NOTICE TO INSTALLER:  Instructions must remain with installation.

 

Congratulations on the purchase of the Zoeller 71 Series submersible 

grinder pump. Zoeller Grinder Pumps are designed for grinding and pumping 

sanitary sewage from submersible lift stations.  The pump is intended to grind 

and pump reasonable quantities of disposable diapers, sanitary napkins, 

paper towels, rubber materials, plastics, cigarette butts and other items 

normally found in sanitary sewage applications. For over seventy years the 

name Zoeller has represented the standard for submersible dewatering and 

sewage pumps. The same high quality workmanship and easy maintenance 

design has been incorporated into this line of heavy-duty submersible grinder 

pumps. This Zoeller pump will provide years of trouble-free service when 

installed according to the manufacturers’ recommendations.

OWNER’S MANUAL

71 SERIES SUBMERSIBLE GRINDER UNITS

 

This manual incorporates the installation, operation, maintenance, and 

service instructions into one document to aid in the ownership of a Zoeller 

submersible wastewater product. Please read and review this manual before 

installing the product. Follow the steps and procedures listed on ZM1074_Eb 

for a proper start-up. Many items contained within, when followed correctly, 

will not only ensure a long and problem-free life for the pump, but also 

save time and money during installation. Reference ZM1788_Ec for repair 

manual on 71 Series Grinder Pumps. Should further assistance be necessary 

please call our Technical Service Department at +1 (502) 778-2731 or email: 

[email protected].

Table of Contents

Safety Instructions .......................................................................1
Limited Warranty ..........................................................................2
Preinstallation Information ..........................................................3
Electrical Data ...............................................................................3
Typical Sewage Installation  ........................................................4
Pump Wiring Instructions .........................................................5-6
Operation .......................................................................................7
Maintenance ..................................................................................7
Service Checklist ..........................................................................8

Safety Instructions

TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MA-

JOR PROPERTY DAMAGE, READ AND FOLLOW ALL SAFETY  

INSTRUCTIONS IN THIS MANUAL AND ON THE PUMP.

THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION 

AND OPERATION OF THIS UNIT AND MUST BE KEPT WITH 

THE PUMP.

This is a 

SAFETY ALERT SYMBOL.

When you see this symbol on the pump or in the 

manual, look for one of the following signal words 

and be alert to the potential for personal injury or 

property damage.

Warns of hazards that 

WILL

 cause serious personal    

injury, death or major property damage.

Warns of hazards that 

CAN 

cause serious personal 

injury, death or major property damage.

Warns of hazards that 

CAN 

cause personal injury 

or property damage.

INDICATES SPECIAL INSTRUCTIONS WHICH ARE 

VERY IMPORTANT AND MUST BE FOLLOWED.

THOROUGHLY REVIEW ALL INSTRUCTIONS AND WARNINGS 

PRIOR TO PERFORMING ANY WORK ON THIS PUMP.

MAINTAIN ALL SAFETY DECALS.

CAUTION

Owner’s Information

REFER TO WARRANTY ON PAGE 2.

Model Number:

 _______________

 Date Code:

  ______________

Serial Number:  Pump 1_____________  Pump 2_____________ 

 Simplex 

  Panel P/N _____________________________

 Duplex 

  Rail System P/N ________________________

Job Name: ____________________________________________
Distributor:

 ____________________________________________

Sales Order Number:

 ____________________________________

Contractor:

 ____________________________________________

Date of Installation:

 _____________________________________

System Readings During Operation: Voltage

_____

 Amps

______

 

IF 

ANY

 INFORMA

TION CHANGES ON THIS SHEET

,  SEE 

ALSO ZM1789.

IF ANY INFORMATION CHANGES ON THIS SHEET,  SEE ALSO ZM1789.

50/60 Hz

MAIL TO:

  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO:

  3649 Cane Run Road • Louisville, KY  40211-1961

(502) 778-2731 • 1 (800) 928-PUMP • 

FAX

 (502) 774-3624

Visit our web site:

zoellerengineered.com

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

Summary of Contents for 71 Series

Page 1: ...Installation 4 Pump Wiring Instructions 5 6 Operation 7 Maintenance 7 Service Checklist 8 Safety Instructions TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MA JOR PROPERTY DAMAGE READ AND FOLLOW ALL SAFETY INSTRUCTIONS IN THIS MANUAL AND ON THE PUMP THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION AND OPERATION OF THIS UNIT AND MUST BE KEPT WITH THE PUMP This is a SAFETY ALERT SYMBOL When you ...

Page 2: ...ng unusual conditions Each Zoeller 71 Series Pump installation is required to have a completed Zoeller Engineered Products Start up Report ZM1074_Eb The report is to be completed by an approved Start up Technician in the presence of the installing contractor A copy of this report will be on file at the Zoeller Engineered Products offices in Louisville KY USA Failure to comply with the requirement ...

Page 3: ...le Allpumpsarefurnished with provisions for proper grounding to help protect you against the possibility of electrical shock 3 Make certain that the control box is within the reach of the pump s power supply cord DO NOT USE AN EXTENSION CORD Extension cords that are too long or too light do not deliver sufficient voltage to the pump motor But more important they could present a safety hazard if th...

Page 4: ...n and free of debris after installation and before operation ZEPA0521 Allinstallationsmustcomplywithallapplicable electrical and plumbing codes including but not limited to governing electrical code local regional and or state plumbing codes etc 1 Electrical wiring and protection must be in accordance with the governing electrical code and any other applicable state and local electrical requiremen...

Page 5: ...per pump one moisture sensor lead from the pump should be hooked to the moisture sensor lead in the panel the other moisture sensor lead from the pump should be hooked to ground to complete the circuit 6 Moisture sensor circuit can be checked for continuity complete circuit with a Volt OHM Meter Set the VOM to read resistance and connect the VOM leads to the sensor cord black and white wires The V...

Page 6: ...S RESISTANCE SEAL FAILURE PROBES PANEL INDUCTION CIRCUIT INTHE CONTROL LEADS MUST BE CONNECTEDTO SEAL FAILURE MOISTURE SENSOR THERMAL THETHERMAL SENSOR LEADS ARETO BE CONNECTED IN SERIES WITH STARTER COIL NOTE 1 SENSOR CABLE WITHTHERMAL AND MOISTURE PROTECTION IS STANDARD ON ALL EXPLOSION PROOF MOTORS SEE NOTE 1 SENSOR CABLE P2 WHITE P1 BLACK W1 RED W2 ORANGE TYPICAL 3 PHASE WIRING DIAGRAM STANDAR...

Page 7: ...x months the following is recommended Pumps If pit is to remain dry then the pump can remain in the pit With the pump in the pit it should be operated for five minutes once every three months If the pit is to remain wet the pump should be removed and stored as noted above Panels The panel should have all openings sealed to prevent moisture and dust from enteringtheenclosure Priortorestartingsystem...

Page 8: ...defective Pit too small D Pump will not shut off Debris clogging cutter mechanism Debris under float switch Float travel obstructed Defective or damaged float switch Magnetic starter contacts shorted Air lock check vent hole E Pump operates but delivers little or no water Check for plugged cutter pump housing pipe or sticking check valve Vent hole clogged or not drilled Discharge head exceeds pump...

Reviews: