ZONEMASTER MAXIPOINT V2 DAMPER CONTROL SYSTEM
- Installation Manual
14
The factory default is set in spill mode and the
set-point is 30%. When the set point is reached
for spill, the screen shows ‘SPILL CONTROL’
and some of the lower order zones remain open
and will not respond to ON/OFF operation.
Similarly if bypass set point is reached the
screen displays ‘BYPASS CONTROL’ as shown
in the right figure.
a)
At the setting mode in ‘Parameter’ screen,
press or button to select
‘Safety Spill’.
b)
Press button to select Spill or
Bypass mode.
c)
Press or button to change
the spill/bypass set-point to required
value. The adjustable range is from 0%
to 50% with 10% increments.
IMPORTANT: DO NOT set spill/bypass set-point to 0% unless there is
a permanent open zone used as spill zone. Otherwise, there will be
no spill zone when all zones are closed and damage may be caused
by high pressure build up inside ducts if air conditioner is running.
5) Turbo Group
The Turbo function will give the selected group
a full-opening while all the other groups
(dampers) opening positions are reduced by
50% of their balanced value. This will bring a
large volume of extra air into the designated
area and cool or heat the area quicker. Typically
this may be a family-room, dining room or home
theatre (or in commercial application a meeting,
lunch or board room). (See Grouping Zones
section for how to group).