background image

BPE Installation Instructions #BPE20651508 

© 2015 ZONEFIRST 

OPERATION

OPERATION

OPERATION

OPERATION    
The BPE controls up to 4 zones on a single HVAC unit and 
up  to  10  dampers  per  zone  on  the  output  terminals.  When 
the  BPE  gets  a  signal  from  the  Zone  Controller  that  a  zone 
damper  is  to  be  powered  open  it  immediately  opens  the 
corresponding  zone  damper(s)  on  the  output  terminals. 
Anytime the BPE’s pressure sensor detects the pressure in the 
supply plenum is higher than the Upper Limit Set Point it will 
modulate  the  closed  zone  dampers  open  to  relieve  the 
excess  pressure  into  those  zones.  As  these  dampers 
modulate open the air pressure should drop below the high 
set-point  and  the  zone  dampers  stop.    When  the  BPE’s 
pressure sensor is below than the Lower Limit Set Point it will 
close the zone dampers.   Once the pressure has equalized 
to  higher  than  the  Lower  Limit  set  point  and  lower  than  the 
Upper Limit set point the BPE will signal the dampers to stay 
in their current position.  
 
IMPORTANT

IMPORTANT

IMPORTANT

IMPORTANT:  When  the  dampers  are  being  modulated  or 
signaled to stop the LEDs on the zone dampers may not be 
illuminated. This is completely normal and the LEDs will only 
illuminate  when  the  damper  is  fully  open  (green)  or  fully 
closed (red). 
 
Upper Limit

Upper Limit

Upper Limit

Upper Limit    
The Upper Limit is adjustable from 0.25”WC to 2”WC.  This 
is  the  limit  that  once  exceeded  all  dampers  in  the  closed 
zones will begin to modulate open. To enter the Upper Limit 
menu  from  the  main  status  display  press  SW1  and  using 
SW1  and  SW2  you  can  raise  or  lower  the  Upper  Limit. 
Once you have finished setting the upper limit the menu will 
automatically exit after 5 seconds back to the main screen. 
    
Lower Limit

Lower Limit

Lower Limit

Lower Limit    
The Lower Limit is adjustable from 0.15”WC to 1.90”WC. 
This  is  the  limit  that  once  the  pressure  drops  below  it  all 
dampers  in  the  closed  off  zones  will  begin  to  modulate 
closed.  To  enter  the  Lower  Limit  menu  from  the  main  status 
display press SW2 and using SW1 and SW2 you can raise 
or lower the Lower Limit. Once you have finished setting the 
lower  limit  the  menu  will  automatically  exit  after  5  seconds 
back to the main screen. 
    
Dead Band 

Dead Band 

Dead Band 

Dead Band     
There  is  a  minimum  0.10”WC  dead  band  between  the 
upper  and  lower  limits  that  insures  there  is  a  sufficient 
pressure  range  that  can  be  maintained  for  the  dampers  to 
modulate properly without constantly opening and closing to 
maintain pressure.   
 
Sensor Calibration

Sensor Calibration

Sensor Calibration

Sensor Calibration    
The  pressure  sensor  is  factory  calibrated  but  due  to  the 
differences  in  elevation  it  may  be  a  good  idea  to  calibrate 
the  pressure  sensor  in  the  location  it  is  installed.  The 

important thing to note is that if the sensor is calibrated with 
the HVAC unit running or in a windy environment it can lead 
to a bad calibration measurement. 
To  calibrate  the  pressure  sensor  press  and  hold  both  SW1 
and  SW2  if  the  unit  does  not  immediately  show  the 
“Calibrating Please Wait” try pressing the upper button first 
then  the  lower  button  while  still  holding  the  top  button.  As 
soon as the calibration message appears release the buttons 
and  calibration  only  takes  approximately  6  seconds  from 
there. 
    
Display

Display

Display

Display    
The  LCD  Display  will  display  the  status  of  the  zones  OP 
(open), CL (closed), or a number from  01 to 99  to indicate 
what percent the zones that were in the closed position were 
modulated  open  in  order  to  relieve  the  excess  air  from  the 
ductwork.  If  a  zone  is  available  for  modulation  that  means 
that the Zone control board is sending a close signal to the 
BPE. In the upper right hand corner the display will read P in 
with the pressure reading being displayed just below it. 
    
Transformer

Transformer

Transformer

Transformer  –  A  24  Volt  AC,  40VA  Transformer  is 
recommended  to  power  the  BPE  and  can  be  the  same 
transformer powering the zone control panel.   
    

 

2

4

V

 T

R

A

N

S

C
R

C
R

T24 -24V 40VA

TRANSFORMER

 

    
    
PRESSURE SENSOR

PRESSURE SENSOR

PRESSURE SENSOR

PRESSURE SENSOR    
The  BPE  pressure  sensor  is  a  very  sensitive  device,  never 
blow  into  the  sensor  with  your  mouth  as  the  amount  of 
pressure  that  the  human  body  can  produce  far  exceeds  the 
limitations of the sensor and it can be damaged that way. If 
there  is  a  need  to  test  the  sensor  simply  fold  the  pressure 
tube  on  itself  and  squeeze  as  this  will  create  a  gentler 
pressure increase on the sensor    
    
TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING    
The  BPE  is  a  very  simple  control  to  troubleshoot,  especially 
with  the  LCD  Display.    The  only  other  device  needed  is  a 
simple Volt/Ohm meter.   
 
Almost all problems can be traced to an external component 
or wiring to the BPE.   While the BPE has been designed to 
operate  under  extreme  voltage  conditions  and  is  fuse 
protected,  like  any  computer  the  micro-processor  can  hang 
up and not operate properly.    