Three Phase Installation
Three phase pumps are nonautomatic. To operate
automatically, a control panel is required. Follow the
instructions provided with the panel to wire the system.
Before installing a pump, check the pump rotation to
insure that wiring has been connected properly to power
source, and that the green lead of power cord (See wiring
diagram), is connected to a valid ground, Momentarily
energize the pump, observing the directions of kick
back due to starting torque. Rotation is correct if kick
back is in the opposite direction of rotation arrow on
the pump casing. If rotation is not correct, switching of
any two power leads other than ground, should provide
the proper rotation.
Refer to the wiring diagram supplied with specific
electrical control panel for correct cable termination
locations.
NOTE:
Sensor cable includes 5 leads; 2 leads for thermal sensor, 2 leads for moisture sensor, and a green ground lead. Sensor wire colors are as shown.
(N/C)
SENSOR
330K OHMS RESISTANCE
SEAL FAILURE PROBES
PANEL.
INDUCTION CIRCUIT IN THE CONTROL
LEADS MUST BE CONNECTED TO
SEAL FAILURE MOISTURE SENSOR
STARTER COIL
CONNECTED IN SERIES WITH
RECOMMENDED THERMAL SENSOR
THERMAL
T3
T2
T1
L3
L2
L1
POWER CABLE
3 PHASE MOTOR
3Ø VAC
SENSOR CABLE
BLACK
WHITE
ORANGE
RED
GREEN
TYPICAL 3-PHASE WIRING DIAGRAM
ZEPA0038E
PHASE POWER AND SENSOR CORD, LEAD IDENTIFICATION
ZEPA0039E
SEAL FAILURE
BLACK & WHITE
LEAD
GROUND
POWER
CORD
LEAD
SENSOR CORD
GREEN GROUND
BLACK
GREEN
RED
WHITE
SENSOR
LEADS
TEMPERATURE
RED & ORANGE
SENSOR
LEADS
“64 HD SERIES” FOUR CONDUCTOR
AWG. POWER CORD SIZE
MODEL
BHP
230/3PH
460/3PH
6424
25
2 AWG.
2 AWG.
6425
30
2 AWG.
2 AWG.
6426
40
2 AWG.
2 AWG.
6427
50
2 AWG.
2 AWG.
6428
60
2 AWG.
2 AWG.
APPROXIMATE CORD DIAMETER PER GAUGE
18/5 AWG.
.50"
2/4 AWG.
1.38"
NOTE: SENSOR CORD 18/5 AWG. APPROXIMATELY
.50" DIAMETER.