONAL EXPENSES ZONIT STRUCTURED SOLUTIONS LLC S LIABILITY SHALL NOT IN ANY EVENT EXCEED THE AMOUNT OF THE PURCHASE PRICE OF THE PRODUCT Some jurisdictions do not allow limitations on how long an imp...

Page 18: ...s product should not be disposed in household waste It should be deposited at an appropriate facility to enable recovery and recycling For information on how to recycle this product please check with the reseller that sold you this product to determine proper waste disposal procedures For assistance contact ...

Page 19: ...17 support zonit com See our website at www zonit com for the latest version of manuals Zonit Structured Solutions LLC 1790 30th Street Suite 140 Boulder Colorado 80301 USA ...

Page 20: ...18 Copyright 2019 Zonit Structured Solutions LLC All Rights Reserved ...