Leaving  Air Sensor 
In Supply Air Duct 

LAS 
LAS 
OAS 
OAS 

Outdoor  Air Sensor   only used with 
Fossil/Dual  Fuel Applications 

 

Outdoor Air Sensor - OAS

 

The  Outdoor  Air  Sensor  is  used  only  when  using  a  Heat 
Pump  with  Dual/Fossil  Fuel  back-up  furnaces.      The  OAS 
senses  the  outdoor air temperature  and  switches  the  heating 
control  between  the  heat  pump  and  the  fossil  fuel  furnace. 
The   temperature  set  point  for   this   is   adjustable   on  the 
Outdoor  Balance  Point  (OBP)  dial  on  the  control  panel.    It  is 
adjustable from 5°F to 53°F.  It is suggested that this be set just 
above  freezing  to  avoid the  heat  pump  from  potentially going 
into Defrost mode. 

    

amount  of  time  the  unit  has  already  been  supplying  the  first 
mode in order to determine how long it will hold off the opposite 
call.   If an opposite call is made shortly after the first call, the 
opposite call may be held off for as much as 20 minutes.   If the 
first call or subsequent calls for the first call mode has had that 
mode operating for up to 20 minutes already and an opposite 
call  comes  in  after  20  minutes,  the  changeover  timer  will 
immediately recognize the opposite call, shutting off the current 
mode,  enter  the  purge  mode  and  automatically  switch  to  the 
opposite mode. 

 

The  longer  a  call  has  been  running  up  to  20  minutes,  the 
shorter the wait time will be for an opposite call.  If a call is over 
20  minutes  and  an  opposite  call  is  made  the  changeover  will 
be  immediate  following  the  purge  time.      This  intelligent 
changeover  timing  makes  the  H32P  unique  to  any  other 
zoning system. 

 

CHECKOUT

 

The  H32P  has  unique  features  that  simplify  the  checkout  of 
the system and has LED readouts that constantly indicate the 
system operation.  Once 24 Volt Power is applied to the panel, 
the Green Power LED will illuminate. This will stay illuminated 
constantly when power is applied. 

 

Stage Timer

 

                

           

The  H32P  has  a  built-in  stage  timer  that  eliminates  the  need 
and added cost of using two stage thermostats.   On a call for 
either heating  or cooling  the timer  begins.   Setting  the  Stage 
Timer  dial  provides  an  adjustable  time  delay  of  4  to  68 
minutes  between  the  first  and  second  stage  calls  and  the 
same between a second stage and third stage call of heating, 
if used. 

 
 
 
 

PURGE TIME

 

The H32P has a built-in Purge Time after each call is satisfied 
and provides a minimum off time before another call is initiated.  
The Purge Time is set at 2 minutes after all calls for a particular 
mode are satisfied or when the Changeover Timer requires a 
changeover due to opposing calls. 

 

After  all  calls  are  satisfied  or  the  changeover  timer  activates, 
the Purge Timer begins and the heating or cooling, whichever 
was  on,  is  deactivated.      Typically  the  fan  may  be  running 
during  this  time  and  the  damper(s)  to  the  last  zone(s)  calling 
will  remain  open  to  purge  the  conditioned  air  only  into  those 
zones that were calling for the conditioning.  DIP Switch 6 can 
be set ON to keep the Fan running during the Purge mode in 
order  to  prevent  the  fan  cycling  off  and  back  on  between 
modes.   In  the instance where the Fan staying  may create a 
draft,  and  the  frequency  of  opposite  calls  is  minimal  this 
switch can be kept to OFF. 

 

Minimum On Timer

 

The  H32P  also  has  a  minimum  on  time  whenever  the 
compressor    operates   in   order    to    prevent    frequent    short 
cycling.  Once there is a call for cooling or the compressor on 
a  heat  pump,  the  H32P  will  hold  that  call  for  a  period  of  2 
minutes. 

CHANGEOVER TIMER

 

Whenever  a  call  is  made  for  either  heating  or  cooling,  the 
changeover  timer  is  activated in  order  to  track  the  amount  of 
time  heating  or cooling  is  on. When an  opposite  call  is  made 
after a first call is existing, the changeover timer calculates the 

 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Zone  Dampers 

–  The  H32P  provides  DC  power  to 

ZONEFIRST

’s  exclusive  Plug-In  Zone  Dampers.      These 

dampers  use  and  are  supplied  with  a  modular  cord  that  is 
complete with RJ11 jacks on each end of a 25

’ cable for each 

zone damper.   Up to 10 dampers can be wired to each zone. 
The  panel  has  a 

GREEN 

LED  to  indicate  when  the  damper 

should be open. 

 

ZONE DAMPER

The System LED will provide several different indications based 
upon color and if it is flashing. 
 

Heat ON - 

RED

 

Second  Stage  Heat  - 

RED  Flashing

,  (1  flash  per 

sec.) 
Heat limit - Intermittent 

RED/AMBER 

Flashing 

Emergency  Heat  -  

RED  Flashing

,  (2  flashes  per 

sec.) 
Cool ON - 

GREEN

 

Second Stage Cool - 

GREEN Flashing

, (1 flash per 

sec.) 
Cool Limit - Intermittent 

GREEN/AMBER 

Flashing 

FAN ON - 

AMBER

 

PURGE - 

AMBER Flashing

 

 

Each  zone  has  its  own  small  Green  indicator  LED  next  to 
each  zone  relay.    This  light  is  lit  when  the  specific  zoning  is 
calling for the mode shown on the System LED. 

 

WIRING

 

The H32P is very simple to wire and requires only a minimum 
number of connections.   The H32P terminal blocks are color 
coded and screw-less for all wires to be easily pushed into their 
respective terminal by de-pressing the button for each point 
and releasing once the wire is seated.   (Solid wire can often 
just be pushed into the terminal without de-pressing the button.) 
To remove the wire, just press its button again and remove the 
wire.

 