BPE Installation Instructions #BPE20651508 

© 2015 ZONEFIRST 

Turn off the power to the panel for several seconds until the 
LCD goes out, and then turn the power back on to see if the 
panel resets.  In many instances this resolves the problem.   
 
The  first  check  is  for  24VAC  Power  to  the  panel.    When 
there  is  power  the  LCD  will  be  lit.    If  not  check  the 
transformer and the power supply to it.   
 
Zone(s) Not C

Zone(s) Not C

Zone(s) Not C

Zone(s) Not Closing

losing

losing

losing    

If a zone is  not  closing and there is an active HVAC call it 
may  be  that  there  is  an  excessive  amount  of  air  being 
bypassed  into  the  zone.  End  all  HVAC  calls  and  using  the 
damper test button on the Main Controller you can check to 
see if the dampers are properly cycling. 
    
Damper 

Damper 

Damper 

Damper Motor 

Motor 

Motor 

Motor Checkout Procedure

Checkout Procedure

Checkout Procedure

Checkout Procedure    

Satisfy  all  zone  thermostats  HVAC  calls  and  check  that  the 
main  controller  is  no  longer  in  purge.  Each  zone  has  a 
damper  test  button  on  the  main  controller.    When  the  zone 
damper(s) are in the Open position and the damper’s green 
LED  is  illuminated,  press  the  damper  test  button  and  hold  it 
down,  the  dampers  on  this  zone  will  cycle  closed  in  a  few 
seconds and their damper LEDs will go out for a few seconds 
and  then  turn  Red  when  the  dampers  close.    Release  the 
button and the dampers will cycle back open.   
 
If the motor(s) fail to operate from the test button, the panel 
RJ11  connections  can  be tested to determine if  the problem 
is from the panel.    If there is power at the motor plug, the 
problem  may  be  a  broken  wire  or  poor  connection  in  the 
cord or the motor itself.   
 
To  check  the  power  to  the  motor  from  the  damper  plug  on 
the panel, switch your meter to DC Volts.  Note the wires on 
the  plug  and  check  across  either  Positive  and  Negative 
wires.  Note that each plug has two positive leads and two 
negative  leads.    Both  positive  and  both  negative  leads  are 
wired together.  The meter will read either Plus (+) or Minus 
(-) 12VDC depending if the damper is to be Open or Closed 
respectively.  
 
DAMPER CLOSED 

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

-12VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
 
DAMPER OPEN 

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

+12VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
When using multiple dampers on a single zone, please note 
that  up  to  10  dampers  may  be  used  on  a  single  zone.   
Adding  dampers  beyond  the  recommended  number  may 
cause  all  dampers  to  be  slow  to  operate  and  may  not  fully 
cycle  between  open  and  closed  as  well  as  possible  failure 
can occur. 

 

 