background image

7

© Copyright 2021 Zoeller

®

 Co. All rights reserved.

Operation

GENERAL

Zoeller pumps are lubricated and tested at the factory prior to shipment and require 

minimum pre-start-up maintenance.
Maximum continuous operating temperature of pump liquid for standard model 

pumps must not exceed 140 °F (40 °C). For longest service life all pumps should be 

totally submerged on long pumping cycles and a maximum of 1/2 hour run time per hour.
These units are not designed to handle liquids other than water or sewage. If 

pump is used in water contaminated with heavy, viscous, or abrasive materials, 

the warranty will be voided.

NAMEPLATE DATA

The nameplate, located on the top of pump, indicates specific information about 

the construction of the pump. The model number, date code, and serial number  

information should be recorded on the front page in the “Owner’s Information” 

section of this manual.

SHORT TERM STORAGE

If pump is to be stored, the following is advised:

•  Store pump inside whenever possible or cover with some type of protective covering.

•  Tape or seal in plastic bag the terminal ends of wire leads.

•  Pump is to be stored in an upright position. Seal leaks that occur in storage to 

a pump laying on its side will not be repaired under warranty.

•  The impeller should be rotated every six months in order to keep the seals 

lubricated and not develop a permanent set.

If panel is to be stored, the following is advised:

•  Store the panel inside whenever possible and leave in the shipping box.

•  All openings shall be sealed.

•  Store in an upright position.

•  Do not stack anything on top of panel.

START-UP PROCEDURE

Before placing the equipment into operation the following checked:

•  Correct pump rotation (3 Phase units only).

•  Clean pit.

•  Panel dry and securely installed.

•  Floats positioned properly.

•  Discharge valves open.

•  3/16” vent hole drilled in pipe between check valve and pump.

Once the above has been verified proceed with the following checks:

•  Pump power cables properly connected to panel.

•  Float cables properly connected to panel.

•  Conduit connections to panel are properly sealed.

•  Thermal overload adjustments made in the panel.

•  After installing the pump into the containment area, with adequate submergence, 

open the discharge valve fully. Start the unit using manual controls. If flow is 

appreciably less than rated performance, pump may be air locked. To expel 

trapped air, jog the unit several times, using the manual controls.

•  Have a qualified electrician take voltage and current measurements on the 

black wire of single phase or all three power wires of three phase with the 

pump running. Record these readings in the space provided in the

 “Owner’s 

Information”

 section on page 1 of this manual for future reference. 

After the preoperational functional test has been completed, system is ready for 

operation. Zoeller requires completing a Start-up Report (ZM1074) whenever a 

system is started for the first time or after a system has had a significant change 

take place (i.e. pump replacement, overhaul, etc..). A copy of the Start-up Report 

should remain with the system for future reference.

ADJUSTMENT PROCEDURE

Pumps:  No adjustments are required other than assuring correct rotation.

Panels:  The thermal overloads in the panel  must be set to the F.L.A. rating on 

the pump nameplate (or refer to pump data sheet).

Floats:   Refer to the system drawing for desired location of each float function.

Valves:  Discharge valves should be placed in the fully open position. Systems 

should not be operated for extended periods of time with the discharge 

valves partially closed due to damaging the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the following is recommended:

Pumps:  If pit is to remain dry, then the pump can remain in the pit. With the 

pump in the pit, it should be operated for five minutes once every three 

months. If the pit is to remain wet, the pump should be removed and 

stored as noted above.

Panels:  The panel should have all openings sealed to prevent moisture and dust 

from entering the enclosure. Prior to restarting system, the panel should 

be inspected for presence of moisture and any loose connections.

Valves:  Consult the valve/actuator supplier for information concerning these 

systems components.

 Repair and service should be performed by a Zoeller Pump 

Company Authorized Service Station only.

SAFETY PROCEDURES

 For your protection, always disconnect pump and panel from 

its power source before handling.

 Never enter the basin until it has been properly vented and 

tested. Any person entering a basin should be wearing a harness with safety rope 

extending to the surface so that they can be pulled out in case of asphyxiation. 

Sewage water gives off methane and hydrogen sulfide gases, both of which can 

be highly poisonous.
Installation and checking of electrical circuits and hardware should be performed 

by a qualified electrician.

Pump is never to be lifted by power cord.

 Unit must be flushed and disinfected, inside and out, prior to 

servicing.

GENERAL SYSTEM INSPECTION

Before the system is placed into operation, a system Start-up Report should be 

conducted by a qualified technician.

 Wiring and grounding must be in accordance with the national 

electrical code and all applicable local codes and ordinances.

LUBRICATION PROCEDURES

No lubrication is required.
If pumps are to be stored for more than six months, refer to short term storage 

procedure in the Operation section.

PREVENTIVE MAINTENANCE

Preventive maintenance is recommended to ensure a long service life from the 

product. Provided is a suggested maintenance schedule.

Every month:

•  Check for proper and unobstructed float operation.

•  Listen for proper check valve operation.

•  Duplex Units - Check for even operating times. Uneven times indicate a  

  defective unit, float switch or control.

•  Inspect the panel for any presence of moisture in enclosure, loose connections, and 

general component condition. check out location and  condition of float switches.

Every year:

•  In addition to the monthly checks, the basin should be inspected and cleaned. 

Any defective components should be replaced. Inspect and remove any sand, 

debris, or mud present in the pump basin assembly. 

Every two years:

•  Check insulating oil in motor and seal chambers. Inspect oil for contaminations 

as follows:

•  Clear oil, no burnt odor - Oil, motor and seals are in satisfactory condition.

•  Dark oil, burnt odor - Pump motor has overheated. Check the motor winding resistance 

to ground. Ohm readings of 1 megohm or higher is required. If lower readings are 

present, return the unit to an Zoeller Authorized Service Station for service.

•  Milky, emulsified oil - Seals have failed. Unit must be returned to an authorized 

service facility for service.

•  Dispose of the motor insulating oil properly if replacement is required.

•  Inspect power cables for damage or wear. Replace immediately if damage or 

wear is detected.

•  Inspect impeller for damage or wear. Replace as required by a Zoeller Authorized 

Service Station.

DOUBLE SEAL PUMPS

•  Double seal pumps offer extra protection from damage caused by seal failure.

•  Oil in a motor housing and lower seal cavity must be checked when pump is 

serviced. If oil from the motor housing contains water or other contamination, 

both seals should be replaced during maintenance. Always replace with new 

factory recommended oil and service parts. All repairs must be made by  Zoeller 

Authorized Service Stations.

Maintenance

Summary of Contents for 61 HD Series

Page 1: ...60 for repair manual on 61 HD Series Pumps Should further assistance be necessary please call our Technical Service Department at 1 800 928 PUMP 7867 Table of Contents Safety Instructions 1 Limited Wa...

Page 2: ...manufactured at Zoeller Engineered Product s option provided however that by so doing we shall not be obligated to replace an entire assembly the entire mechanism or the complete unit Major components...

Page 3: ...it be 36 or larger in diameter 3 INFORMATION VENT HOLE PURPOSE It is necessary that all submersible pumpscapableofhandlingvarioussizesofsolidwastebeofthebottomintake design to reduce clogging and seal...

Page 4: ...t gases and odors to the atmosphere through vent pipe per local and state codes 8 Secure power cord to avoid entanglement with variable level float switch mechanism 9 Do not reduce pump discharge pipe...

Page 5: ...and white wires The VOM should read approximately 330k Ohms Resistance readings significantly lower indicate a seal leak with water in the seal chamber If VOM reading is open then a problem exists wi...

Page 6: ...d must be hooked up to validate warranty The sensors must be specified at time of initial pump order and are not available for field installation Sensor wire colors are as shown N C SENSOR 330K OHMS R...

Page 7: ...a system is shutdown for more than six months the following is recommended Pumps If pit is to remain dry then the pump can remain in the pit With the pump in the pit it should be operated for five min...

Page 8: ...ll not shut off Debris under float switch Float travel obstructed Defective or damaged float switch Magnetic starter contacts shorted Air lock check vent hole E Pump operates but delivers little or no...

Reviews: