background image

10

© Copyright 2020 Zoeller

®

 Co. All rights reserved.

GENERAL

Zoeller pumps are lubricated and tested at the factory prior to shipment 
and require minimum pre-start-up maintenance.

Maximum operating temperature of pump liquid for grinder pumps must 
not exceed 130 °F (54 °C).

These units are designed for intermittent duty sanitary sewage 
applications. If pump is used to dewater areas or pump liquids with 
heavy or abrasive materials, the warranty will be voided.

NAMEPLATE DATA

The nameplate, located on the top of pump, indicates specific information 

about the construction of the pump. The model number and date code 
information should be recorded on the front page in the “Owner’s 
Information” section of this manual.

SHORT TERM STORAGE

Do not install pump until permanent electrical power is available and 
system is operational. 

 When not in use,  the pump should be stored, 

and the following is advised:

•  Store pump inside whenever possible or cover with some type of protective 

covering.

•  Tape or seal in plastic bag the terminal ends of wire leads.
•  Spray coat unpainted surfaces with rust inhibiting oil.
•  The impeller should be rotated every six months in order to keep the 

seals lubricated and not develop a permanent set.

If panel is to be stored, the following is advised:

•  Store the panel inside whenever possible and leave in the shipping 

box.

•  All openings shall be sealed.
•  Store in an upright position.
•  Do not stack anything on top of panel.

START-UP PROCEDURE

Before placing the equipment into operation the following should be 
checked:

•  Clean pit.

•  Pump, float switches, electrical cables and junction box are dry and 

properly installed.

•  Electrical boxes dry, sealed and securely installed.
•  Floats positioned properly.
•  Discharge valves open.
•  3/16” vent hole drilled in pipe between check valve and pump.

Once the above has been verified proceed with the following checks:

•  Pump power cables and control floats properly installed and voltage 

verified.

•  Conduit connections to panel and junction box are properly sealed.
•  After installing the pump into the containment area, with adequate 

submergence, open the discharge valve fully. Start the unit using 

manual controls. If flow is appreciably less than rated performance, 

pump may be air locked. To expel trapped air, jog the unit several 
times, using the manual controls.

•  Have a qualified electrician take voltage and current measurements  

with the pump running. Record these readings in the space provided 
in the 

“Owner’s Information”

 section on page 1 of this manual for future 

reference. 

ADJUSTMENT PROCEDURE

Pumps:  No adjustments are required.
Floats:   Refer to Fig. 4 on page 5 or to the panel wiring schematic for 

desired location of each float switch setting.

Valves:  Discharge valves should be placed in the fully open position. 

Systems should not be operated for extended periods of time 
with the discharge valves partially closed due to damaging 
the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the following is 
recommended:

Pumps:  If pit is to remain dry, then the pump can remain in the pit. 

With the pump in the pit, it should be operated for five minutes 

once every three months. If the pit is to remain wet, the pump 
should be removed and stored as noted above.

Panels:  The panel should have all openings sealed to prevent moisture 

and dust from entering the enclosure. Prior to restarting system, 
the panel should be inspected for presence of moisture and any 
loose connections.

Valves:  Consult the valve/actuator supplier for information concerning 

these systems components.

Operation

Summary of Contents for 7008

Page 1: ...pportDepartment at 1 800 928 PUMP 7867 Owner s Information Table of Contents Safety Instructions 1 Limited Warranty 2 Preinstallation Checklist 3 General Information 4 Pump Wiring Instructions 5 Typical Indoor Prepackaged System 6 Indoor Prepackaged Installation Instructions 7 Typical Outdoor Prepackaged System 8 Outdoor Prepackaged Installation Instructions 9 Operation 10 Cutter Maintenance 11 Se...

Page 2: ...CIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES OR BREACH OF EXPRESSED OR IMPLIED WARRANTY AND ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND OF MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY Some states do not allow limitations on the duration of an implied war ranty so the above limitation may not apply to you Some states do not allowtheexclusionorlimitationofi...

Page 3: ...ed so that the grinder pump will shut off It is recommended to use rigid pipe and fittings and the pit be 24 in diameter for simplex systems and 36 in diameter for duplex systems or larger 4 Grinderinstallationsshouldbecheckedyearlyfordebrisand orbuildupwhich may interfere with the ON or OFF positions of variable level float control switches Repairandservice otherthancutterassemblymaintenance shou...

Page 4: ...ertight seal Installation of electrical panels conduit and connections should be made by a qualified licensed electrician A UL Listed potting kit P N 10 2350 is available from Zoeller Company 4 When installing a pump with a check valve or a rail system with a check valve you must give the pump case time to fill to help prevent air lock when lowering the unit into the liquid The pump case has an ai...

Page 5: ...g Instructions Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician 010415 AUTOMATIC WIRING DIAGRAM 010443 NONAUTOMATIC WIRING DIAGRAM 1 PH FIGURE 4 FIGURE 5 Models WD WH are fully automatic A float switch is included and factory wired in the pump circuit to provide automatic operation once the float switch is secured properly to the...

Page 6: ...CORD SEAL INSPECTION PLATE 3 GROMMET SEAL SWITCH CORD ALARM FLOAT BASIN COVER LIFTING BOLT 16 X 1 4 STEEL 5 16 304 STAINLESS STEEL PUMP PLATE PUMP POWER CORD SILENCE INPUT 1 POWER ON FIELD INSTALLED ALARM 4 RUBBER INLET CAST IRON ADAPTERS OFF 24 NOMINAL TO ALARM PANEL BALL VALVE FIELD INSTALLED GALVANIZED PIPE 1 1 4 X 32 GALVANIZED PIPE 1 1 4 X 12 GRINDER PUMP SINGLE PHASE 2HP 1 1 4 GROMMET SEAL F...

Page 7: ...ould be located in a very low trafficareawithin15 ofthepowerdisconnect Theholeshouldbeat least8 largerindiameterthanthebasininordertoleave4 ofbackfill all the way around the perimeter A minimum of 4 of compacted subbase is also required Backfill and subbase should be 1 8 to 3 4 pea gravel or 1 8 to 1 2 crushed stone Also reference the basin installation instructions included with the unit 6 The 4 ...

Page 8: ...GLASS AFD 1 25 2 Z RAIL 2 CAST IRON CHECK VALVE 3 4 GUIDE RAILS 2 SCH 80 BALL VALVE 2 FLEX BOOT FITTING LOCATION VARIES WITH BASIN DEPTH FLOAT TREE ASSEMBLY 2HP GRINDER PUMP 2 PVC SCH 80 PLBG 1 8 302 STAINLESS STEEL LIFTING CABLE ALARM ON OFF SOLID FIBERGLASS COVER HIGH WATER ALARM OR SIMPLEX CONTROL PANEL FIELD INSTALLED ALARM FLOAT SWITCH MUST OPERATE OFF LOW VOLTAGE TO BE USED WITH QWIK BOX SK3...

Page 9: ...b inner diameter with the hole in the basin Attach the hub to the side of the basin using the sealant and hardware provided 6 The bottom of the excavation can now be properly backfilled compacted and leveled Set basin in hole Ensure the removable cover extends above the finished grade line and the grade slopes awayfromtheunit Backfillandsubbaseshouldbe1 8 3 4 pea gravel or 1 8 1 2 crushed stone Re...

Page 10: ...installed Floats positioned properly Discharge valves open 3 16 vent hole drilled in pipe between check valve and pump Once the above has been verified proceed with the following checks Pump power cables and control floats properly installed and voltage verified Conduit connections to panel and junction box are properly sealed After installing the pump into the containment area with adequate subme...

Page 11: ...rinding both disc and cutter to a 32 micro finish Do not attempt grinding in the field Send parts to a qualified machine shop or return to the factory for repair The disc cutter and shims are a matched set Keep parts together Measure disc before and after resurfacing with micrometer and record measurements 6 After resurfacing the disc and cutter must be flat within 0 001 If the disc has been surfa...

Page 12: ... protective sole shoes and not standing in water Under flooded conditions contact your local electric company or a qualified licensed electrician for disconnecting electrical service to the pump prior to removal Grinder pumps contain oil which becomes pressurized and hot under operating conditions Allow 2 1 2 hours after shut down before servicing pump Condition A Pump will not start or run B Moto...

Reviews: