background image

11

© Copyright 2020 Zoeller

®

 Co. All rights reserved.

OPERATION

GENERAL

Zoeller pumps are lubricated and tested at the factory prior to shipment 

and require minimum pre-start-up maintenance.
Maximum operating temperature of pump liquid must not exceed 104 

°F (40 °C).

These units are not designed to handle liquids other than effluent: 160 

and 180 or sanitary sewage: 280, 290 and 400. If pump is used to dewater 

areas with contaminated liquids with heavy or abrasive materials, the 

warranty will be voided.

NAMEPLATE DATA

The nameplate, located on the side of the pump, indicates specific 

information about the construction of the pump. The model number 

and date code information should be recorded on the front page in the 

“Owner’s Information” section of this manual.

SHORT TERM STORAGE

When not in use, the pump should be stored and the following is advised:
•  Store pump inside whenever possible or cover with some type of 

protective covering.

•  Tape or seal in plastic bag the terminal ends of wire leads.

•  Spray coat unpainted surfaces with rust inhibiting oil.

•  The impeller should be rotated every six months in order to keep the 

seals lubricated and not develop a permanent set.

If panel is to be stored, the following is advised:
•  Store the panel inside whenever possible and leave in the shipping 

box.

•  All openings shall be sealed.

•  Store in an upright position.

•  Do not stack anything on top of panel.

START-UP PROCEDURE

Before placing the equipment into operation the following should be 

checked:

•  Clean pit.

•  Electrical boxes dry and securely installed.

•  Floats positioned properly.

•  Discharge valves open.

•  3/16” vent hole drilled in pipe between check valve and pump.
Once the above has been verified proceed with the following checks:
•  Pump power cables and control floats properly installed and voltage 

verified.

•  Conduit connections to panel are properly sealed.

•  After installing the pump into the containment area, with adequate 

submergence, open the discharge valve fully. Start the unit using 

manual controls. If flow is appreciably less than rated performance, 

pump may be air locked. To expel trapped air, jog the unit several 

times, using the manual controls.

•  Have a qualified electrician take voltage and current measurements  

with the pump running. Record these readings in the space provided 

in the 

“Owner’s Information”

 section on page 1 of this manual for future 

reference. 

ADJUSTMENT PROCEDURE

Pumps:  No adjustments are required.
Floats:   Nonautomatic - Refer to the system drawing or to the panel 

wiring schematic for the desired location of each float switch 

setting.

 

Automatic - Float is factory set to provide approximate on/off 

levels as follows:

 

SERIES 

ON 

OFF

 X160/X190  19-1/2" 

10"

 X280 

19-3/4" 

10"

 X290 

19-1/2" 

10"

 

NOTE:   For non-automatic Class II, Div.1 (alternate Zone  20  designation)  

rated  models,  the  float  switch  “off”  level  must be set to 

a minimum of 10 inches for the X160-X190, X280, X290 series 

and 13 inches for the X400 series.

 

A tighter pumping range can be set by moving the float stop 

closer to the float thereby lowering the "on" point.

Valves:  Discharge valves should be placed in the fully open position. 

Systems should not be operated for extended periods of time 

with the discharge valves partially closed due to damaging 

the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the following is rec-

ommended:
Pumps:  If pit is to remain dry, then the pump can remain in the pit. 

With the pump in the pit, it should be operated for five minutes 

once every three months. If the pit is to remain wet, the pump 

should be removed and stored as noted above.

Panels:  The panel should have all openings sealed to prevent moisture 

and dust from entering the enclosure. Prior to restarting system, 

the panel should be inspected for presence of moisture and any 

loose connections.

Valves:  Consult the valve/actuator supplier for information concerning 

these systems components.

Summary of Contents for MX161

Page 1: ...63 X165 X185 X186 X188 X189 X191 ZOELLER HAZARDOUS LOCATION PUMPS Class I Division I Groups C D and Class 1 Zone 1 Groups IIA IIB Gas Areas OR Class II Division I Groups E F G and Zone 20 Dust Areas M...

Page 2: ...tomintake design to reduce clogging and seal failures If a check valve is incorporated in the installation a vent hole approx 3 16 must be drilled in the discharge pipe below the check valve and pit c...

Page 3: ...450 200 1 60 12 6 6 1 26 8 F 2 0 1 8 JX165 1 3450 200 3 60 7 5 4 8 31 1 M 3 6 3 2 FX165 1 3450 230 3 60 7 4 3 8 29 8 N 5 5 4 7 GX165 1 3450 460 3 60 3 7 2 1 14 9 N 21 8 19 0 BAX165 1 3450 575 3 60 3 0...

Page 4: ...AX292 1 2 3450 575 3 60 2 4 1 7 11 3 U 38 0 33 0 DX293 1 3450 230 1 60 10 2 6 6 20 1 E EX293 1 3450 230 1 60 10 2 6 6 20 1 E 3 0 2 6 HX293 1 3450 200 1 60 12 0 7 5 26 8 F IX293 1 3450 200 1 60 12 0 7...

Page 5: ...structionsareincludedwiththerailsystem and basin instructions If pump is being retrofitted to an existing rail system accessory parts may be required Consult the factory and advise make and model of r...

Page 6: ...6 4 2 0 10 5 10 20 15 20 FLOW PER MINUTE 110 160 240 320 400 30 40 50 60 70 80 100 90 X282 560 480 640 150 130 120 140 X292 170 160 180 X284 80 14 12 10 8 TOTAL DYNAMIC HEAD 25 30 35 40 45 22 20 18 16...

Page 7: ...ILABLE 8 9 16 217 mm 1 1 2 NPT CONDUIT CONNECTION 24 15 16 21 1 2 4 29 32 125 mm 6 1 16 154 mm 116 mm 222 mm 165 mm 633 mm 546 mm 4 9 16 116 mm SK2506 5 127 mm 8 9 16 217 mm 6 5 16 160 mm 2 NPT OR 3 N...

Page 8: ...or strain relief Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician EXPLOSION PROOF WIRING DIAGRAMS X160 X180 X190 X280 X290 X400 SE...

Page 9: ...ACK OR WHITE BLACK TRACER BLACK OR WHITE BLACK TRACER MOTOR AUXILIARYWINDING MAINWINDING OVERLOAD YELLOW RED BLUE POWER CORD M1 M1 M2 M2 RED GREEN 3 3 RED BLUE 2 2 1 1 CAPACITOR ORANGE WHITE BLACK 330...

Page 10: ...and switch any two power leads Turn power back on and retest for proper rotation SENSOR WIRES See pages 8 and 9 The power and sensor wires are contained in the same cord The green wire is a ground con...

Page 11: ...properly sealed After installing the pump into the containment area with adequate submergence open the discharge valve fully Start the unit using manual controls If flow is appreciably less than rate...

Page 12: ...age thermal overload open impeller clogged float switch held down or defective incorrect wiring in control panel water in cap assembly Incorrect voltage impeller blocked negativehead dischargelowertha...

Reviews: