background image

©2017 ZONEFIRST® 

 

OPERATION

 

The  H32P  can  be  controlled  by  conventional  single  stage  or 
heat  pump  thermostats.        Each  thermostat  can  then  call  for 
heating, cooling or the fan.  When a thermostat calls the panel 
will  keep  open  the  damper  to  the  calling  zone,  if  not  already 
open,  close  the  dampers  to  the  zone(s)  not  calling  and 
activate  the  appropriate  HVAC  equipment.     When  opposite 
calls exist for both heating and cooling the panel will allow the 
zones  to  automatically switch  between the modes.   When all 
zones are satisfied the panel then looks for individual fan calls 
from any zone and controls the dampers based on these calls 
as  well.     When  all  zone  thermostats  are  not  calling  for 
heating,  cooling  or  the  fan,  all  dampers  will  return  to  a 
normally open position. 

 

Once a call for either heating or cooling is made the panel will 
open   the   damper(s)   to   the   zone(s)   calling,   close   the 
damper(s) to those zones not calling, activate the  appropriate 
controls for  heating  or cooling,  whichever  is  being  called  and 
not accept any calls for the opposite mode. 

 

Any calls for the opposite mode will be locked out until the initial 
mode is either satisfied or a period of time has elapsed that is 
sufficient for the first mode to satisfy, a maximum of 20 minutes.  
A  unique  sequence  determines  the  time  the  unit  has  been 
running  or  needs  to  continue  to  run  in  order  to  adequately 
provide conditioning for each mode.   If a particular mode  has 
already been calling for 20 minutes or longer and an opposite 
call comes in the H32P will immediately drop the mode, enter 
the purge mode in order to dissipate the conditioned air into the 
zones  calling  before  switching  over  to  provide  the  new 
conditioning call to its zones. 

 

When  using  the   H32P  to  control  two-stage  heating,  the 
second  stage  is  controlled  based  upon  time  after  the  first 
stage  call  from  the  thermostat.      When  any  zone  calls  the 
panel

’s  built-in  timer  begins  and  after  the  set  period  of  time 

elapses  the  H32P  will  also  activate  the W 2  for  second  stage 
heating.    The  Second  Stage  Timer  is  adjustable  between  4 
and 68 minutes after the first stage calls. 

 

Once all zone thermostats are satisfied for heating and cooling, 
the  H32P  can  now  accept  Fan  calls  allowing  Continuous  Air 
Circulation(CAC)  in  those  zones  where  the  thermostat

’s  Fan 

Switch is set to ON.   These zone dampers will be Open while 
the dampers to the zones where the Fan Switch is set to AUTO 
will be CLOSED. 

 

When all zone thermostats  are satisfied for both Heating and 
Cooling,  and  all  Fan  switches  are  set  to  AUTO  position,  the 
HVAC  unit  will  be  off  and  all  zone  dampers  will  return  to  a 
normally  open  position.     Once  a  zone  calls  for  heating, 
cooling or fan, the dampers  to the calling zones  remain open 
and the dampers to the zones not calling will close. 

 

Set-Up for Various HVAC Equipment

 

Heat call.  In HP position Y1 makes as the compressor call for 
both heating and cooling. 

HP  Type 

– CONV or FF 

–  This  switch is  used to  determine 

the  equipment  output  when  the  System  switch  is  set  to  HP  , 
this  switch  determines  if  the  output  will  be  for  a  conventional 
heat  pump  with  electric  back-up  heat  or  fossil  (dual)  fuel 
mode. 

FAN  IN  HEAT 

– YES or NO 

– This  switch  will activates  the 

Fan on a call for Heat in the Yes position.   In Off, the heating 
unit must activates the fan when the heat is called. 

FAN PURGE 

– YES or NO – 

This switch determine if the Fan 

is kept on during the Purge Mode, after the end of each heat 
or cool call. 

STAT  RV 

–  O  or  B  – 

When  using  HP  type  thermostats  this 

determines  if  the  O  or  B  terminal  is  wired  to  the  W/OB 
terminal on each thermostat to determine if the call if for Heat 
(B) or Cool (O). 

TSTAT 

– HC-HP 

Switch determines if conventional Heat/Cool 

thermostats  or  Heat  Pump  thermostats  are  being  used  for 
ALL  zones.   A  conventional  HC  stat  would  have  separate W 
and Y output for heating and  cooling calls.   A HP thermostat 
uses Y for both a heat and cool call and the O or B is used to 
determine whether the call is for Cooling (O) or Heating (B). 

EM  HEAT 

– 

This  switch  sets  any  heat  call  to  call  for  the 

Emergency Heat.   The Red  EM HEAT LED  on the panel will 
light only when this switch is ON.   This is used when there is 
no Emer Heat switch on the thermostats. 

TEST 

– 

This  switch  accelerates  the panel timings  in order  to 

provide a quick checkout of all of the functions without having 
to wait the full time for each sequence. 

ZONE STAGING MODE 

– ON OR OFF – 

This switch is used 

to  control  how  the  second  stage  of  heating  &  cooling  is 
determined.    In    the    OFF    position,    the    second    stage    is 
controlled  by  the  stage  timer  setting.  In  the  ON  position,  the 
second  stage  is  brought  on  based  on  the  number  of  zones 
calling. When  2  of  the 3  zones  are  calling,  the  second  stage 
will activate for both heating and cooling. 

 

Leaving Air and Outdoor Air Sensor

 

The  Leaving  Air  Sensor,  Model  ZPS, is  a  remote sensor that 
is  located  in  the  supply  air  duct  to  sense  the  Leaving  Air 
temperature  of  the  HVAC  Unit.      The  ZPS  is  a  high  limit 
protection  for  the  heating  and  a  low  limit  protection  for  the 
cooling.    When  zoning,  the  airflow  through  the  HVAC  Unit  is 
critical.      The  ZPS  protects  the  equipment  in  low  air  flow 
situations  as  well as  when  by-pass  air is  being directed back 
into the return air duct. 

 

The  heating  limit  is  adjustable  from  110 F  to  170 F.      The 
cooling limit is  fixed  at 45 F.    When the  ZPS  senses  heating 
above  its  set  point,  or  cooling  below  its  set  point,  the  H32P 
will drop both all stages of heating or cooling.   The ZPS must 
sense  a  10 F  fall  for  heating  or  rise  for  cooling  before  re- 
activating  the  first  stages  of  heating  or  cooling.    If  two  stage 
heating  or  cooling  is  being  used  the  second  stage  timer  will 
start again once the first stage is re-activated.

 

The  H32P  is  factory  set  for  conventional  heating  and  cooling 
operation.  The panel only needs to be configured when using 
with  an  electric  furnace  or  heat  pumps.  Most  all  of  the  panel 
configuration  is  done  by  setting  the  DIP  switches  in  the  top 
right of the panel.   Other functions come by wiring for specific 

applications.  Below  is  shown  the  most  typical  settings..  

Review each function for your application  

 

 
 

130 

120 

 

110 

 

 

140 

 

 
 

150 

160 

 

170

 

 

 

 

SYSTEM 

–  G/E  OR  HP 

This  switch  sets  the  HVAC  Output 

operation.   In G/E the Y1 makes  as a Cool call and W1 as a 

 

                                                               HIGH LIMIT 
 
 
 

The ZPS and OAS (if used) each require two (2) wires to their 
respective LAS and OAS terminals on the H32P panel.

 

Reviews: