background image

10

© Copyright 2020 Zoeller

®

 Co. All rights reserved.

 Repair and service must be performed by a firm approved 

by Zoeller Company to repair a pump with an explosion-proof motor in 

accordance to the guidelines listed in Policy # FM0212-3d. Contact  the 

Zoeller Product Support Department for additional information.

 

If the motor housing or cord cap is disassembled or repaired 

by a firm NOT approved to work on explosion-proof motors, the explosion proof 
rating is void, and the cCSAus tag MUST BE REMOVED FROM THE PUMP.

SAFETY PROCEDURES

 

For your protection, always disconnect pump 

and panel from its power source before handling.

 Never enter the basin until it has been properly 

vented and tested. Any person entering a basin should be wearing 

a harness with safety rope extending to the surface so that they can 

be pulled out in case of asphyxiation. Sewage water gives off methane 

and hydrogen sulfide gases, both of which can be highly poisonous.

Installation and checking of electrical circuits and hardware should be 

performed by a qualified electrician.

Pump is never to be lifted by power cord.

 Unit must be cleaned and disinfected, inside the pumping 

chamber and all exterior surfaces, prior to servicing.

GENERAL MAINTENANCE

GENERAL SYSTEM INSPECTION

Before the system is placed into operation, it should be inspected 

by a qualified technician.

 

Wiring and grounding must be in accordance 

with the National Electrical Code and all applicable local codes 

and ordinances.

LUBRICATION PROCEDURES

No lubrication is required.

If pumps are to be stored for more than six months, refer to short term 

storage procedure in the Operation section.

PREVENTIVE MAINTENANCE

Preventive maintenance is recommended to ensure a long service 

life from the product. Provided is a suggested maintenance schedule.

Every six months:

•  Inspect and test system for proper operation.

•  Check for proper and unobstructed float operation.

•  Listen for proper check valve operation.

Every 5 years or 10,000 hours of operation:

•  Remove pump, inspect and service using a Zoeller rebuild kit.

•  Flush and clean basin.

It is very important that these units be connected for proper rotation.  Since no rotating parts are visible without removing the pump from the pit, the rota-
tion on 3 phase units should be checked before installation into the pit as follows:

After the proper electrical connections are made, momentarily energize the pump observing the direction of kick back due to starting torque. The 

rotation is correct if the kick back is in the opposite direction of the rotation arrow. If the rotation is not correct, disconnect power and switch 

any two power leads. Turn power back on and retest for proper rotation.

SENSOR WIRES (See pages 8 and 9)

  The power and sensor wires are contained in the same cord. The green wire is a ground connection. All wires must terminate in the control panel.

The following should be noted:
(1)  The thermal sensors are normally closed and mounted adjacent to the motor windings. If internal temperatures exceed a maximum limit, 

the pump will deactivate. On 3 phase models connect the white and red wires with the black tracer to the control panel's thermal cut-out 

terminals. The pump is able to restart once the motor cools down. Continued deactivation of this circuit requires the attention from mainte-

nance personnel.

(2)  The seal failure wires are connected to a 330K ohm moisture detection circuit. An indicator light will activate whenever water is present in 

the shaft seal cavity or cord cap assembly. Whenever the seal leak light is activated, indicating the entry of moisture into the pump, it should 

be removed and serviced in order to avoid damage to the motor.  Moisture sensor circuit can be checked for continuity (complete circuit) 

with a (Volt-OHM-Meter).  Set the VOM to read resistance and connect the VOM leads to the moisture sensor wires.  The VOM should 

read approximately 330k Ohms.  Resistance readings significantly lower indicates an entry of moisture into the pump.  If VOM reading is 

open then a problem exists with moisture detection circuit.

(3)  The green wire shall be connected to a ground lug in the panel.  Check resistance between the green ground conductor and all other wires.  

This resistance reading should indicate an open circuit.  If VOM reading returns a reading other than open, then a problem exists with the 

sensor circuit wiring or cordage and the pump should be taken to an approved repair station.  

CONTROL PANELS

These pumps are nonautomatic and they require a control panel with intrinsically safe float and moisture sensor circuits. A motor starter circuit, 

control circuit, and high-water alarm circuit within the panel are standard features. Enclosures rated for outdoor use and alternating relays are 

often required. The following should be noted.
(1)  The seal failure sensor and thermal sensor (3 phase only) protection require that interfacing terminals and functions be incorporated into 

the panel.  

(2)  All 3 phase pumps require overload protection in panel. Use with approved motor control that matches motor input in full load amperes with 

overload element(s) selected or adjusted in accordance with control instructions.

(3)  Lightning arrestors, condensation heaters and elapsed-time meters are optional features that provide added protection.

INSTRUCTIONS FOR CHECKING ROTATION OF THREE PHASE UNITS

Summary of Contents for MX161

Page 1: ...63 X165 X185 X186 X188 X189 X191 ZOELLER HAZARDOUS LOCATION PUMPS Class I Division I Groups C D and Class 1 Zone 1 Groups IIA IIB Gas Areas OR Class II Division I Groups E F G and Zone 20 Dust Areas M...

Page 2: ...tomintake design to reduce clogging and seal failures If a check valve is incorporated in the installation a vent hole approx 3 16 must be drilled in the discharge pipe below the check valve and pit c...

Page 3: ...450 200 1 60 12 6 6 1 26 8 F 2 0 1 8 JX165 1 3450 200 3 60 7 5 4 8 31 1 M 3 6 3 2 FX165 1 3450 230 3 60 7 4 3 8 29 8 N 5 5 4 7 GX165 1 3450 460 3 60 3 7 2 1 14 9 N 21 8 19 0 BAX165 1 3450 575 3 60 3 0...

Page 4: ...AX292 1 2 3450 575 3 60 2 4 1 7 11 3 U 38 0 33 0 DX293 1 3450 230 1 60 10 2 6 6 20 1 E EX293 1 3450 230 1 60 10 2 6 6 20 1 E 3 0 2 6 HX293 1 3450 200 1 60 12 0 7 5 26 8 F IX293 1 3450 200 1 60 12 0 7...

Page 5: ...structionsareincludedwiththerailsystem and basin instructions If pump is being retrofitted to an existing rail system accessory parts may be required Consult the factory and advise make and model of r...

Page 6: ...6 4 2 0 10 5 10 20 15 20 FLOW PER MINUTE 110 160 240 320 400 30 40 50 60 70 80 100 90 X282 560 480 640 150 130 120 140 X292 170 160 180 X284 80 14 12 10 8 TOTAL DYNAMIC HEAD 25 30 35 40 45 22 20 18 16...

Page 7: ...ILABLE 8 9 16 217 mm 1 1 2 NPT CONDUIT CONNECTION 24 15 16 21 1 2 4 29 32 125 mm 6 1 16 154 mm 116 mm 222 mm 165 mm 633 mm 546 mm 4 9 16 116 mm SK2506 5 127 mm 8 9 16 217 mm 6 5 16 160 mm 2 NPT OR 3 N...

Page 8: ...or strain relief Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician EXPLOSION PROOF WIRING DIAGRAMS X160 X180 X190 X280 X290 X400 SE...

Page 9: ...ACK OR WHITE BLACK TRACER BLACK OR WHITE BLACK TRACER MOTOR AUXILIARYWINDING MAINWINDING OVERLOAD YELLOW RED BLUE POWER CORD M1 M1 M2 M2 RED GREEN 3 3 RED BLUE 2 2 1 1 CAPACITOR ORANGE WHITE BLACK 330...

Page 10: ...and switch any two power leads Turn power back on and retest for proper rotation SENSOR WIRES See pages 8 and 9 The power and sensor wires are contained in the same cord The green wire is a ground con...

Page 11: ...properly sealed After installing the pump into the containment area with adequate submergence open the discharge valve fully Start the unit using manual controls If flow is appreciably less than rate...

Page 12: ...age thermal overload open impeller clogged float switch held down or defective incorrect wiring in control panel water in cap assembly Incorrect voltage impeller blocked negativehead dischargelowertha...

Reviews: